Electronic circuit protector REX12
Description
The new electronic overcurrent protection REX12 consists of the
supply module EM12-T and the single or double channel electronic
circuit protector REX12-T which allows modular side-by-side mounting.
The modules with a width of only 12.5 mm feature push-in
technology including press release buttons and allow time-saving and
maintenance-free wiring without tools. The supply module is designed
for DC 24 V and 40 A and accommodates max. 10 mm² with wire
end ferrule as a plus (+) supply. On the load output side the circuit
protector can be wired with 2.5 mm².
The new generation of electronic overcurrent protection REX12
combines flexibility with a compact design. It is exactly tailored to the
needs of machine and panel builders. And what is more: no additional
accessories are required when connecting the individual components
electrically and mechanically. This helps save time and money!
Features
Technical data (T
= +23 °C, U = DC 24 V)
amb B
REX12-TAx-xxx circuit protectors
REX12-TA1-107-DC24V-xA
lꢀ
Combination of supply module and electronic circuit protector
Single and double channel selective load protection by means of
electronic trip curve
1-channel
2-channel
lꢀ
ꢀ
REX12-TA2-107-DC24V-xA/xA
lꢀ
lꢀ
Operating voltage UB
DC 24 V (18...30 V)
No accessories required for connecting the components
ꢀ
Width per channel only 12.5 mm (1-channel) or
Closed-circuit current I0
REX12-TA1 1-channel
REX12-TA2 2-channel
6.25 mm (2-channel)
Fixed current ratings from 1 A to 10 A
in ON condition
in ON condition
typically 5 mA
typically 8 mA
lꢀ
lꢀ
lꢀ
lꢀ
lꢀ
lꢀ
Integral fail-safe element, adjusted to current rating
Switching capacitive loads up to 20,000 µF
Manual ON/OFF/reset momentary switch
Clear status indication by means of LED and signal contact Si
Reverse polarity
protection
yes
Power failure
buffering time
up to 10 ms
fixed ratings:
1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A
2 A / 2 A, 4 A / 4 A, 6 A / 6 A
ꢀ
Connection via push-in terminals including orange press release
Current ratings IN
REX12-TA1
REX12-TA2
buttons
Visual status indication
green:
load circuit connected
Benefits
by LED
green/orange blinking:
4
lꢀ
load current warning limit reached 80 %
Saves cost – no further accessories required
Saves time through innovative and flexible mounting and
connection technology
Saves space – with a width of only 12.5 mm for two channels
Provides flexibility through ease of mounting, disassembly and
modular design
lꢀꢀ ꢀ
orange: overload or short circuit until
disconnection
lꢀ
lꢀꢀ ꢀ
red:
- after disconnection due to
overload or short circuit
- after undervoltage release
of operating voltage in ON
condition with autoreset
Device switched off by means
of ON/OFF momentary switch
or no operating voltage
Approvals and standards
OFF:
Approval
authority
Standard
Rated
Current
voltage
rating range
Load circuit
UL
UL
UL 2367
DC 24 V
1 A…10 A
1 A…10 A
Load output
power MOSFET switching output
(plus switching)
UL60947 / cULus508listed DC 24 V
under preparation
Load current
typically 0.8 x IN
warning limit (IWLimit
hysteresis
)
typically 5 %
Overview of ordering number codes
Overload current
disconnection (IOL
with trip times (tOL
typically IOL: IN x 1.05
typically IOL: IN x 1.35
typically IOL: IN x 2.00
typically IOL: IN x 2.50
tOL: 3s
)
)
tOL: 0,5 s
tOL: 0.1 s
tOL: 0.012 s
Supply module
EM12-T01-001-DC24V-40A
REX12-TA1-107-DC24V-1A
REX12-TA1-107-DC24V-2A
REX12-TA1-107-DC24V-3A
REX12-TA1-107-DC24V-4A
REX12-TA1-107-DC24V-6A
REX12-TA1-107-DC24V-8A
REX12-TA1-107-DC24V-10A
circuit protectors:
1-channel
Short circuit
typically at short circuti (ISC) tSC: 0,002 s1)
(see time/current characteristic)
1) depends on the power suplly
trip time (tSC
)
Influence of ambient
temperature on
overload disconnection
see temperature factor table
and load current warning limit
circuit protectors:
2-channel
REX12-TA2-107-DC24V-2A/2A
REX12-TA2-107-DC24V-4A/4A
REX12-TA2-107-DC24V-6A/6A
1646
www.e-t-a.de
1
Electronic circuit protector REX12
Technical data (T
= +23 °C, U = DC 24 V)
Technical data (T
= +23 °C, U = DC 24 V)
amb
B
amb B
General data
Fail-safe element
integral
blade fuse
adjusted to
related current rating IN
IN: 1 A
IN: 2 A
IN: 3 A
IN: 4 A
IN: 6 A
fail-safe IN: 1 A
fail-safe IN: 2 A
fail-safe IN: 3.15 A
fail-safe IN: 4 A
fail-safe IN: 6.3 A
fail-safe IN: 8 A
Housing material
Mounting
moulded
symmetrical rail to EN 60715-35x7.5
Ambient temperature
-25 °C...+60 °C
(without condensation, cf. EN 60204-1)
IN: 8 A
IN: 10 A
fail-safe IN: 10 A
fail-safe IN: 2 A / 2 A
fail-safe IN: 4 A / 4 A
fail-safe IN: 6.3 A / 6.3 A
Storage temperature
Mounting temperature
Humidity
-40 °C...+70 °C
+5 °C…+60 °C
IN: 2 A / 2 A
IN: 4 A / 4 A
IN: 6 A / 6 A
96 hrs / 95% RH 40 °C to IEC 60068-2-
78-Cab, climate class 3K3 to EN 60721
Voltage drop in load circuit at IN and at IN 70% between LINE+ and
LOAD+
Vibration
3g test to IEC 60068-2-6, test Fc
(IEC 60529, DIN VDE 0470) IP30
IN: 1 A
IN: 2 A
IN: 3 A
IN: 4 A
IN: 6 A
IN: 8 A
IN: 10 A
typically 180 mV
typically 110 mV
typically 120 mV
typically 115 mV
typically 170 mV
typically 160 mV
typically 180 mV
IN: 70%
IN: 70%
IN: 70%
IN: 70%
IN: 70%
IN: 70%
IN: 70%
typically 125 mV
typically 80 mV
typically 85 mV
typically 80 mV
typically 110 mV
typically 105 mV
typically 120 mV
Degree of protection
EMC requirements
(EMC directive, CE logo) susceptibility:
noise emission
EN 61000-6-3
EN 61000-6-2
Insulation co-ordination
(IEC 60934)
0.5 kV / pollution degree 2
max. DC 30 V (load circuit)
Dielectric strength
Operating voltage
monitoring
with regard to low voltage with automatic ON and
OFF switching
OFF at typically UB < 16.0 V
ON at typically UB > 17.5 V
Insulation resistance
(OFF condition)
n/a, only electronic disconnection
Approvals
CE logo,
UL 2367, File # E306740,
(UL60947 / UL 508, File # E...)
under preparation
Switch-on delay
- with power ON
channel 1:
channel 2:
typically 100 ms
typically 200 ms
- when switching on via channel 1:
typically 5 ms
typically 100 ms
Ordering number code - REX12-T
ON/OFF momentary
switch or
- after undervoltage
channel 2:
Type
channel 1:
channel 2:
typically 5 ms
typically 5 ms
REX12 Electronic circuit protector with PT connection technology
Mounting method
Disconnection of
load circuit
- manually on the device with the
ON/OFF momentary switch
- after an overload / short circuit
disconnection with storage
(no automatic reset)
T
rail mounting
Design
A
1 load output terminal per channel, fixed current ratings xA
or xA/xA
Number of channels
- temporarily at undervoltage
- at no operating voltage
1
2
1 channel
2 channels
Version
4
Switch-on of load circuit
- momentary switch
ON/OFF
1
without physical isolation
Signal input
without signal input
Signal output:
device can only be switched on
when operating voltage is applied
0
- applying
operating voltage
the device starts up with the condition
last stored
7
status output
Operating voltage
Reset function
a blocked load output (blocked by
overload / short circuit) can externally be
reset by the ON/OFF momentary switch
DC 24 V
voltage rating DC 24 V
Current ratings
1 A
(only 1-channel)
Leakage current in load typically < 1 mA
circuit in OFF condition
2 A
3 A
4 A
6 A
(only 1-channel)
(only 1-channel)
(only 1-channel)
(only 1-channel)
(only 1-channel)
(only 1-channel)
(only 2-channel)
(only 2-channel)
(only 2-channel)
Capacitive loads
up to 20,000 µF
Free-wheeling diode
external free-wheeling circuit at inductive
load (rating according to load)
8 A
10 A
2 A/2 A
4 A/4 A
6 A/6 A
Parallel connection of
several load outputs
not allowed
Status output
REX12 - T
REX12 - T
A
A
1 - 1
2 - 1
0
0
7 - DC24V - 10 A
7 - DC24V - 6 A / 6 A example of 2-channel
example of 1-channel
Status indication REX12-T minus switching signal output
group signalling is implemented in
connection with EM12-T supply module
Screw terminals
LOAD+
0.14 mm2...2.5 mm2, flexible
8 mm...10 mm
Preferred types
Push-in terminal PT 2.5
Stripping length
Preferred types
REX12-TA1
Standard current ratings (A)
Dimensions (w x h x d)
12.5 x 98,5 x 80 mm
2
4
6
10 2/2 4/4 6/6
Mass
REX12-TA1-xxx 1-channel approx. 57 g
REX12-TA2-xxx 2-channel approx. 58 g
x
x
x
x
REX12-TA1-107-DC24V-
REX12-TA2
2
4
6
10 2/2 4/4 6/6
x
x
x
REX12-TA2-107-DC24V-
2
www.e-t-a.de
1646
Electronic circuit protector REX12
Dimensions with connection diagram: REX12-TA1-xxx and REX12-TA2-xxx circuit protectors
ꢇꢈꢉꢊ
ꢇꢋ
ꢒꢑꢍꢕꢎꢒꢕ ꢎꢗꢞ
1ꢋꢉꢊ
ꢂꢁꢠ1ꢋꢐ
ꢂꢁꢠ1ꢋꢐ
ꢡꢄ1ꢐ1ꢝꢝ
ꢡꢄꢋꢐ1ꢝꢝ
ꢭꢎꢮꢔꢙ ꢔꢯꢟꢯ ꢖꢗꢑꢞ
ꢰꢥꢑꢔꢍꢘꢝ
ꢢꢣꢋ4ꢤ
ꢢꢣꢋ4ꢤ
ꢣꢑꢍꢕꢎꢒꢕ ꢱꢲꢪꢐ1ꢋ
ꢛꢉꢊ
ꢝꢄ
ꢃꢑꢞꢔꢍꢕꢎꢗꢦ ꢌꢧꢘꢕꢒꢥ
ꢖꢑꢗ ꢨꢅꢩꢨꢪꢪ ꢎꢍꢫ
ꢗꢔꢌꢔꢕ ꢧꢘꢕꢥ ꢘꢍꢕꢔꢟꢗꢎꢙ
ꢌꢕꢎꢕꢬꢌ ꢘꢍꢫꢘꢒꢎꢕꢘꢑꢍ
ꢝꢄ
ꢝꢄ
ꢋꢯ1
ꢋꢯ1 ꢋꢯꢋ
ꢭꢨꢄꢢ ꢳ
ꢭꢨꢄꢢ ꢳ
ꢘꢍꢌꢕꢎꢙꢙꢎꢕꢘꢑꢍ
ꢎꢗꢔꢎ
ꢑꢏꢔꢗꢎꢕꢘꢍꢟ
ꢎꢗꢔꢎ
1ꢐꢒꢥꢎꢍꢍꢔꢙ
ꢋꢐꢒꢥꢎꢍꢍꢔꢙꢌ
ꢌꢍꢎꢏꢐꢑꢍ ꢌꢑꢒꢓꢔꢕ ꢖꢑꢗ
ꢗꢎꢘꢙ ꢁꢅ 6ꢚꢛ1ꢊꢐꢜꢊꢝꢛꢉꢊ
Time/current characteristic (Tamb = +23 °C, UB = DC – 24 V)
Preferred mounting postion REX12: horizontal
1ꢀꢀꢀ
1ꢀꢀ
1ꢀ
4
1
ꢀꢌ1
ꢀꢌꢀ1
ꢀꢌꢀꢀ1
ꢀꢌꢏ
1
1ꢌꢐ 1ꢌ4 1ꢌ6 1ꢌꢏ
ꢐ
ꢐꢌꢐ ꢐꢌ4 ꢐꢌ6 ꢐꢌꢏ
ꢑ
ꢒꢓꢔ
ꢌꢌꢌꢁꢃꢅꢆꢈ ꢂꢍꢁꢆꢋ ꢉꢎꢂꢂꢆꢇꢁ
Temperature factor / continuous duty
The time/current characteristic depends on the ambient temperature.
In order to avoid premature trip, the rating of the circuit protector has
to be multiplied with a temperature factor and has to be accounted
for when mounted side-by-side (see chapter Technical Information).
Temperature factor table:
ambient temperature [°C]
temperature factor
0
1
10
1
23
1
40
50
60
0,95
0,90
0,85
Note: When mounted side-by-side, the devices can carry max. 80 %
of their rated load or a different rating has to be selected (see chapter
Technical Information).
Note:
With high temperatures, the load current warning threshold “warn limit
typically 0.8 x IN” will be reduced in accordance with the temperature
factor.
1646
www.e-t-a.de
3
Electronic circuit protector REX12
Description – EM12-T supply module
Dimensions EM12-Txx supply module
The EM12-T supply module receives the DC 24 V supply voltage, e.g.
from a switched mode power supply, and distributes it to the mounted
circuit protectors via the integral connector arm of the REX12-T.
The potential-free auxiliary contact in the EM12-T indicates
any detected failures through the circuit protector, e.g. to the
superordinate control unit (CPU).
ꢀꢁ
ꢀ1ꢂꢃ
1ꢣꢂ4
ꢒꢤ1ꢣꢈ
ꢥꢔ1ꢈꢔꢔ1
ꢦꢟꢣ4ꢧ
4ꢔ ꢨ
Technical data (T
= +23 °C, U = DC 24 V)
B
amb
Operating voltage UB
Operating current IB
DC 24 V (18...30 V)
max. 40 A
1ꢖ 14
Reverse polarity protection yes
Quiescent current I0
typically 10 mA
ꢩꢧ
Potential-free auxiliary
change-over contact
max. DC 30 V / 0.5 A
min. 10 V / 1 mA
Group signalling Si
Contact: Si (13) / Si (14)
auxiliary contact, make contact
ꢘꢪꢓꢒ ꢫ1
ꢄꢅꢆꢇꢈꢉꢅ ꢄꢉꢊꢋꢌꢍ ꢎꢉꢏ
ꢏꢆꢐꢑ ꢒꢓ 6ꢔꢕ1ꢃꢈꢖꢃꢗꢕꢂꢃ
normal condition:
auxiliary contact closed
- when ON, load output connected
- when OFF, load output disconnected
ꢘꢆꢙꢌꢑ ꢌꢚꢛꢚ ꢎꢏꢉꢜ
ꢝꢞꢉꢌꢅꢐꢗ ꢟꢉꢅꢍꢆꢊꢍ ꢠꢡꢢꢈ1ꢣ
fault condition:
auxiliary contact open
- after an overload or short circuit
disconnection
- after undervoltage release of operating
voltage in ON condition with autoreset
- at no operating voltage UB in supply
module
Schematic diagram EM12-Txx with REX12-xx
ꢎꢏꢐꢑ 16 ꢒꢓꢔ
Insulation co-ordination 0.5 kV / pollution degree 2
Power failure
ꢊꢋ1ꢅꢌꢍ
ꢕꢊꢖ1ꢅꢌꢍ
14
1ꢙ
buffering time
up to 10 ms
Screw terminals
LINE+
Push-in terminal PT 10
Stripping length
0.5 mm2...10 mm2, flexible
18 mm...10 mm
4
ꢗ ꢘ
Screw terminals
0 V / Si 13 / Si 14
Push-in terminal PT 2.5
Stripping length
0.14 mm2...2.5 mm2, flexible
8 mm...10 mm
ꢀꢈꢉꢊꢄ1
Dimensions (w x h x d)
Mass
12.5 x 98 x 80 mm
approx. 52 g
ꢀꢁꢂꢃꢄ ꢅ1 ꢆꢅꢅꢇ
Number of circuit
protectors to be mounted
side-by-side to EM12
REX12-TA1-x or
REX12-TA2-x
max. 16 pcs
Ordering number code – EM12
Type
EM12
supply module for REX, with PT connection technology
Mounting method
T
rail mounting
Version: communication, interface
01 analog signal
Additional functionality
0 without
Signal input:
0 without signal input
Signal output:
1
signal make contact
Operating voltage
DC 24 V voltage rating DC 24 V
Current ratings
40 A
EM12 -
T
01 - 0
0
1 - DC 24 V
-
40 A
ordering example
4
www.e-t-a.de
1646
Electronic circuit protector REX12
Application example: REX… mounting on or removing from symmetrical rail
ꢀꢁꢂꢂꢃꢄꢅꢁꢆ ꢇꢆꢈ
ꢄꢇꢂ ꢉꢃ ꢄꢊꢁꢋꢃꢌ
ꢐꢃꢈꢁꢗꢃ ꢐꢑꢒꢝꢝꢝ ꢠꢆꢁꢈ ꢆꢇꢔꢊ
ꢍꢎꢋꢏ ꢐꢑꢒ
ꢅꢁꢓꢇꢆꢌꢋ ꢆꢇꢔꢊ
ꢜꢁꢎꢂꢅ ꢐꢑꢒꢝꢝꢝ
ꢋꢔꢌꢃꢞꢉꢟꢞꢋꢔꢌꢃ ꢓꢔꢅꢏ ꢑꢜꢝꢝꢝ
ꢖꢂꢊꢇꢅꢄꢏ ꢓꢔꢅꢏ ꢋꢆꢃꢓꢌꢆꢔꢗꢃꢆꢘ
ꢅꢔꢊꢅ ꢎꢙꢓꢇꢆꢌꢋ ꢇꢂꢌ ꢆꢃꢈꢁꢗꢃ
ꢚꢄꢁꢂꢂꢃꢄꢅꢁꢆ ꢇꢆꢈ ꢄꢇꢂ ꢉꢃ ꢄꢊꢁꢋꢃꢌꢛ
ꢕꢇꢅꢄꢏ ꢁꢂ ꢃꢂꢄꢊꢁꢋꢎꢆꢃ
ꢌꢁꢓꢂꢓꢇꢆꢌꢋ
Application example: REX... replacement or disassembly
ꢒꢓꢋꢁ ꢅꢐꢁꢁꢋꢅꢄꢐꢊ
ꢃꢊꢔ
ꢒꢓꢋꢁ ꢅꢐꢁꢁꢋꢅꢄꢐꢊ
ꢃꢊꢔ
4
ꢎꢏꢂꢂ ꢐꢏꢄ ꢃꢄ ꢊꢈꢑꢆꢄ
ꢃꢁꢑꢂꢋꢉ ꢄꢐ ꢄꢆꢋ ꢊꢃꢈꢂ
ꢀꢁꢂꢃꢄꢅꢆ ꢇꢈꢄꢆ ꢉꢅꢊꢋꢇꢌꢊꢈꢍꢋꢊ
Instructions for installation
Mounting or actuation of the REX connector arm must only be effected
at dead-voltage. For start-up the REX connector arm must be closed.
1646
www.e-t-a.de
5
Electronic circuit protector REX12
Application example: EM12-T with REX12-TA1… and REX12-TA2…
Application example: REX... Locked connector arms
Application example: REX12(D)-T... distance
between cable duct and connector arm
6ꢈ
4
ꢀꢁꢂꢂꢃꢄꢅꢁꢆ ꢇꢆꢈꢉ ꢄꢇꢂ
ꢊꢃ ꢋꢁꢄꢌꢃꢍ ꢎꢏꢅꢐ
ꢃꢂꢄꢋꢁꢉꢑꢆꢃ
All dimensions without tolerances are for reference only. E-T-A reserves the right change
specifications at any time in the interest of improved design, performance and cost effective-
ness, the right to make changes in these specifications without notice is reserved. Product
markings may not be exactly as the ordering codes. Errors and omissions excepted.
6
www.e-t-a.de
1646