D34900000230 [ETC]
Channel Generators; 频道发电机型号: | D34900000230 |
厂家: | ETC |
描述: | Channel Generators |
文件: | 总3页 (文件大小:79K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
®
Channel Generators
Types FPD 1901, D 3490 0000
Du line
Fieldbus Insta lla tionbus
• Generates 8, 16, 32, 64 or 128 channels
• Number of sequences selectable
• Quartz-controlled oscillator
• Cable compensation
• Stop-function
• Plug-in type (FPD)
• DIN-rail mounting type (D3490) (EN 50022)
• LED-indication for supply
• LED-indication for supply and Dupline® carrier
• AC or DC power supply
FPD
D 3490
Product Description
Ordering Key
FPD 1901 024
Type: Dupline®
Channel generator
Supply
FPD 1901: standard channel systems, especially suitable
generator for all Dupline® sys- for building installations. Iso-
tems. Number of channels lation according to IEC
selectable by means of code 60664/60664 A reinforced.
module.
Increased Dupline® output
D 3490 0000: Standard chan- power for connection of non-
nel generator for all Dupline® powered Dupline® transmitters.
Type Selection
Supply
Ordering no.
No. of channels selectable
1, 2 or 3 sequences
Ordering no.
No of channels selectable
1, 2 or 3 sequences
24 VAC
120 VAC
220 VAC
FPD 1901 024
FPD 1901 120
FPD 1901 220
D 3490 0000 024
D 3490 0000 115
D 3490 0000 230
15 to 30 VDC
FPD 1901 824
D 3490 0000 824
Code modules:
1 sequence
2 sequences
3 sequences
FMK 8 to FMK 128
FMK 16-2 to 128-2
FMK 16-3 to 128-3
FMK 8 to FMK 128
FMK 16-2 to 128-2
FMK 16-3 to 128-3
Input/Output Specifications
FPD 1901 ...
(1, 2 or 3 sequences)
D 3490 0000
(1, 2 or 3 sequences)
Inputs
Function
1 contact
Stop
1 contact
Stop
Open loop voltage
Short-circuit current
Operating time for signal "1" ≤ 1 s
Operating time for signal "0" ≤ 10 ms
Contact resistance
Cable length
12 VDC
5 mA
12 VDC
1.25 mA
≤ 1 s
≤ 10 ms
≤ 100 W
≤ 3 m
≤ 100 W
≤ 3m
Insulation voltage
Input - Dupline®
Outputs
Number of outputs
Output voltage
Current
None
None
Dupline® carrier
1
Dupline® carrier
1
8.2 VDC
≤ 40 mA
≤ 600 s
8.2 VDC
≤ 70 mA
≤ 60 s
Short-circuit protection
Specifications are subject to change without notice (28.09.99)
1
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
FPD 1901, D 3490 0000
®
Du line
Fieldbus Insta lla tionbus
Input/Output Specifications (cont.)
FPD 1901 ...
(1, 2 or 3 sequences)
D 3490 0000
(1, 2 or 3 sequences)
Output (cont.)
Output impedance
-
≤ 25 Ω
Sequence time
Time for 1 pulse train (± 1%):
15.63 ms *
23.44 ms *
39.06 ms *
70.31 ms *
132.80 ms *
100% (refer to "Cable Selection")
Time for 1 pulse train (± 1%)
15.63 ms *
23.44 ms *
39.06 ms *
70.31 ms *
132.80 ms *
100% (refer to "Cable Selection")
Code module FMK 8
Code module FMK 16
Code module FMK 32
Code module FMK 64
Code module FMK 128
Distance to transmitters
* When using 2 or 3 sequences, the sequence time will be 2 or 3 times higher.
Supply Specifications
General Specifications
Power supply AC types
Rated operational voltage
through pins A1 & A2
Overvoltage cat. III (IEC 60664) Power ON delay
≤ 1 s
Indication for
Supply ON
220 230 VAC +6%, -15% (IEC 60038)
120 120 VAC ± 10% (IEC 60038)
024 24 VAC ± 10%
LED, green
LED, yellow
Dupline® carrier*
Environment
through term. 21 & 22 230 230 VAC ± 15% (IEC 60038)
115 115 VAC ± 15% (IEC 60038)
Degree of protection
Pollution degree
Operating temperature
Storage temperature
IP 20
3 (IEC 60664)
-20° to +50°C (-4° to +122°F)
-50° to +85°C (-58° to +185°F)
024 24 VAC ± 15%
Frequency
45 to 65 Hz
≤ 40 ms
Typ. 2.5 VA
Voltage interruption
Rated operational power
Rated impulse withstand
voltage
Humidity (non-condensing)
20 to 80%
Mechanical resistance
Shock
Vibration
220 4 kV
120 2.5 kV
024 800 V
15 G (11 ms)
2 G (6 to 55 Hz)
Dimensions
Material
(see "Technical Information")
Dielectric voltage
Supply - Dupline® FPD 1901 None
D-housing, H4-housing
D 3490 0000 ≥ 4 kVAC (rms)
Supply - Inputs FPD 1901 ≥ 2 kVAC (rms)
D 3490 0000 ≥ 4 kVAC (rms)
Weight
FPD 1901
AC type 200 g
DC type 125 g
Power supply DC types
Rated operational voltage
through pins A1 & A2
Ripple
Reverse polarity protection
Current consumption
Inrush current
Overvoltage cat. III (IEC 600664)
D 3490 0000
250 g
Approvals
CSA, UL (only FPD 1901)
824 15 to 30 VDC (ripple included)
≤ 3 V
Yes
≤ 90 mA
≤ 1 A
Rated impulse withstand
voltage
800 V
Dielectric voltage
Supply - Dupline®
Supply - Input
None
≥ 200 VAC (rms)
* Not applicable to FPD 1901
Mode of Operation
The channel generators gen- mission stops immediately, vated whenever new Dupli- tical status until the channel
erate pulse trains and syn- and 8 VDC is supplied to the ne® modules are to be con- generator changes the duty
chronize the transmission two wires keeping all con- nected to the system or cycle for the respective
signals for an entire system nected Dupline® modules whenever Dupline® modules channel. This change of
of Dupline® modules. At the ready for operation. When need to be removed or duty cycle causes the recei-
same time they supply non- the stop-function is deacti- replaced.
vers to change their status.
powered Dupline® transmit- vated, a delay of approx. 2 s The selection of 2 or 3 se-
ters. If the stop-function is elapses before the signal quences means that 2 or 3
activated (pins 2 & 3 inter- transmission is resumed.
consecutive signals of a
connected), the signal trans- The stop input must be acti- transmitter must show iden-
2
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
FPD 1901, D 3490 0000
®
Du line
Fieldbus Insta lla tionbus
Mode of Operation (cont.)
In Dupline® systems with digi-
tal transmitters and receivers
the use of 2 or 3 sequences is
only recommended in cases
of extremely long cabling in
high noise level environment.
Application of 2 or 3 se-
quences results in absolutely
correct transmission but also
in a slow reaction time for the
system.
Note:
tion of pins 4 & 6 (FPD 1901) Note: It is highly recommend-
or terminals 4 & 1 (D 3490 ed to place the channel ge-
0000. For inductive cables a nerator in the middle of a
separate capacitor of less Dupline® system.
than 1 µF may be mounted
between pins 3 & 6 (FPD
1901) or terminals 1 & 2 (D
3490 0000). But in the majori-
ty of cases the cable appears
to be capacitive requiring no
additional capacitor.
- Do not use 2 or 3 sequen-
ces if analog modules or
counters are connected to
the system.
- Do not use 3 sequences if
the modem interface D9091
... is used in the system.
-
The transmission distance
of a Dupline® network is
reduced by 33% when
using 2 or 3 sequences, com-
pared to the figures given
under "Cable Selection".
HF disturbance that is indu-
ced to the Dupline® may be
suppressed by interconnec-
Operation Diagram
Power supply
Dupline® carrier
Stop function
Wiring Diagrams
FPD 1901 AC supply
D 3490 0000
Noise
suppression
Stop
Noise
suppression
Stop
~
~
(+) (-)
AC
Power supply
Power Supply
S: signal wire
S: signal wire
FPD 1901 824 DC supply
Accessories
Socket◊
Socket cover
D 411
BB 5
Hold down spring◊
Front mounting bezel
DIN-rail for D 411
HF
FRS 2
FMD 411
Noise
suppression
Stop
For further information refer to "Accessories".
+
-
DC
Power Supply
S: signal wire
Specifications are subject to change without notice (28.09.99)
Dupline® is a registered trademark. A product of the CARLO GAVAZZI Group
3