GT3A
Timers
GT3A
GT3A Series — AnalogTimers
Key features:
•ꢀ 4ꢀselectableꢀoperationꢀmodesꢀonꢀeachꢀmodel
•ꢀ Externalꢀstart,ꢀreset,ꢀandꢀgateꢀinputs
•ꢀ Panelꢀmountꢀorꢀsocketꢀmount
•ꢀ Largeꢀvarietyꢀofꢀtimingꢀfunctions
•ꢀ PowerꢀandꢀoutputꢀstatusꢀindicatingꢀLEDs
UL,ꢀc-ULꢀListed
FileꢀNo.ꢀE55996
ꢀꢀ ꢀꢀꢀꢀꢀꢀ
Specifications
GT3A-1
GT3A-2
GT3A-3
GT3A-4,-5,-6
Multi-modeꢀwithꢀinputsꢀ(11ꢀpins)
Operation
Multi-mode
Time Range
0.1sꢀtoꢀ180ꢀhours
100ꢀtoꢀ240VꢀAC,ꢀ50/60Hz
12VꢀDC
Rated Voltage
24VꢀAC,ꢀ50/60Hzꢀ/ꢀ24VꢀDC
ꢀ125VꢀAC/250VꢀAC,ꢀ3A;ꢀ
30VꢀDC,ꢀ1Aꢀ(resistiveꢀload)
125VꢀAC/250VꢀAC,ꢀ5A;ꢀ
30VꢀDC,ꢀ5Aꢀ(resistiveꢀload)
Contact Ratings
Minimum Applicable Load
5V,ꢀ10mAꢀ(referenceꢀvalue)
AF20ꢀ(100VꢀAC):ꢀ85ꢀtoꢀ264VꢀAC
AD24:ꢀ20.4ꢀtoꢀ26.4VꢀAC/21.6ꢀtoꢀ26.4VꢀDC
D12:ꢀ10.8ꢀtoꢀ13.2VꢀDC
Voltage Tolerance
Error
±0.2%,ꢀ±10ꢀmsecꢀ(repeat,ꢀvoltage,ꢀtemperature)
±10%ꢀmaximum
Setting Error
Reset Time
60msecꢀmaximum
Insulation Resistance
100MWꢀminimum
Betweenꢀpowerꢀandꢀoutputꢀterminals:ꢀ2,000VꢀAC,ꢀ1ꢀminute
Betweenꢀcontactsꢀofꢀdifferentꢀpoles:ꢀ2,000VꢀAC,ꢀ1ꢀminute
Betweenꢀcontactsꢀofꢀtheꢀsameꢀpole:ꢀ750VꢀAC,ꢀ1ꢀminute
Dielectric Strength
DelayedꢀSPDTꢀ+ꢀꢀ
DelayedꢀDPDT
DelayedꢀSPDT
DelayedꢀDPDT
instantaneousꢀSPDT
10.8VA
(200VꢀAC,ꢀ60Hz)
13.5VA
(200VꢀAC,ꢀ60Hz)
14.4VA
(200VꢀAC,ꢀ60Hz)
4.7VAꢀ(100VꢀAC,ꢀ60Hz),ꢀ
14.4VAꢀ(200VꢀAC,ꢀ60Hz)
Power Consumption
(approximate)
12VDC/1W
24VDC/0.7W
24VAC/1.2VA
12VDC/1.1W
24VDC/0.6W
24VAC/1.3VA
12VDC/0.8W
24VDC/0.6W
24VAC/1.3VA
Mechanical Life
ꢀ10,000,000ꢀoperationsꢀminimum
ꢀ50,000ꢀoperationsꢀminimumꢀ(ratedꢀload)
63g 73g
ꢀ5,000,000ꢀoperationsꢀminimum
100,000ꢀoperationsꢀminimumꢀ(ratedꢀload)
79g 80g
Electrical LIfe
Weight (approximate)
Vibration Resistance
100m/sec2ꢀ(approximateꢀ10G)
Operatingꢀextremes:ꢀ100m/sec2ꢀ(approximateꢀ10G)
Damageꢀlimits:ꢀ500m/sec2ꢀ(approximateꢀ50G)
Shock Resistance
Operating Temperature
Operating Humidity
Storage Temperature
Housing Color
–10ꢀtoꢀ+50°C
45ꢀtoꢀ85%ꢀRH
–30ꢀtoꢀ+80°C
Gray
800-262-IDEC (4332) • USA & Canada
843
GT3A
Timers
Part Numbers
GT3A-1, -2, -3
Complete Part No.
Mode Of
Operation
Rated Voltage Code
Time Range
Output
Contact
8-Pin
11-Pin
AF20:ꢀ100ꢀtoꢀ240VꢀACꢀ(50/60Hz)
DelayedꢀSPDT
GT3A-1AF20
GT3A-2AF20
GT3A-2D12
GT3A-2AD24
GT3A-3AF20
GT3A-3D12
GT3A-3AD24
GT3A-1EAF20
GT3A-2EAF20
GT3A-2ED12
GT3A-2EAD24
GT3A-3EAF20
GT3A-3ED12
GT3A-3EAD24
250VꢀAC,ꢀ3A,
30VꢀDC,ꢀ1A
(resistiveꢀload)
DelayedꢀSPDTꢀ+
InstantaneousꢀSPDT
A:ꢀON-delayꢀ1
B:ꢀIntervalꢀ1
C:ꢀCycleꢀ1
D:ꢀCycleꢀ3
0.1ꢀsecondsꢀꢀ
toꢀ180ꢀhoursꢀ
AF20:ꢀ100ꢀtoꢀ240VꢀACꢀ(50/60Hz)
D12:ꢀ12VꢀDC
AD24:ꢀ24VꢀACꢀ(50/60Hz)/24VꢀDC
240VꢀAC,ꢀ5A,
24VꢀDC,ꢀ5A
(resistiveꢀload)
DelayedꢀDPDT
1.ꢀ ForꢀwiringꢀschematicsꢀandꢀtimingꢀdiagramsꢀforꢀGT3A-1,ꢀ-2,ꢀ-3,ꢀseeꢀpagesꢀpageꢀ845ꢀandꢀpageꢀ846ꢀrespectively.
2.ꢀ Forꢀmoreꢀdetailsꢀaboutꢀtimeꢀranges,ꢀseeꢀinstructionsꢀonꢀpageꢀpageꢀ850.
3.ꢀ Forꢀsocketꢀandꢀaccessoryꢀpartꢀnumbers,ꢀseeꢀpageꢀ860.
GT3A-4, -5, -6
Complete Part No.
Mode of
Operation
Rated Voltage Code
Time Range
Output
Contact
Input
A (11-pin)
B (11-pin)
GT3A-4AF20
GT3A-4EAF20
A:ꢀON-Delayꢀ2
B:ꢀCycleꢀ2
C:ꢀSignalꢀON/OFF-Delayꢀ1
D:ꢀSignalꢀOFF-Delayꢀ1
AF20:ꢀ100ꢀtoꢀ240VꢀACꢀ(50/60Hz)
D12:ꢀ12VꢀDC
AD24:ꢀ24VꢀACꢀ(50/60Hz)/24VꢀDC
GT3A-4D12
GT3A-4ED12
GT3A-4AD24
GT3A-4EAD24
A:ꢀIntervalꢀ2
GT3A-5AF20
GT3A-5AD24
GT3A-6AF20
GT3A-6AD24
GT3A-5EAF20
GT3A-5EAD24
GT3A-6EAF20
GT3A-6EAD24
250VꢀAC,ꢀ5A,
24VꢀDC,ꢀ5A
(resistiveꢀload)
Start
Reset
Gate
0.1ꢀseconds
toꢀ180ꢀhours
Delayedꢀ
DPDT
B:ꢀOne-ShotꢀCycle
C:ꢀSignalꢀON/OFF-Delayꢀ2
D:ꢀSignalꢀOFF-Delayꢀ2
AF20:ꢀ100ꢀtoꢀ240VꢀACꢀ(50/60Hz)
AD24:ꢀ24VꢀACꢀ(50/60Hz)/24VꢀDC
A:ꢀOne-Shot
B:ꢀOne-ShotꢀON-Delay
C:ꢀOne-Shotꢀ2
D:ꢀSignalꢀON/OFF-Delayꢀ3
4.ꢀ ForꢀwiringꢀschematicsꢀandꢀtimingꢀdiagramsꢀGT3A-4,-5,-6,ꢀseeꢀpagesꢀ832,ꢀ833,ꢀandꢀ833ꢀrespectively.
5.ꢀ Forꢀmoreꢀdetailsꢀaboutꢀtimeꢀranges,ꢀseeꢀinstructionsꢀonꢀpageꢀ850.
6.ꢀ Aꢀ(11-pin)ꢀandꢀBꢀ(11-pin)ꢀdifferꢀinꢀtheꢀwayꢀinputsꢀareꢀwired.
7.ꢀ Forꢀsocketꢀandꢀaccessoryꢀpartꢀnumbers,ꢀseeꢀpageꢀ860.
8.ꢀ Forꢀtheꢀtimingꢀdiagramsꢀoverview,ꢀseeꢀpageꢀ832.
www.IDEC.com
844 ꢀ
ꢀ
GT3A
Timers
Timing Diagrams/Schematics
GT3A-1 Timing Diagrams
Delayed SPDT
Operation
Mode
Selection
Item
SetꢀTime
Terminal Number
Operation
ON-Delay 1
MODE
A
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Power
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
OUT
Item
SetꢀTime
Terminal Number
Operation
Operation
Operation
Interval 1
MODE
B
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Power
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
(NC)
Delayedꢀ
Contact
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NO)
POWER
Indicator
OUT
Cycle 1
(OFFꢀfirst)ꢀ
Item
SetꢀTime
Terminal Number
T
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Power
MODE
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
(NC)
Delayedꢀ
Contact
C
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NO)
POWER
Indicator
OUT
Cycle 3
(ONꢀfirst)ꢀ
Item
SetꢀTime
Terminal Number
T
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Power
MODE
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
(NC)
Delayedꢀ
Contact
D
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NO)
POWER
Indicator
OUT
800-262-IDEC (4332) • USA & Canada
845
GT3A
Timers
GT3A-2 Timing Diagrams
Delayed SPDT + Instantaneous SPDT
GT3A-3 Timing Diagrams
Delayed DPDT
Operation
Mode
Selection
Operation
Mode
Selection
Item
SetꢀTime
Terminal Number
Operation
Operation
Operation
Operation
Item
SetꢀTime
Terminal Number
Operation
ON-Delay 1
MODE
A
T
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
ON-Delay 1
MODE
A
Power
Power
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
1ꢀ-4,ꢀ5ꢀ-ꢀ8ꢀ(8p)
1ꢀ-4,ꢀ8ꢀ-ꢀ11ꢀ(11p)
1ꢀ-3,ꢀ6ꢀ-ꢀ8ꢀ(8p)
1ꢀ-3,ꢀ9ꢀ-ꢀ11ꢀ(11p)
(NC)
(NC)
(NO)
Delayedꢀ
Contact
Delayedꢀ
Contact
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NO)
1ꢀ-ꢀ4
(NC)
(NO)
POWER
Instantaneousꢀ
Contact
Indicator
1ꢀ-ꢀ3
OUT
POWER
OUT
Indicator
Item
SetꢀTime
Terminal Number
Operation
Interval 1
MODE
B
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Power
Item
SetꢀTime
Terminal Number
1ꢀ-4,ꢀ5ꢀ-ꢀ8ꢀ(8p)
1ꢀ-4,ꢀ8ꢀ-ꢀ11ꢀ(11p)
(NC)
T
Delayedꢀ
Contact
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
1ꢀ-3,ꢀ6ꢀ-ꢀ8ꢀ(8p)
1ꢀ-3,ꢀ9ꢀ-ꢀ11ꢀ(11p)
Interval 1
MODE
B
Power
(NO)
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
(NC)
POWER
Delayedꢀ
Contact
Indicator
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NO)
OUT
1ꢀ-ꢀ4
(NC)
(NO)
Instantaneousꢀ
Contact
1ꢀ-ꢀ3
Cycle 1
(OFFꢀfirst)ꢀ
Item
SetꢀTime
Terminal Number
Operation
T
T
POWER
OUT
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Indicator
Power
MODE
1ꢀ-4,ꢀ5ꢀ-ꢀ8ꢀ(8p)
1ꢀ-4,ꢀ8ꢀ-ꢀ11ꢀ(11p)
(NC)
Delayedꢀ
Contact
1ꢀ-3,ꢀ6ꢀ-ꢀ8ꢀ(8p)
1ꢀ-3,ꢀ9ꢀ-ꢀ11ꢀ(11p)
C
(NO)
Item
SetꢀTime
Terminal Number
POWER
T
T
Cycle 1
(OFFꢀfirst)ꢀ
Indicator
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Power
OUT
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
(NC)
Delayedꢀ
Contact
MODE
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
(NO)
Cycle 3
(ONꢀfirst)ꢀ
Item
SetꢀTime
Terminal Number
Operation
C
1ꢀ-ꢀ4
(NC)
(NO)
Instantaneousꢀ
Contact
T
T
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
1ꢀ-ꢀ3
Power
MODE
1ꢀ-4,ꢀ5ꢀ-ꢀ8ꢀ(8p)
1ꢀ-4,ꢀ8ꢀ-ꢀ11ꢀ(11p)
POWER
OUT
(NC)
Delayedꢀ
Contact
Indicator
1ꢀ-3,ꢀ6ꢀ-ꢀ8ꢀ(8p)
1ꢀ-3,ꢀ9ꢀ-ꢀ11ꢀ(11p)
D
(NO)
POWER
Indicator
OUT
Item
Terminal Number
SetꢀTime
T
T
Cycle 3
(ONꢀfirst)ꢀ
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
5ꢀ-ꢀ8ꢀ(8p)
8ꢀ-ꢀ11ꢀ(11p)
6ꢀ-ꢀ8ꢀ(8p)
9ꢀ-ꢀ11ꢀ(11p)
Power
(NC)
Delayedꢀ
Contact
MODE
(NO)
D
1ꢀ-ꢀ4
(NC)
(NO)
Instantaneousꢀ
Contact
1ꢀ-ꢀ3
POWER
OUT
Indicator
Note:ꢀPinsꢀ1,ꢀ3,ꢀandꢀ4ꢀareꢀtheꢀinstantaneousꢀcontacts.
www.IDEC.com
846 ꢀ
ꢀ
GT3A
Timers
GT3A-4 Timing Diagrams
Delayed DPDT
Operation
Mode Selection
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
ON-Delay 2
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
A
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
Ta
T'
T"
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Cycle 2
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
B
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
T
T
T
T
T
T
Ta
T
T
T
T"
T"
T
T
T
T
T
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Signal ON/OFF-Delay 1
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
C
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
T
Ta
T
Ta
T
T
T
T"
Ta
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Signal OFF-Delay 1
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
D
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
Ta
Ta
T
T
T
ꢀ
Tꢀ=ꢀSetꢀtimeꢀ Taꢀ=ꢀShorterꢀthanꢀsetꢀtime
Tꢀ=ꢀT'ꢀ+ꢀT"
800-262-IDEC (4332) • USA & Canada
847
GT3A
Timers
GT3A-5 Timing Diagrams
Delayed DPDT
Operation
Mode Selection
Item
Power
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Interval 2
MODE
A
Input
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
Ta
T'
T"
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
One-Shot Cycle
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
B
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
T
T
Ta
T'
T"
T
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Signal ON/OFF-Delay 2
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
C
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
T
Ta
T
Ta
Operation
Ta
T
T'
T"
Ta
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Signal OFF-Delay 2
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
D
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
Ta
Ta
T
T'
T"
Tꢀ=ꢀSetꢀtimeꢀ Taꢀ=ꢀShorterꢀthanꢀsetꢀtime
Tꢀ=ꢀT'ꢀ+ꢀT"
www.IDEC.com
848 ꢀ
ꢀ
GT3A
Timers
GT3A-6 Timing Diagrams
Delayed DPDT
Operation
Mode Selection
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
One-Shot 1
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
A
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
Ta
Ta
T
Ta
T'
T"
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
One-Shot ON-Delay
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
B
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
T
Ta
T
T
T
T
T'
T"
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
One-Shot 2
MODE
C
Input
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
Ta
T'
T"
Item
Terminal Number
2ꢀ-ꢀ10ꢀPOWER
Operation
Power
2ꢀ-ꢀ6ꢀ(A)
5ꢀ-ꢀ7ꢀ(B)
2ꢀ-ꢀ7ꢀ(A)
6ꢀ-ꢀ7ꢀ(B)
Start
Reset
Gate
ONꢀorꢀL
ONꢀorꢀL
Signal ON/OFF-Delay 3
Input
MODE
2ꢀ-ꢀ5ꢀ(A) ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
D
(NC)
(NO)
Delayedꢀ
Contact
POWER
Indicator
SetꢀTime
OUT
T
Ta
T'
T"
Ta
Ta
T
Tꢀ=ꢀSetꢀtimeꢀ Taꢀ=ꢀShorterꢀthanꢀsetꢀtime
Tꢀ=ꢀT'ꢀ+ꢀT"
800-262-IDEC (4332) • USA & Canada
849
GT3A
Timers
Instructions: Setting GT3A SeriesTimers
ꢀ TimedꢀOUTꢀIndicatorꢀ
ꢀ POWERꢀIndicatorꢀ(flashesꢀ
duringꢀtime-delayꢀperiod)
mꢀSettingꢀKnob
jꢀOperatorꢀModeꢀSelectorꢀ
A,ꢀB,ꢀC,ꢀD
lꢀTimeꢀRangeꢀSelectorꢀꢀ
1S,ꢀ10S,ꢀ10M,ꢀ10H
kꢀDialꢀSelectorꢀ
0-1, 0-3, 0-6, 0-18
Step 1.
Desired Mode of Operation
Selection
Remarks
For Timers
Mode of Operation
ON-delayꢀ1
Intervalꢀ1
Cycleꢀ1
Cycleꢀ3
j Operation Mode Selector
A
B
C
D
GT3A-1
GT3A-2
GT3A-3
ON-delayꢀ2
Cycleꢀ2
A
B
C
D
A
B
C
D
Theꢀdesiredꢀoperationꢀmodeꢀcanꢀbeꢀselectedꢀfromꢀ
theꢀA,ꢀB,ꢀC,ꢀandꢀDꢀmodesꢀusingꢀtheꢀOperationꢀModeꢀ
Selector.ꢀChangeꢀtheꢀoperationꢀmodeꢀfromꢀAꢀtoꢀB,ꢀC,ꢀ
andꢀDꢀinꢀturnꢀbyꢀturningꢀtheꢀoperationꢀmodeꢀselectorꢀ
clockwiseꢀusingꢀaꢀflatꢀscrewdriverꢀwhichꢀisꢀaꢀmaximumꢀ
ofꢀ0.156”ꢀ(4mm)ꢀwide.ꢀTheꢀselectedꢀmodeꢀisꢀdisplayedꢀ
inꢀtheꢀwindow.
GT3A-4
GT3A-5
GT3A-6
SignalꢀON/OFF-delayꢀ1
SignalꢀOFF-delayꢀ1
Intervalꢀ2
One-shotꢀcycle
SignalꢀON/OFF-delayꢀ2
SignalꢀOFF-delayꢀ2
One-shotꢀ1
Selectꢀtheꢀdesiredꢀmodeꢀ
ofꢀoperation.ꢀ
A
One-shotꢀON-delay
One-shotꢀ2
SignalꢀON/OFF-delayꢀ3
B
C
D
Step 2.
Desired Time Range
Time Ranges
Selection
Remarks
k Dial Selector
l Time Range Selector
0.1ꢀsecondsꢀtoꢀ1ꢀsecond
0.1ꢀsecondsꢀtoꢀ3ꢀseconds
0.1ꢀsecondsꢀtoꢀ6ꢀseconds
0.15ꢀsecondsꢀtoꢀ18ꢀseconds
0.1ꢀsecondsꢀtoꢀ10ꢀseconds
0.3ꢀsecondsꢀtoꢀ30ꢀseconds
0.6ꢀsecondsꢀtoꢀ60ꢀseconds
1.8ꢀsecondsꢀtoꢀ180ꢀseconds
6ꢀsecondsꢀtoꢀ10ꢀminutes
18ꢀsecondsꢀtoꢀ30ꢀminutes
36ꢀsecondsꢀtoꢀ60ꢀminutes
108ꢀsecondsꢀtoꢀ180ꢀminutes
6ꢀminutesꢀtoꢀ10ꢀhours
0-1
0-3
0-6
0-18
0-1
0-3
0-6
0-18
0-1
0-3
0-6
1S
10S
Selectꢀtheꢀtimeꢀrangeꢀ
thatꢀcontainsꢀtheꢀdesiredꢀ
timeꢀperiod.
Theꢀdesiredꢀtimeꢀrangeꢀisꢀselectedꢀbyꢀsettingꢀbothꢀ
kꢀDialꢀSelectorꢀandꢀ
lꢀTimeꢀRangeꢀSelector.
10M
0-18
0-1
18ꢀminutesꢀtoꢀ30ꢀhours
36ꢀminutesꢀtoꢀ60ꢀhours
0-3
0-6
10H
108ꢀminutesꢀtoꢀ180ꢀhours
0-18
Step 3.
Selection
SetꢀtheꢀpreciseꢀperiodꢀofꢀtimeꢀdesiredꢀbyꢀusingꢀtheꢀmꢀSettingꢀKnob.
www.IDEC.com
850 ꢀ
ꢀ
GT3F
Timers
GT3F Series —True Power OFF DelayTimers
Key features:
•ꢀ “True”ꢀpowerꢀOFF-delayꢀupꢀtoꢀ10ꢀminutes
•ꢀ Noꢀexternalꢀcontrolꢀswitchꢀnecessary
•ꢀ Availableꢀwithꢀresetꢀinputs
•ꢀ Mountableꢀinꢀsocketsꢀorꢀflushꢀpanel
UL,ꢀc-ULꢀListed
FileꢀNo.ꢀE55996
ꢀꢀ ꢀꢀꢀꢀꢀꢀ
Specifications
GT3F-1
GT3F-2
Operation
TrueꢀpowerꢀOFF-delay
Time Range
ꢀ0.1ꢀsecondsꢀtoꢀ600ꢀseconds
100ꢀtoꢀ240VꢀAC,ꢀ50/60Hz
24VꢀAC/DC
Rated Voltage
250VꢀAC/30VꢀDC,ꢀ5Aꢀ
(resistiveꢀload)
250VꢀAC/30VꢀDC,ꢀ3A
(resistiveꢀload)
Contact Rating
Contact Form
SPDT
DPDT
Minimum Power Application Time
ꢀ1ꢀsecond
AF20:ꢀ100ꢀtoꢀ240VꢀAC
AD24:ꢀ21.6ꢀtoꢀ26.4VDC,ꢀ20.4ꢀtoꢀ26.4VAC
Voltage Tolerance
Repeat Error
±0.2%,ꢀ±10ꢀmsec
±0.2%,ꢀ±10ꢀmsec
±0.2%,ꢀ±10ꢀmsec
±10%ꢀmaximum
100MWꢀminimum
Voltage Error
Temperature Error
Setting Error
Insulation Resistance
Betweenꢀpowerꢀandꢀoutputꢀterminals:
2,000VꢀAC,ꢀ1ꢀminuteꢀ(SPDT)
1,500VꢀAC,ꢀ1ꢀminuteꢀ(DPDT)
Betweenꢀcontactsꢀonꢀdifferentꢀpoles:
1,000VꢀAC,ꢀ1ꢀminuteꢀ(DPDT)
Betweenꢀcontactsꢀofꢀtheꢀsameꢀpole:
750VꢀAC,ꢀ1ꢀminute
Dielectric Strength
Power Consumption
AF20:ꢀ3.7VAꢀ(200VꢀAC,ꢀ60Hz)
AD24:ꢀ0.8Wꢀ(DC),ꢀ1.2VAꢀ(AC)
Mechanical Life
Electrical Life
20,000,000ꢀoperationsꢀminimum
100,000ꢀoperationsꢀminimum
100m/sec2ꢀ(approximateꢀ10G)
Vibration Resistance
Operatingꢀextremes:
100ꢀm/sec2ꢀ(approximateꢀ10G)
Shock Resistance
Damageꢀlimits:ꢀ500ꢀm/sec2ꢀ(approximateꢀ50G)
Operating Temperature
Storage Temperature
Operating Humidity
–10ꢀtoꢀ+50°C
–30ꢀtoꢀ+80°C
45ꢀtoꢀ85%ꢀRH
Weight (approximate)
ꢀ77g
79g
1.ꢀ Anꢀinrushꢀcurrentꢀflowsꢀduringꢀtheꢀminimumꢀpowerꢀapplicationꢀtime.ꢀAF20:ꢀapproximateꢀ0.4A,ꢀꢀ
AD24:ꢀapproximateꢀ1.2A
2.ꢀ GT3Fꢀdoesꢀnotꢀreadꢀtheꢀpresetꢀtimeꢀrangeꢀshownꢀonꢀtheꢀknobꢀafterꢀpowerꢀisꢀturnedꢀoff.ꢀNoteꢀthatꢀminimizingꢀ
theꢀpresetꢀtime,ꢀbyꢀturningꢀtheꢀknobꢀtoꢀzero,ꢀdoesꢀnotꢀshortenꢀtheꢀdelayꢀtimeꢀafterꢀpowerꢀisꢀremoved.
800-262-IDEC (4332) • USA & Canada
851
GT3F
Timers
Part Numbering List
GT3F
Complete Part Number
Mode of
Operation
Rated
Voltage Code
Time Range
Output
250VꢀAC,ꢀ5A,
Contact
DelayedꢀSPDT
DelayedꢀDPDT
Optional Input
8-Pin
11-Pin
GT3F-1AF20
GT3F-1AD24
GT3F-2AF20
GT3F-2AD24
GT3F-1EAF20
GT3F-1EAD24
GT3F-2EAF20
GT3F-2EAD24
AF20:ꢀ100ꢀtoꢀ
240VACꢀ(50/60Hz)
Reset
30VꢀDC,ꢀ5Aꢀ(resistiveꢀload)
250VꢀAC,ꢀ3A,
True-Powerꢀꢀ
OFF-delay
0.1ꢀsecondsꢀtoꢀ
600ꢀseconds
Noneꢀ(8p)ꢀ
Resetꢀ(11p)
AD24:ꢀ24VꢀAC/DC
30VꢀDC,ꢀ3Aꢀ(resistiveꢀload)
ꢀOptionalꢀresetꢀinputꢀresetsꢀtheꢀcontactꢀtoꢀtheꢀOFFꢀstateꢀbeforeꢀtimeꢀout.
Timing Diagrams/Schematics
GT3F-1 Timing Diagrams
GT3F-1 (8-pin)
GT3F-1E (11-pin)
Delayed SPDT Output, with Reset Input
Item
Power
Terminal Number
2ꢀ-ꢀ7ꢀ(8p)
2ꢀ-ꢀ10ꢀ(11p)
Operation
Resetꢀ
Input
1ꢀ-ꢀ4ꢀ(8p)
6ꢀ-ꢀ7ꢀ(11p)
5ꢀ-ꢀ8ꢀ(8p)
ONꢀorꢀL
(NC)
1ꢀ-ꢀ4ꢀ(11p)
Delayedꢀ
Contact
6ꢀ-ꢀ8ꢀ(8p)
1ꢀ-ꢀ3ꢀ(11p)
(NO)
Indicator POWER
SetꢀTime
Tr
T
Ta
Ts
T
Tꢀ=ꢀSetꢀtimeꢀ
Taꢀ=ꢀShorterꢀthanꢀsetꢀtime
Tsꢀ=ꢀ1ꢀSecond
Trꢀ=ꢀMinimumꢀPowerꢀApplicationꢀTime
GT3F-1:ꢀ1ꢀSecond
1.ꢀ Forꢀtimeꢀranges,ꢀseeꢀpageꢀpageꢀ854.
2.ꢀ Forꢀsocketsꢀandꢀaccessoryꢀpartꢀnumbers,ꢀseeꢀpageꢀpageꢀ860.
3.ꢀ Whenꢀpowerꢀisꢀapplied,ꢀtheꢀNOꢀoutputꢀcontactꢀcloses.ꢀWhenꢀpowerꢀisꢀremoved,ꢀtheꢀtimingꢀperiodꢀ
begins.ꢀWhenꢀtimeꢀhasꢀelapsed,ꢀtheꢀNOꢀcontactꢀopens.ꢀ
4.ꢀ Forꢀtheꢀtimingꢀdiagramꢀoverview,ꢀseeꢀpageꢀpageꢀ832.
www.IDEC.com
852 ꢀ
ꢀ
GT3F
Timers
GT3F-2 Timing Diagrams
GT3F-2 (8-pin)
GT3F-2E (11-pin)
Delayed DPDT Output
(Contact Input)
(Transistor Input)
o
o
m
n
q
p
p
n
n
Reset
q
q
m
l
m
l
l
o
Reset
r
r
(-) k
p (+)
s
s
(-) k
(-) k
(+)
(+)
j
j
j
POWER
POWER
POWER
Item
Terminal Number
2ꢀ-ꢀ7
1ꢀ-ꢀ4ꢀ
Operation
Power
(NC)
5ꢀ-ꢀ8
Delayedꢀ
Contact
1ꢀ-ꢀ3ꢀ
6ꢀ-ꢀ8
8-Pin Type
(NO)
Indicator POWER
SetꢀTime
T
Tr
T
Item
Power
Terminal Number
Operation
2ꢀ-ꢀ10
Resetꢀ
Input
6ꢀ-ꢀ7ꢀ(11p)
ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
1ꢀ-ꢀ3
9ꢀ-ꢀ11
(NC)
(NO)
Delayedꢀ
Contact
11-Pin Type
Indicator POWER
SetꢀTime
Tr
T
Ta
Ts
T
Whenꢀpowerꢀisꢀapplied,ꢀtheꢀNOꢀcontactꢀcloses.ꢀWhenꢀpowerꢀisꢀremoved,ꢀtheꢀtimingꢀperiodꢀbegins.ꢀWhenꢀtimeꢀhasꢀelapsed,ꢀtheꢀNOꢀcontactꢀopens.ꢀOptionalꢀresetꢀ
inputꢀwillꢀreturnꢀcontactsꢀtoꢀoriginalꢀstateꢀbeforeꢀtimeꢀelapses.
Tꢀ=ꢀSetꢀtimeꢀ
Taꢀ=ꢀShorterꢀthanꢀsetꢀtime
Tsꢀ=ꢀ1ꢀSecond
Trꢀ=ꢀMinimumꢀPowerꢀApplicationꢀTime
GT3F-1:ꢀ1ꢀSecond
Item
Power
Terminal Number
Operation
2ꢀ-ꢀ10
Resetꢀ
Input
6ꢀ-ꢀ7ꢀ(11p)
ONꢀorꢀL
1ꢀ-ꢀ4
8ꢀ-ꢀ11
(NC)
(NO)
Delayedꢀ
Contact
1ꢀ-ꢀ3
9ꢀ-ꢀ11
Indicator POWER
SetꢀTime
Tr
T
Ta
Ts
T
800-262-IDEC (4332) • USA & Canada
853
GT3F
Timers
Instructions: Setting GT3F SeriesTimers
ꢀ POWERꢀIndicatorꢀ
lꢀSettingꢀKnob
ꢀ
jꢀDialꢀSelectorꢀ
0-1,ꢀ0-3,ꢀ0-6,ꢀ0-18,ꢀ0-60
kꢀTimeꢀRangeꢀSelectorꢀꢀ
1S,ꢀ10S
Step 1
Desired Operation
Selection
k Time Range Selector
Remarks
Base Time Ranges
0.1sꢀtoꢀ1s
j Dial Selector
0ꢀtoꢀ1
0.1sꢀtoꢀ3s
0ꢀtoꢀ3
1s
Selectꢀaꢀtimeꢀ
rangeꢀthatꢀ
Timeꢀrangeꢀcanꢀbeꢀselectedꢀfromꢀ1Sꢀandꢀ10Sꢀusingꢀaꢀflatꢀscrewdriverꢀandꢀfiveꢀ
differentꢀdialsꢀofꢀ0ꢀtoꢀ1,ꢀ0ꢀtoꢀ3,ꢀ0ꢀtoꢀ6,ꢀ0ꢀtoꢀ18,ꢀandꢀ0ꢀtoꢀ60ꢀareꢀdisplayedꢀinꢀtheꢀsixꢀ
windowsꢀbyꢀturningꢀtheꢀDialꢀSelector,ꢀallowingꢀforꢀselectingꢀtheꢀbestꢀsuitedꢀscale.ꢀ
Noteꢀthatꢀtheꢀswitchꢀdoesꢀnotꢀturnꢀinfinitely.
0.1sꢀtoꢀ6s
0ꢀtoꢀ6
containsꢀtheꢀ
desiredꢀperiodꢀ
ofꢀtime.
0.1sꢀtoꢀ10s
0.3sꢀtoꢀ30
0ꢀtoꢀ1
0ꢀtoꢀ3
0.6sꢀtoꢀ60
0ꢀtoꢀ6
10s
1.8sꢀtoꢀ180s
6sꢀtoꢀ600s
0ꢀtoꢀ18
0ꢀtoꢀ60
Step 2
Remarks
SettingꢀExamples:
1.ꢀWhenꢀtheꢀSettingꢀKnobꢀlꢀisꢀsetꢀatꢀ2.5,ꢀwithꢀDialꢀSelectorꢀjꢀ0ꢀtoꢀ3ꢀandꢀTimeꢀ
RangeꢀSelectorꢀkꢀ1Sꢀselected,ꢀthenꢀtheꢀsetꢀtimeꢀisꢀ2.5ꢀseconds.
TheꢀsetꢀtimeꢀisꢀselectedꢀbyꢀturningꢀtheꢀlꢀSettingꢀKnob.
2.ꢀWhenꢀtheꢀSettingꢀKnobꢀlꢀisꢀsetꢀatꢀ5.0,ꢀ
withꢀDialꢀSelectorꢀjꢀ0ꢀtoꢀ60ꢀandꢀTimeꢀRangeꢀSelectorꢀkꢀ10Sꢀselected,ꢀthenꢀtheꢀ
setꢀtimeꢀisꢀ500ꢀseconds.
www.IDEC.com
854 ꢀ
ꢀ
GT3F
Timers
Instructions:Wiring Inputs
Inputs of GT3F
Toꢀavoidꢀelectricꢀshock,ꢀdoꢀnotꢀtouchꢀtheꢀinputꢀsignalꢀterminalꢀduringꢀpowerꢀvoltageꢀapplication.ꢀꢀ
NeverꢀapplyꢀtheꢀinputꢀsignalsꢀtoꢀtwoꢀorꢀmoreꢀGT3Fꢀtimersꢀusingꢀtheꢀsameꢀcontactꢀorꢀtransistor.
[Incorrect]
Input
Contact or Transistor
GT3 Series
Timer
[correct]
Input
Input
Terminal
Terminal
2
2
10
10
2
10
Power
Power
Input
Terminal
Input
Terminal
2
10
ꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀꢀ
Inꢀaꢀtransistorꢀcircuitꢀforꢀcontrollingꢀinputꢀsignals,ꢀwithꢀitsꢀprimaryꢀandꢀsecondaryꢀpowerꢀcircuitsꢀisolated,ꢀdoꢀnotꢀgroundꢀtheꢀsecondaryꢀcircuit.
GT3 Series
Timer
Input
Terminal
Power
Circuit
Insulating Transformer
OnꢀtheꢀGT3Fꢀtimers,ꢀconnectꢀtheꢀinputꢀsignalsꢀtoꢀterminalꢀNo.1ꢀandꢀ4ꢀonlyꢀonꢀtheꢀ8-pinꢀtype;ꢀconnectꢀtheꢀinputꢀsignalsꢀtoꢀterminalꢀNo.ꢀ6ꢀandꢀ7ꢀonlyꢀonꢀtheꢀ11-pinꢀtype.ꢀ
Neverꢀapplyꢀvoltageꢀtoꢀotherꢀterminals;ꢀotherwise,ꢀtheꢀinternalꢀcircuitꢀmayꢀbeꢀdamaged.
Inputꢀsignalꢀlinesꢀmustꢀbeꢀmadeꢀasꢀshortꢀasꢀpossibleꢀandꢀinstalledꢀawayꢀfromꢀpowerꢀcablesꢀandꢀpowerꢀlines.ꢀUseꢀshieldedꢀwiresꢀorꢀaꢀseparateꢀconduitꢀforꢀinputꢀwir-
ing.ꢀ
TheꢀGT3F,ꢀconsistingꢀofꢀaꢀhigh-impedanceꢀcircuit,ꢀmayꢀnotꢀbeꢀresetꢀdueꢀtoꢀtheꢀinfluenceꢀofꢀanꢀinductiveꢀvoltageꢀorꢀresidualꢀvoltageꢀcausedꢀbyꢀaꢀleakageꢀcurrent.ꢀIfꢀnotꢀ
reset,ꢀconnectꢀanꢀRCꢀfilterꢀorꢀbleederꢀresistorꢀbetweenꢀpowerꢀterminalsꢀsoꢀthatꢀtheꢀvoltageꢀbetweenꢀpowerꢀterminalsꢀcanꢀbeꢀreducedꢀtoꢀlessꢀthanꢀ15%ꢀofꢀtheꢀratedꢀ
voltage.
800-262-IDEC (4332) • USA & Canada
855
GT3W
Timers
GT3W Series — DualTime RangeTimers
Key features:
•ꢀ Sequentialꢀstart,ꢀsequentialꢀinterval,ꢀon-delay,ꢀrecycler,ꢀꢀ
andꢀintervalꢀONꢀtimingꢀfunctions
•ꢀ 2ꢀtimeꢀsettingsꢀinꢀoneꢀtimer
•ꢀ 8ꢀselectableꢀoperationꢀmodesꢀonꢀeachꢀmodel
•ꢀ Mountableꢀinꢀsocketsꢀorꢀflushꢀpanel
•ꢀ PowerꢀandꢀoutputꢀstatusꢀindicatingꢀLEDs
•ꢀ Timeꢀrangesꢀupꢀtoꢀ300ꢀhours
UL,ꢀc-ULꢀListed
FileꢀNo.ꢀE55996
ꢀꢀ ꢀꢀꢀꢀꢀꢀ
General Specifications
Operation System
Contact Ratings
Allowable Contact Power
Allowable Voltage
SolidꢀstateꢀCMOSꢀCircuit
960VA/120W
250VꢀAC/150VꢀDC
5A
Operation Type
Multi-Mode
Time Range
1:ꢀ0.1secꢀtoꢀ6ꢀhours,ꢀ3:ꢀ0.1secꢀtoꢀ300ꢀhours
2ꢀ(IE60664-1)
Allowable Current
Pollution Degree
Over Voltage Category
Maximum permissible
operating frequency
1800ꢀcyclesꢀperꢀhour
IIIꢀ(IE60664-1)
1/8HP,ꢀ240VꢀAC
AF20
AD24
D12
100-240VꢀAC(50/60Hz)
24VꢀAC(50/60Hz)/24VꢀDC
12VꢀDC
3A,ꢀ240VꢀACꢀ(Resistive)
Rated Operational Voltage
Voltage Tolerance
Rated Load
5A,ꢀ120VꢀAC/30VꢀDCꢀ
(Resistive)
AF20
AD24
D12
85-264VꢀAC(50/60Hz)
20.4-26.4VꢀAC(50/60Hz)/21.6-26.4VꢀDC
10.8-13.2VꢀDC
Conditional Short Circuit
Fuseꢀꢀꢀ5A,ꢀ250V
100,000ꢀop.ꢀminimumꢀ
(Resistive)
Electrical
Life
Disengaging Value of Input Voltage
RatedꢀVoltageꢀx10%ꢀminimum
-10ꢀtoꢀ+50ºCꢀ(withoutꢀfreezing)
Mechanical 20,000,000ꢀop.ꢀminimum
Range of Ambient Operating Temperature
Range of Ambient Storage
and Transport Temperature
-30ꢀtoꢀ+75ºCꢀ(withoutꢀfreezing)
Range of Relative Humidity
Atmospheric Pressure
Reset Time
35ꢀtoꢀ85%RHꢀ(withoutꢀcondensation)
80kPaꢀtoꢀ110kPaꢀ(Operating),ꢀ70kPaꢀtoꢀ110kPaꢀ(Transport)ꢀ
60msecꢀmaximum
Repeat Error
±0.2%,ꢀ±10msec*
Voltage Error
±0.2%,ꢀ±10msec*
Temperature Error
Setting Error
±0.6%,ꢀ±10msec*
±10%ꢀmaximum
Insulation Resistance
100MΩꢀminimumꢀ(500VꢀDC)
Betweenꢀpowerꢀandꢀoutputꢀterminals:ꢀ2000VꢀAC,ꢀ1ꢀminute
Betweenꢀcontactsꢀofꢀdifferentꢀpoles:ꢀ2000VꢀAC,ꢀ1ꢀminute
Betweenꢀcontactsꢀofꢀtheꢀsameꢀpole:750VꢀAC,ꢀ1ꢀminute
10ꢀtoꢀ55Hzꢀamplitudeꢀ0.75mm2ꢀhoursꢀinꢀeachꢀofꢀ3ꢀaxes
Operatingꢀextremes:ꢀ98m/sec2ꢀ(approx.10G)ꢀ
Damageꢀlimits:ꢀ490m/sec2ꢀ(approx.ꢀ50G)
3ꢀtimesꢀinꢀeachꢀofꢀ3ꢀaxes
Dielectric Strength
Vibration Resistance
Shock Resistance
Degree of Protection
IP40ꢀ(enclosure),ꢀIP20ꢀ(socket)ꢀꢀꢀꢀ(IEC60529)
100VꢀAC/60Hz 2.3VA
200VꢀAC/60Hz 4.6VA
AF20
Power Consumption
(Approx.)
AD24ꢀ(AC/DC)
1.8VA/0.9W
Mounting Position
Dimensions
Free
40Hxꢀ36Wꢀxꢀ70ꢀmm
72g
Weight (Approx.)
*ꢀForꢀtheꢀvalueꢀofꢀtheꢀerrorꢀagainstꢀaꢀpresetꢀtime,ꢀwhicheverꢀtheꢀlargestꢀapplies.
www.IDEC.com
856 ꢀ
ꢀ
GT3W
Timers
Part Number List
Time Range*
Part Numbers
Mode of Operation
Output
Contact
Rated Voltage
Pin Configuration
New Part Numbers
8ꢀpin
GT3W-A11AF20N
GT3W-A11EAF20N
GT3W-A11AD24N
GT3W-A11EAD24N
GT3W-A11D12N
GT3W-A11ED12N
GT3W-A33AF20N
GT3W-A33AD24N
100ꢀtoꢀ240VꢀACꢀ
(50/60Hz)
11ꢀpin
8ꢀpin
A:ꢀSequentialꢀStart
1:ꢀ0.1secꢀ-ꢀ6ꢀhours
*(SeeꢀTimeꢀRangeꢀSet-
tingsꢀforꢀdetails.)
B:ꢀOn-delayꢀwithꢀcourseꢀandꢀfine
C:ꢀRecyclerꢀandꢀinstaneous
D:ꢀRecyclerꢀoutputsꢀ(OFFꢀStart)
E:ꢀRecyclerꢀoutputsꢀ(ONꢀStart)
F:ꢀIntervalꢀON
G:ꢀIntervalꢀONꢀDelay
H:ꢀSequentialꢀ
24VꢀAC/DC
12VꢀDC
Delayed
ꢀSPDT
+
Delayed
ꢀSPDT
3A,ꢀ240VꢀAC
11ꢀpin
8ꢀpin
5A,ꢀ120VꢀAC/30VꢀDC
(ResistiveꢀLoad)
11ꢀpin
Interval
100ꢀtoꢀ240VꢀACꢀ
(50/60Hz)
3:ꢀ0.1secꢀ-ꢀ300ꢀhours
8ꢀpin
24VꢀAC/DC
1.ꢀ Forꢀtimingꢀdiagramsꢀandꢀschematics,ꢀseeꢀpageꢀ858.
2.ꢀ Forꢀsocketꢀandꢀaccessoryꢀpartꢀnumberꢀinformation,ꢀseeꢀpageꢀ860.
3.ꢀ 8-ꢀandꢀ11-pinꢀmodelsꢀdifferꢀonlyꢀinꢀtheꢀnumberꢀofꢀpinsꢀ(extraꢀpinsꢀareꢀnotꢀused).
4.ꢀ Forꢀtheꢀtimingꢀdiagramꢀoverview,ꢀseeꢀpageꢀ832.
5.ꢀ*Forꢀdetailsꢀonꢀsettingꢀtimeꢀranges,ꢀseeꢀtheꢀinstructionsꢀonꢀpageꢀ859.
Time Range Table
Time Range Code: 1
Scale
Time Range Code: 3
Time Range
Selector
Time Range
Selector
Time Range
Scale
Time Range
1S
10S
10M
1S
0.1ꢀsecꢀ-ꢀ1ꢀsec
0.3ꢀsecꢀ-ꢀ10ꢀsec
15ꢀsecꢀ-ꢀ10ꢀmin
0.1ꢀsecꢀ-ꢀ6ꢀsec
1ꢀsecꢀ-ꢀ60ꢀsec
6ꢀsecꢀ-ꢀ6ꢀmin
1S
1M
1H
1S
0.1ꢀsecꢀ-ꢀ3ꢀsec
3ꢀsecꢀ-ꢀ3ꢀmin
0-1
0ꢀ-ꢀ3
3ꢀminꢀ-ꢀ3ꢀhours
0.6ꢀsecꢀ-ꢀ30ꢀsec
36ꢀsecꢀ-ꢀ30ꢀmin
36minꢀ-ꢀ30ꢀhours
10S
1M
10M
1H
1M
1H
0ꢀ-ꢀ6
0ꢀ-ꢀ30
1ꢀminꢀ-ꢀ60ꢀmin
6ꢀminꢀ-ꢀ6ꢀhours
10H
6ꢀhoursꢀ-ꢀ300ꢀhours
800-262-IDEC (4332) • USA & Canada
857
GT3W
Timers
Timing Diagrams/Schematics
Mode
OperationꢀChart
Mode
OperationꢀChart
Terminal
No.
Terminal
No.
Item
Operation
Description
Item
Operation
Description
Power
2-7
Power
2-7
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Delayed
Contact
Ry1
Delayed
Contact
Ry1
ON during T1
OFF during T2
ON after T1
Delayed
Contact
Ry2
Delayed
Contact
Ry2
ON during T1
OFF during T2
ON after T1 + T2
OUT1
OUT2
OUT1
OUT2
Indicator
Indicator
Set Time
Set Time
T1
T2
T1
T2
Terminal
No.
Terminal
No.
Item
Operation
Description
Item
Operation
Description
Power
2-7
Power
2-7
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Delayed
Contact
Ry1
Delayed
Contact
Ry1
ON during T1
ON after T1 + T2
ON after T1 + T2
Delayed
Contact
Ry2
Delayed
Contact
Ry2
ON after T1,
during T2
OUT1
OUT2
OUT1
OUT2
Indicator
Indicator
Set Time
Set Time
T1
T2
T1
T2
Terminal
No.
Terminal
No.
Item
Operation
Description
Item
Operation
Description
Power
2-7
Power
2-7
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Delayed
Contact
Ry1
Delayed
Contact
Ry1
Instantaneous ON
ON during T1
Delayed
Contact
Ry2
Delayed
Contact
Ry2
OFF during T1
ON during T2
ON after T1 + T2
OUT1
OUT2
OUT1
OUT2
Indicator
Indicator
Set Time
Set Time
T1
T2
T1
T2
Terminal
No.
Terminal
No.
Item
Operation
Description
Item
Operation
Description
Power
2-7
Power
2-7
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
1-4
(NC)
1-3
(NO)
5-8
(NC)
6-8
(NO)
Delayed
Contact
Ry1
Delayed
Contact
Ry1
OFF during T1
ON during T2
ON during T1 + T2
Delayed
Contact
Ry2
Delayed
Contact
Ry2
OFF during T1
ON during T2
ON after T1,
during T2
OUT1
OUT2
OUT1
OUT2
Indicator
Indicator
Set Time
Set Time
T1
T2
T1
T2
www.IDEC.com
858 ꢀ
ꢀ
GT3W
Timers
Instructions: Setting GT3WTimer
1.ꢀTheꢀswitchesꢀshouldꢀbeꢀsecurelyꢀturnedꢀusingꢀaꢀflatꢀscrewdriverꢀ4mmꢀ
wideꢀ(maximum).ꢀNoteꢀthatꢀincorrectꢀsettingꢀmayꢀcauseꢀmalfunction.ꢀ
Theꢀswitches,ꢀwhichꢀdoꢀnotꢀturnꢀinfinitely,ꢀshouldꢀnotꢀbeꢀturnedꢀbeyondꢀ
theirꢀlimits.
T2ꢀSettingꢀKnob
T1ꢀSettingꢀKnob
T2ꢀTimeꢀRangeꢀSelector
OperationꢀModeꢀSelector
T1ꢀTimeꢀRangeꢀSelector
2.ꢀSinceꢀchangingꢀtheꢀsettingꢀduringꢀtimerꢀoperationꢀmyꢀcauseꢀmalfunction,ꢀ
turnꢀpowerꢀoffꢀbeforeꢀchanging.
Safety Precautions
SpecialꢀexpertiseꢀisꢀrequiredꢀtoꢀuseꢀElectronicꢀTimers.
Caution
•ꢀ AllꢀElectronicꢀTimerꢀmodulesꢀareꢀmanufacturedꢀunderꢀIDEC’sꢀrigorousꢀqualityꢀ
controlꢀsystem,ꢀbutꢀusersꢀmustꢀaddꢀaꢀbackupꢀorꢀfailꢀsafeꢀprovisionꢀtoꢀtheꢀ
controlꢀsystemꢀwhenꢀusingꢀtheꢀElectronicꢀTimerꢀinꢀapplicationsꢀwhereꢀheavyꢀ
damageꢀorꢀpersonalꢀinjuryꢀmayꢀoccurꢀshouldꢀtheꢀElectronicꢀTimerꢀfail.
Cautionꢀnoticesꢀareꢀusedꢀwhereꢀinattentionꢀmightꢀcauseꢀpersonalꢀinjuryꢀorꢀdam-
ageꢀtoꢀequipment.
•ꢀ TheꢀElectronicꢀTimerꢀisꢀdesignedꢀforꢀinstallationꢀinꢀequipment.ꢀDoꢀnotꢀinstallꢀ
theꢀElectronicꢀTimerꢀoutsideꢀequipment.
•ꢀ InstallꢀtheꢀElectronicꢀTimerꢀaccordingꢀtoꢀinstructionsꢀdescribedꢀinꢀthisꢀcatalog.
•ꢀ InstallꢀtheꢀElectronicꢀTimerꢀinꢀenvironmentsꢀdescribedꢀinꢀtheꢀspecifications.ꢀIfꢀ
theꢀElectronicꢀTimerꢀisꢀusedꢀinꢀplacesꢀwhereꢀitꢀwillꢀbeꢀsubjectedꢀtoꢀhigh-tem-
perature,ꢀhigh-humidity,ꢀcondensation,ꢀcorrosiveꢀgases,ꢀexcessiveꢀvibrations,ꢀ
orꢀexcessiveꢀshocks,ꢀthenꢀelectricalꢀshocks,ꢀfireꢀhazard,ꢀorꢀmalfunctionꢀcouldꢀ
result.
•ꢀ Makeꢀsureꢀthatꢀtheꢀoperatingꢀconditionsꢀareꢀasꢀdescribedꢀinꢀtheꢀspecifica-
tions.ꢀIfꢀyouꢀareꢀuncertainꢀaboutꢀtheꢀspecifications,ꢀcontactꢀIDECꢀinꢀadvance.
•ꢀ Inꢀtheseꢀdirections,ꢀsafetyꢀprecautionsꢀareꢀcategorizedꢀinꢀorderꢀofꢀimportanceꢀ
toꢀWarningꢀandꢀCaution.
•ꢀ UseꢀanꢀIEC60127-approvedꢀfuseꢀandꢀcircuitꢀbreakerꢀonꢀtheꢀpowerꢀandꢀoutputꢀ
lineꢀoutsideꢀtheꢀElectronicꢀTimer.
Warning
•ꢀ Doꢀnotꢀdisassemble,ꢀrepair,ꢀorꢀmodifyꢀtheꢀElectronicꢀTimer.
Warningꢀnoticesꢀareꢀusedꢀtoꢀemphasizeꢀthatꢀimproperꢀoperationꢀmayꢀcauseꢀseverꢀ
personalꢀinjuryꢀorꢀdeath.
•ꢀ WhenꢀdisposingꢀofꢀtheꢀElectronicꢀTimer,ꢀdoꢀsoꢀasꢀindustrialꢀwaste.
•ꢀ TurnꢀpowerꢀoffꢀtoꢀtheꢀElectronicꢀtimerꢀbeforeꢀstartingꢀinstallation,ꢀremoval,ꢀ
Wiring,ꢀmaintenance,ꢀandꢀinspectionꢀonꢀtheꢀElectronicꢀTimer.ꢀ
•ꢀ Failureꢀtoꢀturnꢀpowerꢀoffꢀmayꢀcauseꢀelectricalꢀshocksꢀorꢀfireꢀhazard.
•ꢀ Emergencyꢀstopꢀandꢀinterlockingꢀcircuitsꢀmustꢀbeꢀconfiguredꢀoutsideꢀtheꢀ
Electronicꢀtimer.ꢀIfꢀsuchꢀaꢀcircuitꢀisꢀconfiguredꢀinsideꢀtheꢀElectronicꢀTimer,ꢀ
failureꢀofꢀtheꢀElectronicꢀtimerꢀmayꢀcauseꢀmalfunctionꢀofꢀtheꢀcontrolꢀsystem,ꢀorꢀ
anꢀaccident.
800-262-IDEC (4332) • USA & Canada
859
GT3 Series Accessories
Timers
GT3 Series
Accessories
DIN Rail Mounting Accessories
DIN Rail/Surface Mount Sockets and Hold-Down Springs
DIN Rail Mount Socket
Applicable Hold-Down Springs
Appearance Part No.
Style
Appearance
Use with Timers
Part No.
GT3A-1, 2, 3 (8-pin)
GT3F-1, 2 (8-pin)
GT3W (8-pin)
8-Pin Screw Terminal
(dual tier)
SR2P-05
GT3A-1, 2, 3 (11-pin)
GT3A-4, 5, 6
GT3F-1, 2 (11-pin)
GT3W (11-pin)
11-Pin Screw Terminal
(dual tier)
SR3P-05
SFA-203
GT3A-1, 2, 3 (8-pin)
GT3F-1, 2 (8-pin)
GT3W (8-pin)
8-Pin Fingersafe Socket
11-Pin Fingersafe Socket
8-Pin Screw Terminal
11-Pin Screw Terminal
SR2P-05C
SR3P-05C
SR2P-06
SR3P-06
GT3A-1, 2, 3 (11-pin)
GT3A-4, 5, 6
GT3F-1, 2 (11-pin)
GT3W (11-pin)
GT3A-1, 2, 3 (8-pin)
GT3F-1, 2 (8-pin)
GT3W (8-pin)
SFA-202
GT3A-1, 2, 3 (11-pin)
GT3A-4, 5, 6
GT3F-1, 2 (11-pin)
GT3W (11-pin)
DIN Mounting Rail
Length 1000mm
—
BNDN1000
Installation of Hold-Down Springs
DIN Rail Mount Socket
Insert the springs into the outer
slots with the projections
facing inside.
Panel Mount Socket
Hold-down Spring
SFA-402
Insert the springs
into the slots.
Insert
8-pin Socket
SR2P-51
Socket SR2P-05
Hold-down Spring (sold separately)
SFA-203 (use two springs)
Socket SR2P-06
Hold-down Spring (sold separately)
SFA-202 (use two springs)
www.IDEC.com
860
GT3 Series Accessories
Timers
Panel Mounting Accessories
Panel Mount Sockets and Hold-Down Springs
Panel Mount Socket
Applicable HD Springs
Style
Appearance
Use with Timers
Part No.
Appearance
Part No.
GT3A- (8-pin)
GT3W- (8-pin)
GT3F- (8-pin)
8-Pin Solder Terminal
SR2P-51
SFA-402
GT3A- (11-pin)
GT3W- (11-pin)
GT3F- (11-pin)
11-Pin Solder Terminal
SR3P-51
For information on installing the hold-down springs, see page 860.
Flush Panel Mount Adapter and Sockets that use an Adapter
Accessory
Description
Appearance
Use with Timers
Part No.
Panel Mount Adapter Adaptor for flush panel mounting GT3 timers
All GT3 timers
RTB-G01
8-pin screw terminal
All 8-pin timers
SR6P-M08G
SR6P-M11G
(Shown: SR6P-M08G for Wiring Socket Adapter)
11-pin screw terminal
All 11-pin timers
Sockets for use with
Panel Mount Adapter
8-pin solder terminal
All 8-pin timers
All 11-pin timers
SR6P-S08
SR6P-S11
11-pin solder terminal
No hold down springs are available for flush panel mounting.
800-262-IDEC (4332) • USA & Canada
861
GT3 Series Instructions
Timers
Instructions:Wiring Inputs for GT3 Series
Inputs
To avoid electric shock, do not touch the input signal terminal during power voltage application.
When connecting the input signal terminals of two or more GT3A timers to the same contact or transistor, the input terminals of the same number should be con-
nected. (Connect Terminals No.2 in common.)
[Incorrect]
Input
Contact or Transistor
GT3 Series
Timer
[correct]
Input
Input
Terminal
Terminal
2
2
10
10
2
10
Power
Power
Input
Terminal
Input
Terminal
2
10
In a transistor circuit for controlling input signals, with its primary and secondary power circuits isolated, do not ground the secondary circuit.
GT3 Series
Timer
Input
Terminal
Power
Circuit
Insulating Transformer
Connect the input signal terminals of the GT3A timers to Terminal No.2 only. Never apply voltage to other terminals; otherwise, the internal circuit may be damaged.
R
Y
5, 6, and 7
Input Terminal
2
10
Power
Input signal lines must be made as short as possible and installed away from power cables and power lines. Use shielded wires or a separate conduit for
input wiring.
www.IDEC.com
862
GT3 Series Instructions
Timers
Inputs Instructions, continued
For contact input, use gold-plated contacts to make sure that the residual voltage is less than 1V when the contacts are closed.
6
5
7
4
8
3
9
2
10
1
11
Power
For transistor input, use transistors with the following specifications; VCE = 40V, VCES = 1V or less, IC = 50 mA or more, and ICBO = 50µA or less. The resistance
should be less than 1kΩ when the transistor is on. When the output transistor switches on, a signal is input to the timer.
6
5
7
4
8
3
9
2
10
1
11
Power
Inputs: GT3A-1, -2, -3
Transistor output equipment such as proximity switches and photoelectric switches can input signals if they are voltage/current output type, with power voltage
ranges from 18 to 30V and have1V. When the signal voltage switches from H to L, a signal is input to the timer
6
5
7
4
8
3
9
2
10
1
11
Power
Inputs: GT3A-4, -5, -6
The start input initiates a time-delay operation and controls
output status.
No-voltage contact inputs and NPN open collector transis-
tor inputs are applicable.
Start Input
Reset Input
Gate Input
When the reset input is activated, the time is reset, and
contacts return to original state.
24V DC, 1mA maximum
The time-delay operation is suspended while the gate input
is on (pause).
Input response time: 50msec maximum
800-262-IDEC (4332) • USA & Canada
863
GT3 Series Dimensions
Timers
Dimensions
70.0
36.0
5.6
Unit: mm
NOTE: GT3W series are UL Listed when used in combination
with following IDEC’s sockets:
GT3W-A11, A33:
GT3W-A11E:
SR2P-06* pin type socket.
SR3P-05* pin type socket.
(*-May be followed by A,B,C or U)
The socket to be used with these timers are rated:
-Conductor Temperature Rating 60ºC min.
-Use 14AWG max.(2mm2max.) Copper conductors only
-Terminal Torque 1.0 to 1.3 N-m
Analog GT3 Timer, 8-Pin with SR2P-06
Analog GT3 Timer, 11-Pin with SR3P-06
(When using
When using BAA/BAP: 99 maximum
DIN Rail)
Analog Setting Type
(When using
When using BAA/BAP: 99 maximum
DIN Rail)
Analog Setting Type
95 maximum
95 maximum
Hold-
down
spring
Hold-
down
spring
DIN Rail
DIN Rail
(
)
SFA-202
(
)
SFA-202
18
22
18
22
36
8
64.2
13
36
8
64.2
13
Analog GT3 Timer, 11-Pin with SR3P-05
(When using DIN Rail)
BAA or BAP: 105.5 maximum
Analog Setting Type
DIN Rail
(BAA/BAP/BADA)
101.5 maximum
Hold-down
Spring (SFA-203)
16.5
20
36
8
64.2
13
28.5
Panel Mount Adapter
Analog GT3 Timer, 8-Pin and 11-Pin
with SR6P-S08 or SR6P-S11
98 maximum
Panel Thickness 0.8 to 5mm
Back Wiring Socket
48
11
61.2
www.IDEC.com
864
GT3 Series Dimensions
Timers
Mounting Hole Layout
Single
Tolerance: +0.5 to 0
N: No. of timers mounted
Horizontal Close Mounting
48N--3
Mounting
45
GT3 Timer, 8-Pin with SR6P-M08G
GT3 Timer, 11-Pin with SR6P-M11G
8-M3.5 Terminal Screw
44.6
11-M3.5 Teminal Screws
Panel Thickness 0.8 to 5mm
45
16.7
1
3.5 max.
6.9 max.
5.6 min.
5.8 min.
3.5 max.
6.9 max.
ø3.6 min.
3
2
4
1
5
8
6
7
2
11
8
7
9
6
ø3.6 min.
5
4
3
10
7
30.5
7
9.8 × 3
80.5
92
8.5 × 4
800-262-IDEC (4332) • USA & Canada
865
General Instructions
Timers
General Instructions for AllTimer Series
Load Current
Vibration and Shock
With inductive, capacitive, and incandescent lamp loads, inrush current more
than 10 times the rated current may cause welded contacts and other undesired
effects. The inrush current and steady-state current must be taken into consider-
ation when specifying a timer.
Excessive vibration or shocks can cause the output contacts to bounce, the
timer should be used only within the operating extremes for vibration and shock
resistance. In applications with significant vibration or shock, use of hold down
springs or clips is recommended to secure a timer to its socket.
Contact Protection
Time Setting
Switching an inductive load generates a counter-electromotive force (back EMF)
in the coil. The back EMF will cause arcing, which may shorten the contact life
and cause imperfect contact. Application of a protection circuit is recommended
to safeguard the contacts.
The time range is calibrated at its maximum time scale; so it is desirable to use
the timer at a setting as close to its maximum time scale as possible. For a more
accurate time delay, adjust the control knob by measuring the operating time
with a watch before application.
Temperature and Humidity
Input Contacts
Use the timer within the operating temperature and operating humidity ranges
and prevent freezing or condensation. After the timer has been stored below
its operating temperature, leave the timer at room temperature for a sufficient
period of time to allow it to return to operating temperatures before use.
Use mechanical contact switch or relay to supply power to the timer. When
driving the timer with a solid-state output device (such as a two-wire proximity
switch, photoelectric switch, or solid-state relay), malfunction may be caused by
leakage current from the solid-state device. Since AC types comprise a capaci-
tive load, the SSR dielectric strength should be two or more times the power
voltage when switching the timer power using an SSR.
Environment
Generally, it is desirable to use mechanical contacts whenever possible to apply
power to a timer or its signal inputs. When using solid state devices, be cautious
of inrushes and back-EMF that may exceed the ratings on such devices. Some
timers are specially designed so that signal inputs switch at a lower voltage
than is used to power the timer (models designated as “B” type).
Avoid contact between the timer and sulfurous or ammonia gases, organic sol-
vents (alcohol, benzine, thinner, etc.), strong alkaline substances, or strong acids.
Do not use the timer in an environment where such substances are prevalent. Do
not allow water to run or splash on the timer.
Timing Accuracy Formulas
Timing accuracies are calculated from the following formulas:
=
=
1 x Maximum Measured ꢀalue – Minimum Measured ꢀalue x 100%
2 Maximum Scale ꢀalue
Repeat Error
Voltage Error
Tv - Tr x 100%
Tr
Tv: Average of measured values at voltage ꢀ
Tr: Average of measured values at the rated voltage
=
Tt - T20 x 100%
T20
Temperature Error
Tt: Average of measured values at °C
T20: Average of measured values at 20°C
=
Average of Measured ꢀalues - Set ꢀalue x 100%
Maximum Scale ꢀalue
Setting Error
www.IDEC.com