GC42-1128 [ETC]
;型号: | GC42-1128 |
厂家: | ETC |
描述: |
|
文件: | 总3页 (文件大小:238K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Relays
New Series GC
10A, 230/240VAC, 300VDC
SINGLE THROW FOUR/SIX/EIGHT/TEN POLE
Series GC
Force guided relay rated for 10A, 230/240 Vac, 300 Vdc
Available in 4, 6, 8 or 10 pole configuration. See Table 1 for part
numbers.
ELECTRICAL SPECIFICATIONS
GENERAL SPECIFICATIONS
Parameter
Min Typ Max Units
FEATURES:
Operate Time (See Note 1)
Release Time (See Note 1)
Switching Frequency
Shock (11 msec, See Note 3)
Vibration (10-100 Hz, See Note 3)
Electrical Life
30
7
msec
msec
Hz
• Force Guided Contacts per EN50205:
Consists of at least one NO and one NC
contact mechanically linked. This allows
the contact‘s behavior to be pre-
determined and the user the ability to
monitor the contact.The mechanism
provides true status.
5
10
10
g
g
• Dielectric designed for 3-phase systems.
105
107
-25
Cycles
Cycles
oC
• Contacts are physically linked making it
impossible for a NO and NC to be closed
simultaneously.
Mechanical Life
Ambient Temperature
80
• Internal creepage distances and
clearances are designed for Overvoltage
Category III and Degree of Pollution 2 per
IEC 60664.
CONTACT SPECIFICATIONS
Maximum Load Current
• Wide range of Contact configurations and
Coil Voltages.
2 Contacts
3 Contacts
10
8.4
7.3
6.5
5.9
5.5
5.1
A
A
A
A
A
A
A
APPROVALS:
4 Contacts
UL: Approved
TUV / CSA: Pending
5 Contacts
6 Contacts
ACCESSORIES:Contact Factory
7 Contacts
Current regulator unit DIL housing
Current regulator unit SO.8 housing
Retaining clip
8 Contacts
Maximum Switching Voltage
230/240 Vac
300 Vdc
Maximum Load Capacity (Resistive)
2000/120 VA/W
© 2000 TELEDYNE RELAYS
800-284-7007 • www.teledynerelays.com
GC 1
Series GC
Maximum Switching Capacity
(Inductive)
AC15-230/240V
DC13-24V
4
2
Arms
Adc
Contact Resistance (See Note 2)
Dielectric Test Voltage (O=III, P=2)
Coil to Contact
100 mOhm
2500 Vac
2500 Vac
Contact to Contact
Characteristics Table
Part No.
Contacts
Contact Material
(/Gold Plating)
AgCdO/5.0um
AgCdO/0.2um
AgCdO/5.0um
AgCdO/5.0um
AgCdO/0.2um
AgCdO/5.0um
AgCdO/5.0um
AgCdO/5.0um
AgCdO/5.0um
AgCdO/5.0um
AgCdO/0.2um
AgCdO/5.0um
AgCdO/0.2um
AgCdO/5.0um
TABLE 1
Coil Resistance
Coil Voltage
(Nominal @ 25°C)
(Ohm)±12%
320
GC35-1097
GC31-1100
GC22-1121
GC22-1123
GC42-1128
GC42-1135
GC33-1149
GC33-1151
GC44-1161
GC44-1163
GC62-1168
GC62-1175
GC53-1183
GC64-1220
3NO/5NC
3NO/1NC
2NO/2NC
2NO/2NC
4NO/2NC
4NO/2NC
3NO/3NC
3NO/3NC
4NO/4NC
4NO/4NC
6NO/2NC
6NO/2NC
5NO/3NC
6NO/4NC
24
24
24
60
24
24
24
60
24
60
24
24
24
24
480
480
2,700
480
480
480
2,700
320
1,870
320
320
320
350
Outline Dimensions
( mm )
4 POLE PACKAGE
6 POLE PACKAGE
GC 2
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
© 2000 TELEDYNE RELAYS
Series GC
Outline Dimensions ( Cont.)
( mm )
( mm )
8 POLE PACKAGE
10 POLE PACKAGE
( mm )
( mm )
( mm )
2NO/2NC PACKAGE
3NO/3NC PACKAGE
4NO/4NC PACKAGE
( mm )
( mm )
( mm )
6NO/2NC PACKAGE
4NO/2NC PACKAGE
6NO/4NC PACKAGE
(VIEW FROM TERMINALS)
Notes:
1) Timing varies with coils voltage.
2) For new contacts only.
3) Contacts will not chatter in excess of 1ms.
© 2000 TELEDYNE RELAYS
800-284-7007 • www.teledynerelays.com