CRD5170-300-5 [ETC]
TRANSDCR DGTL RS485 300VAC/5AAC;型号: | CRD5170-300-5 |
厂家: | ETC |
描述: | TRANSDCR DGTL RS485 300VAC/5AAC |
文件: | 总2页 (文件大小:313K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Data Stream RS485 Digital Transducer
The CRD5100 Series Data Stream Digital Transducers are designed for
complete monitoring of electrical power systems. The digital technolo-
gy is used to measure voltage, current, power frequency and energy in
single and three phase designs. The data is streamed over an RS485
IEEE bus which enables multiple transducers to communicate thru a sin-
gle master connection. These advanced sensors are ideal for entire
plant or zone monitoring. Also, the communication alagorithm can be
pre-ordered with ASCII based control or modified MODBUS based
control.
DIN RAIL / PANEL MOUNT
Sensing
Voltage, True RMS
Current, True RMS
CRD5110
Single Element - .26” (6.5) Window
150 to 300 VAC
Active Power, bi-directional
Active Energy, bi-directional
Reactive Power, bi-directional
Reactive Energy, bi-directional
Power Factor
B
1 to 25 AAC Input Range
Frequency
Applications
Sub-Metering
Motor Loads
Uninterruptible Power Systems
Remote Monitoring
Load Shedding
CRD5150
Two Element - .26” (6.5) Window
150 to 300 VAC
Energy Management
1 to 25 AAC Input Range
Features
35mm DIN Rail or Panel Mount
Red LED - Flashes when Power is Connected
Red & Green LED Flash during Communication
24 VDC powered
Use with external current transformers
Highest precision available
Connection diagram printed on case
Regulatory Agencies
CRD5170
Three Element - .26” (6.5) Window
150 to 300 VAC
1 to 25 AAC Input Range
PART NUMBERS
CRD5110
CRD5150
CRD5170
1 Element, AC Multifunction RS485 Digital Transducer
-
-
3 Phase, 3-Wire AC Multifunction RS485 Digital Transducer
3 Phase, 4-Wire AC Multifunction RS485 Digital Transducer
-
-
-
-
1
5
-
-
-
-
0-1 AAC
0-5 AAC
0-15 AAC
0-25 AAC
Note: Add an M at
the end for MODBUS
CRD5110-150-5-M
150
300
-
-
0-150 VAC
0-300 VAC
15
25
Available up to and including 600 VAC
Above 30 AAC must use 5 amp CT
The Professional
Energy Monitoring
Company
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
M
N TI
13
ISO 9001:2008 Quality Management System
RS485 Digital Transducer
SPECIFICATIONS
Basic Accuracy: .......................0.5%
Calibration: ..............................True RMS Sensing
Thermal Drift: ..........................500 PPM/°C
Torque Specifications: ....................3.0 inch lbs (0.4Nm)
Response Time: .......................250 ms. max. 0-90% FS
Relative Humidity: .............5% to 95%, Non-Condensing
Output Resolution: ..................................................16 bit
Transducer fanout on common bus: ...................64 max.
Operating Temperature : ..........0°C to +60°C
1
Installation Category: ..............CAT II
Vibration Tested To: .................IEC 60068-2-6,1995
Pollution Degree: ....................2
Insulation Voltage: ..................2500 VDC
Altitude: ..................................2000 meter max
Frequency Range: .................20 Hz - 5 KHz
Baud Rate : ...............1200, 2400, 4800, 9600,19.2K .bps
A/D Conversion Type: ..................4th order Delta Sigma
3
Device Address : ............................................00 to FF
3
Data Format: .... .....................................................ASCII
Supply Current:..................Typical 30mA
Max 30mA
MTBF: ....................................Greater than 100K hours Weight:.. ..............................................................0.5 lbs.
Cleaning: ................................Water-dampened cloth
B
Supply Voltage : ......................24 VDC 10%
2
1) RH 5% to 95%, non-condensing 2) 0.4% max. ripple Vpp
no flow control, 1 stop bit
3) Factory default settings:
address 01, baud rate 9600, no parity,
LINE
LINE
L1
L2
N
N
L1
1
2
3
4
1
2
3
4
LOAD
9
8
7
6
5
+
-
9
8
7
6
5
+
-
485
-
485
-
+
+
L3
L2
LOAD
L1
SUPPLY
LOAD
SUPPLY
CRD5150 Dual Element, 3-Wire
CRD5110 Single Element, 2-Wire
LINE
L2
L1
1
N
L3
LINE
L2
L1
L3
1
2
3
4
1
2
3
4
9
8
7
6
5
485
9
8
7
6
5
+
-
485
-
SUPPLY
+
LOAD
LOAD
SUPPLY
CRD5170 3 Element, 4-Wire
CRD5150 Dual Element, 3-Wire
CRD485-232
RS485 to RS232 Converter Accessory
Connection Diagram
TX
Connect PC to RS485 Bus
RED INDICATIOR LED
GREEN INDICATOR LED
RX
1
2
3
4
[26.6]
1.05
DATA +
9
DATA-
DATA STREAM
TRANSDUCER
8
7
6
5
GND
COM
RS232
CRD485-232
[3.3]
.13
OPTIONAL
MOUNTING
+5VDC
DIN RAIL
MOUNTING
CLIP
[73.1]
2.88
[83.3]
3.28
[25]
.98
GND
[31.0]
1.22
+
-
DB 9, FEMALE
SUPPLY
[6.6]
[78.7] .26
3.10
[76.7]
3.02
[64]
2.52
MAX
ASCII Simplified Programming Commands
[5.6]
.22
TYP
[28.3]
1.12
A simplified data structure is used with only 6 commands required for full control of
the transducer. Commands are : Read Transducer Name, Read Configuration, Set
Configuration, Read Measurements, Read Energy Totalizer and Clear Energy
Totalizer. For illustration, the following commands are used to read data from a
CRD5170 3 Phase, 4 Wire Transducer with a device address of 00.
Command Transducer to Read Data: #00A<cr>
[88.7]
3.49
[36.6]
1.44
[31.0]
1.22
[35.0]
1.38
[13.5]
.53
[19.8] [19.8]
.78
.78
Transducers Response: >+[% FS Voltage
]+[% FS Current ]+[% FS
L1
L1-N
Voltage
]+[% FS Current ]+[% FS Voltage
]+[% FS Current ,][+/- % FS
L2-N L2 L3-N
L3
Power][+/-% FS VARS][+/-Power Factor][Frequency]<cr>
Command Transducer to Read Energy Totalizer: #00W<cr>
Transducer Responds: 01[+/-KWHr]{\[+/-KVHr][check sum]<cr>
Note: This is for illustration purposes only, See Applications Guides (Section I
for complete instructions.
OUTLINE DRAWING
The Professional
Energy Monitoring
Company
3500 Scarlet Oak Blvd. St. Louis MO USA 63122 V: 636-343-8518 F: 636-343-5119
Web: http://www.crmagnetics.com E-mail: sales@crmagnetics.com
M
N TI
14
ISO 9001:2008 Quality Management System
相关型号:
©2020 ICPDF网 联系我们和版权申明