IAL/CEL/LEL Series
Magnetic Circuit Protectors
Introduction • 147
Poles • 148
Handles • 150
Configurations • 154
Operating Characteristics • 157
Delay Curves • 159
Specifications • 163
Decision Tables • 165
IAL/CEL/LEL Series
Hydraulic Magnetic Circuit Protectors
INTRODUCTION
IAL/IUL/IEL/LEL magnetic circuit protectors provide low-cost
power switching, reliable circuit protection and accurate
circuit control for equipment in the international marketplace.
the LEL models are UL listed under the conditions of UL 489. Both
are CSA certified and CCC Approved. The IEL is CSA certified as
a supplementary protector per CSA C22.2–No. 235.
IAL models are for those applications where the unit’s inherent
attributes are desired, but compliance with the various
standards is not required.
The CEL model has achieved two new enhancements, including
a single pole, 125 amp rating with TÜV approval, and a parallel
4-pole version with 400 amp rating.
IUL models have been tested and approved in accordance with
UL 1077 requirements for UL recognition.
Airpax™ IAL/CEL/LEL circuit protectors are available in a wide
variety of configurations, including series, series with auxiliary
switch, shunt and relay with choice of delays and ratings in DC
and/or 50/60Hz or 400Hz versions. Single or multi-pole versions
are available with a variety of pole arrangements to meet your
specifications. Please see the appropriate product specification
table for ratings and limitations.
IEL/LEL models are VDE approved to VDE 0660, part 101. They
meet IEC spacing requirements, mandatory for equipment
which must comply with IEC specifications 601 and 950, and
VDE specifications 0804 and 0805. In addition, the IEL models
are UL recognized to UL 1077 as supplementary protectors and
IAL Series - Introduction
147
http://airpax.sensata.com
SINGLE POLE, STANDARD STUD TERMINAL
(SEE TABLE)
.281
STUD TERMINAL TYPES
[7.14]
.140
[3.56]
(SEE TABLE)
Screw Stud Thread
Dimension “A”
Dimension “B”
.510 .045
ꢀ12.95 1.14ꢁ
.652 .035
ꢀ16.56 0.89ꢁ
ON
M6
1.940
[49.28]
.545 .045
ꢀ13.84 1.14ꢁ
.687 .035
ꢀ17.45 0.89ꢁ
1/4 -20
M5
.142
[3.61]
OFF
.510 .045
ꢀ12.95 1.14ꢁ
.652 .035
ꢀ16.56 0.89ꢁ
.545 .045
ꢀ13.84 1.14ꢁ
.687 .035
ꢀ17.45 0.89ꢁ
10-32
.690
1.859
[17.53]
[47.22]
Single Pole
Mounting Detail
.755
2X 6-32 THREAD
[19.18]
.140 [3.56] DEEP
M3 ISO THD. OPTIONAL
.220
.402
[5.59]
[10.21]
1.448
[36.78]
Panel Mounting Detail
Tolerance .005 ꢀ.13ꢁ unless noted.
2.060
[52.32]
1.438
[36.53]
2.060
[52.32]
.432
[10.98]
2XØ .156
[3.96]
2.490
[63.24]
.750
[19.05]
Screw Terminal
Bullet Terminal
Clip Terminal
.281
Ø .250MAX.
.281
[7.13]
[6.35]
.967
[7.13]
[24.57]
1.940
1.940
[49.28]
[49.28]
.142
[3.61]
.375
[9.53]
.392
[9.96]
.592
[15.04]
Notes:
Tolerance .015 ꢀ.39ꢁ unless noted.
Dimensions in brackets ꢀ ꢁ are millimeters.
A Terminal protrusion dimensions are referenced from back of mounting
panel.
Bullet terminal receptacle should be .312 .001
diameter hole not less than .250 depth. Contact
Sensata for other bullet sizes.
B Each screw terminal is supplied with a 10-32x.312 ꢀ7.92ꢁ or M5 x 8mm
screw, flatwasher and external tooth lockwasher.
C Stud terminals are supplied with a flatwasher, external tooth lockwasher
and a 10-32 or M5 hex nut (<=70A) (<=50A for LEL),1/4-20 or M6 hex nut
(>70A)(>50A for LEL).
Note: Each outer terminal is supplied with a
flatwasher, tooth lockwasher and a hex nut.
IAL Series - Poles
148
MULTI-POLE CIRCUIT PROTECTORS
Multi-pole units are combined in an assembly with the trip
mechanisms internally coupled. A fault in any protected circuit
opens all poles simultaneously. Applications include use in
polyphase circuits, single-phase three-wire systems, or in two
or more related but electrically isolated circuits. A mix of
delays, ratings and configurations are offered. The auxiliary
switch is offered with either gold or silver contacts and is
available when a series construction pole is specified.
Two Pole Units
An assembly consisting of two single pole units, having their trip
mechanisms internally coupled, is available with either a single
toggle handle or with a handle per pole. Please see decision
one of the part number decision tables. Individual poles may
vary in ratings, delays and internal configurations. If the poles
are of series construction, an auxiliary switch may be included
in either or both poles, allowing you to mix SELV and hazardous
voltages.
Two Pole
IEL11
IELH11
(SEE TABLE)
.281
4X 6-32 THREAD
.140 [3.56] DEEP
[7.14]
.140
M3 ISO THD. OPTIONAL
.402
.220
[3.56]
(SEE TABLE)
[10.21]
[5.59]
ON
1.438
1.940
[36.53]
[49.28]
2.060
.142
[52.32]
[3.61]
OFF
1.515
1.515
[38.48]
MAX.
[38.48]
MAX.
2.490
.690
1.859
[17.53]
[63.24]
[47.22]
Note:
Tolerance .015 ꢀ.38ꢁ unless noted.
Dimensions in brackets ꢀ ꢁ are millimeters.
Two Pole*
Two Pole*
1.530
[38.86]
M6
.510
.652
4XØ .156
[3.96]
1/4 - 20
.545
.687
M5
.510
.652
1.448
10 - 32
.545
.687
[36.78]
2.060
[52.32]
Screw stud
thread
Dim. “A”
Dim. “B”
( .035ꢀ
(
.045ꢀ
Note:
Each outer terminal is supplied with a flatwasher, tooth
lockwasher and a hex nut.
.750
Panel Mounting Detail
Tolerance .005 ꢀ.13ꢁ unless noted.
.432
[19.05]
.750
[10.97]
[19.05]
Note:
A Terminal protrusion dimensions are referenced from back of mounting panel.
B Each screw terminal is supplied with a 10-32x.312 ꢀ7.92ꢁ or M5 x 8mm screw, flatwasher and external tooth lockwasher.
C Stud terminals are supplied with a flatwasher, external tooth lockwasher and a 10-32 or M5 hex nut (<=70A), 1/4 -20 or M6 hex nut (>70A).
IAL Series - Poles
149
http://airpax.sensata.com
Three Pole and Four Pole Units
BX - FLAT ROCKER HANDLE
The three pole structure consists of three single pole units
assembled with an internal mechanical interlock which
actuates all units simultaneously. The units are available
with either a single toggle handle or with a handle per pole.
Units with four pole construction operate with a minimum
of two center toggle handles or with a handle per pole.
Please see decision one of the part number decision tables.
Mixing of delays, ratings and configurations is available in
each individual pole. The auxiliary switch is offered in any
series trip pole.
The innovative new design of our IAL/CEL/LEL BX Style
circuit protectors features a flat rocker that will satisfy your
aesthetic needs while guarding against accidental
actuation, providing the highest degree of circuit protection
and quality. Only Airpax offers this new standard in user
interface. Available on a variety of versions with a full range
of agency approvals, the IEL BX style circuit protectors meet
or exceed all current performance specifications, including
interrupting capacities up to 50,000 amperes.
Breaker poles are numbered consecutively when viewed
from the terminal side, with the ON position up, starting with
pole #1 on the left side and proceeding to the right.
.387 REF.
[9.84]
2.173 MAX.
[55.19]
Three Pole
IEL111
Mounting Detail*
.125
[3.17]
1.859
[47.22]
.768
[19.49]
1.395
[35.43]
2.490 MAX.
[63.25]
.750
2.265
[57.53]
MAX.
[19.05]
.750
[19.05]
1.239
[31.47]
Three Pole
IELH111
Mounting Detail*
.314
[7.98]
6-32 THD. MOUNTING
M3 ISO THD. OPTIONAL
.750 MAX.
[19.05]
.750
[19.05]
2.265
[57.53]
MAX.
.750
[19.05]
ACTUATION
ACCESS
(SEE NOTE)
2.280
[57.91]
HANDLE
HANDLE
POSITION "OFF"
WITH GUARD
POSITION "ON"
WITH GUARD
1.660
[42.16]
(SIXTH DECISION, G)
(SIXTH DECISION, G)
Four Pole
IEL1111
Mounting Detail*
1.530
[38.86]
OPTIONAL
GUARD
(SEE DETAIL ìCî)
SINGLE POLE
.750
[19.05]
HANDLE
HANDLE
POSITION "OFF"
GUARD WITH NO ACTUATE
OFF FEATURE
POSITION "ON"
GUARD WITH NO ACTUATE
OFF FEATURE
(SIXTH DECISION, X)
(SIXTH DECISION, X)
3.015
[76.58]
MAX.
.750
.750
[19.05]
[19.05]
1.660
[42.16]
.750
1.260
[32.00]
[19.05]
Four Pole
IELH1111
Mounting Detail*
.200
[5.08]
2X ÿ.156
[3.96]
3.030
[76.96]
HANDLE
HANDLE
POSITION "ON"
WITHOUT GUARD
Panel Mounting Detail
Mounting Detail Tolerance:
±.005 [.13] unless noted
POSITION "OFF"
WITHOUT GUARD
DETAIL "A"
NOTE: ACCESS IS LIMITED TO A DEVICE SMALLER THAN THE
UNDERWRITERS LABORATORY "ARTICULATED PROBE"
DEFINED IN UL-489 FIG. 11.1.7.2.1.
3.015
[76.58]
MAX.
.750
.750
[19.05]
[19.05]
.750
[19.05]
Note:
Panel Mounting Detail
Tolerance .015 ꢀ.39ꢁ unless noted. Dimensions in brackets ꢀ ꢁ are millimeters.
*See Single Pole Mounting Detail for Hole Sizes and Locations.
Tolerance .005 ꢀ.13ꢁ unless noted.
IAL Series - Handles
150
LELHP/CELHP CIRCUIT PROTECTORS
The Airpax™ LELHP/CELHP high current magnetic circuit protector compliments our entire series of LEL circuit protectors. Its unique,
parallel current sensing design provides precise current overload protection and reliability in the compact size of a two pole LEL.
The unit is ideal for high power DC applications such as drive motor systems and telecommunication power systems.
LEL is available in series and series with auxiliary switch configurations with a choice of delays for DC ratings of 125, 150, 175 and 200
amperes. The CEL has been enhanced to include these same ratings plus a 4-pole, parallel 400 amp rating for UL489A. The LELHP is
UL listed under the conditions of UL489 and CSA certified. The CELHP is UL listed under the conditions of UL489A. Mid-trip handle
indication, voltage trip and remote operator options complete the LELHP/CELHP circuit breaker series. Please see the individual
product tables for approved ratings.
Two Pole
1.515 MAX
.687
[17.45]
[38.48]
2X 6-32 THREAD
.740
[18.80]
(Note E)
.140 [3.56] DEEP
.281
[7.14]
M3 ISO THD OPTIONAL
.220
[5.59]
.545
[13.84]
.402
[10.21]
.140
[3.56]
.640
[16.26]
ON
2.490
[63.25]
1.047
[26.59]
1.438
[36.53]
2.060
[52.32]
1.940
[49.28]
1.282
[32.56]
OFF
1.859
[47.22]
.690
[17.53]
.750
[19.05]
1/4-20 STUD
(M6 x 1.0 STUD
OPTION)
Three Pole (Note D)
.740
[
]
18.80
Series Parallel with optional
1REC4 Auxiliary switch
Series Parallel
(
)
Note E
.220
[5.59]
.740
[
]
18.80
(
)
Note E
.402
[10.21]
C
NO
NC
OFF
OFF
OFF
1.438
[36.53]
2.060
[52.32]
BREAKER IN
OFF POSITION
2.490
[63.25]
-REC4
175/200 Parallel Pole
2.265MAX.
[57.53]
.110
[2.79]
6X 6-32 THREAD
.140 [3.56] DEEP
M3 ISO THD OPTIONAL
2.438 MAX
[61.93]
(SEE NOTE 1)
Four Pole (CEL _ _ P and CML _ _ P only)
DIM. "H"
(SEE TABLE)
8X 6-32 THREAD
.140 [3.56] DEEP
.402
.260
[6.60]
DIM. "H"
DIM. "H"
.220
5.59
10.21
M3 ISO THD OPTIONAL
(SEE TABLE)
(SEE TABLE)
Notes:
2.490
63.25
Tolerance ꢀ.01 ꢁꢀꢂ39 unless notedꢀ ꢃiꢄensions in ꢅracꢆets ꢁ 9 are ꢄilliꢄetersꢀ
A
B
Terꢄinal protrusion diꢄensions are referenced froꢄ ꢅacꢆ of ꢄounting panelꢀ
Each screw terꢄinal is supplied with a 0.-ꢂ2xꢀꢂ02ꢁ7ꢀ329 or M1 x 8ꢄꢄ screw,
flatwasher and external tooth locꢆwasherꢀ
OFF
OFF
OFF
OFF
1.438
36.53
2.060
52.32
C
Stud terꢄinals are supplied with a flatwasher, external tooth locꢆwasher and
a 0.-ꢂ2 or M1 hex nut (<=7.A), 0/4 -2. or M6 hex nut (>7.A)ꢀ
Units are supplied without ꢅus ꢅars ꢄust have a ꢄiniꢄuꢄ copper strap (0
ꢂ0/ꢂ2 x 0/2 x 0/06 ) of appropriate length to accoꢄꢄodate connections tying
each set of terꢄinals togetherꢀ
ꢃ
3.005
[76.33]
MAX
E
Other spacing availaꢅle upon requestꢀ Contact factory for assistanceꢀ
IAL Series - Handles
151
http://airpax.sensata.com
IALN/IULN PANEL SEAL CIRCUIT PROTECTORS
.130
[3.30]
The lALN/IULN family is a sealed toggle version of the IAL/IUL
family. The silicone rubber seal around the handle assures
panel seal integrity and makes this style a natural for harsh
environments.
6-32 MTG. SCREW
FOR HIGH SHOCK
MTG.
LOCKWASHER
ON
This sealed toggle family is available in one to three pole
models with ratings of .050 to 100 amperes.
OFF
1/2-32 HEX NUT
.142
2.040
[3.61]
.625
.750
[51.82]
[15.88]
[19.05]
Single Pole
Two Pole
Three Pole
KEYWAY
.060 [1.52]-.065 [1.65] WIDE
.030 [.76]-.035 [.89] DEEP
1.515
[38.48]
MAX.
2.265
[57.53]
MAX.
.750
[19.05]
1.375
[34.92]
2.490
[63.25]
.656
[16.66]
(Optional handle ꢄay ꢅe in
pole 2 instead
of pole 0ꢀ)
Panel Mounting Details: Tolerance .005 ꢀ.13ꢁ Unless noted.
Single Pole
Two Pole*
Three Pole*
.750
[19.05]
MAX.
.750
[19.05]
MAX.
.750
[19.05]
MAX.
Ø.156
[3.96]
.656
Ø.515
[16.66]
[13.08]
Optional handle
*See Single Pole Mounting Detail for Hole
Sizes and Locations.
Notes:
A
B
C
Terꢄinal protrusion diꢄensions are referenced froꢄ ꢅacꢆ of ꢄounting panelꢀ
Each screw terꢄinal is supplied with a 0.-ꢂ2xꢀꢂ02ꢁ7ꢀ329 or M1 x 8ꢄꢄ screw, flatwasher and external tooth locꢆwasherꢀ
Stud terꢄinals are supplied with a flatwasher, external tooth locꢆwasher and a 0.-ꢂ2 or M1 hex nut (<=7.A), 0/4 -2. or M6 hex nut (>7.A)ꢀ
IAL Series - Handles
152
IALX/IULX/IELX ROCKER HANDLE
The rocker style is available in one to four poles. Choose
either vertical or horizontal mounting with ON-OFF,
international markings or a combination of both.
1.859
[47.22]
2.490
[63.25]
1.375
[34.92]
Five front panel enhancing colors including black, white, red,
grey and orange are available.
1.940
[49.28]
[3.61]
2.249
[57.12]
.419
[10.65]
Single Pole
Panel Mounting Detail*
Single,Two & Three Pole
2X 6-32 THD. (TYP.)
Two Pole
Three Pole
Four Pole
Four Pole**
M3 ISO THD.
OPTIONAL
.750
[19.05]
1.510
[38.35]
2.361
1.972
[50.09]
ON
ON
ON
ON
ON
1.660
[42.16]
1.260
1.260
OFF
OFF
[32.00]
OFF
OFF
[32.00]
1.660
OFF
[42.17]
3.015
[76.58]
MAX.
1.499
[38.07]
MAX.
2.249
[57.12]
MAX.
.735
[18.67]
(HANDLE WIDTH)
.750
2X Ø .156
.200
.750
[19.05]
[3.96]
[5.08]
[19.05]
(Optional handle may be in
Pole 2 instead of Pole 1.)
Note:
*Mounting detail tolerance .005 ꢀ.13ꢁ Unless noted.
**See single mounting detail for hole sizes and locations.
A
B
Terminal protrusion dimensions are referenced from back of mounting panel.
Each screw terminal is supplied with a 10-32x.312ꢀ7.92ꢁ or M5 x 8mm screw,
flatwasher and external tooth lockwasher.
C
Stud terminals are supplied with a flatwasher, external tooth lock washer and
a 10-32 or M5 hex nut (<=70A), º -20 or M6 hex nut (>70A).
IALZX/IULZX/IELZX ROCKER HANDLE
The IALZX/IULZX/IELZX style adds our rocker handle options of
contrasting dual color rocker actuators, affording a clear visual
indication of the handle position and integrated handle guards, to
help prevent accidental turn-on and turn-off of the unit. Available
with a black rocker and white, red or green indicator color for
either ON or OFF indication.
Panel Mounting Detail
.420 REF
[10.67]
2.173 MAX.
[55.19]
1.859
[47.22]
.750 MAX.
[19.05]
.201
[5.11]
.772
[19.62]
.750
[19.05]
1.395
[35.43]
2.490 MAX.
[63.25]
ON
1.660
[42.16]
1.660
[42.17]
1.260
[32.00]
OFF
OPTIONAL
HANDLE GUARDS
1.239
[31.47]
.314
[7.98]
.506
[12.85]
2X Ø .156
[3.96]
.200
[5.08]
2X 6-32 THD.
M3 ISO THD.
OPTIONAL
Panel Mounting Detail
Tolerance .005 ꢀ.13ꢁ unless noted.
Note: Tolerance .015 ꢀ.38ꢁ unless noted.
Dimensions in brackets ꢀ ꢁ are millimeters.
IAL Series - Handles
153
http://airpax.sensata.com
Series and Switch Only
.281
[7.13]
Dimension B
(See Table)
CONFIGURATIONS
Series Trip
The most popular configuration for magnetic
protectors is the series trip where the sensing coil
and contacts are in series with the load being
protected. The handle position conveniently
indicates circuit status. In addition to providing
conventional overcurrent protection, it’s
simultaneously used as an on-off switch.
SERIES
SWITCH ONLY
1.940
[49.28]
Dimension A
(See Table)
Series with Auxiliary Switch
Shunt Trip
.648
[16.46]
The shunt trip is designed for controlling two
separate loads with one assembly. The control is
established by providing overload protection for the
critical load. When the current through this load
becomes excessive and reaches the trip point, the
protector will open and remove power from both
loads simultaneously. The total current rating of both
loads must not exceed the maximum contact rating.
C
NO
NC
1.055
[26.80]
1.290
[32.77]
BREAKER IN OFF POSITION
STUD TERMINAL TYPES
Dual Coil
Screw Stud Thread
Dimension “A”
Dimension “B”
By combining two electrically independent coils on
a common magnetic circuit, it is possible to provide
contact opening when either an over-current or trip
voltage is applied to the respective coils. One coil
will be a current trip coil with standard
.510 .045
ꢀ12.95 1.14ꢁ
.652 .035
ꢀ16.56 0.89ꢁ
M6
.545 .045
ꢀ13.84 1.14ꢁ
.687 .035
ꢀ17.45 0.89ꢁ
1/4 -20
M5
specifications. The second, or dual coil, can be used
to provide a control function permitting contact
opening from a remote interlock or other transducer
functions. Standard coils are 6, 12, 24, 48, 120 and
240 volts. Tripping is instantaneous and must be
removed (usually self-interrupting) after trip.
.510 .045
ꢀ12.95 1.14ꢁ
.652 .035
ꢀ16.56 0.89ꢁ
.545 .045
ꢀ13.84 1.14ꢁ
.687 .035
ꢀ17.45 0.89ꢁ
10-32
Shunt and Dual Coil
Auxiliary Switch (Applies to Series Trip Only)
This is furnished as an integral part of a series pole
in single or multi-pole assemblies. Isolated
electrically from the protector’s circuit, the switch
works in unison with the power contacts and
provides indication at a remote location of the
protector’s on-off status.
Dimension B
(See Table)
.278
[7.05]
.660 ±.045
[16.76] ±1.14]
1.26
[32.00]
1.940
[49.28]
Auxiliary switch contacts actuate simultaneously
with the main breaker contacts, and will open
regardless of whether the breaker contacts are
opened manually or electrically. For auxiliary switch
ratings below 6Vac or 5Vdc, an auxiliary switch with
gold contacts, designated as REG is available. Gold
contacts are not recommended for load current
above 100 milliamps.
.795
[20.19]
2.640 MAX.
[67.06]
(SEE NOTE A)
SHUNT
DUAL COIL
Spacing for VDE Switch
2.454 MAX.
[64.52]
(SEE NOTE A)
.187
[4.75]
.676
.971
[17.17]
[24.66]
Note:
.250
[6.35]
1.266
A Terminal protrusion dimensions are referenced from back of mounting
panel.
[32.16]
-IREC5
B Each screw terminal is supplied with a 10-32x.312ꢀ7.92ꢁ or M5 x 8mm
screw, flatwasher and external tooth lockwasher.
C Stud terminals are supplied with a flatwasher, external tooth lock
washer and a 10-32 or M5 hex nut (<=70A), 1/4-20 or M6 hex nut (>70A).
2.438 MAX.
[64.52]
.110
[2.79]
(SEE NOTE A)
.260
[6.60]
Note: Each outer terminal is supplied with a flatwasher,
tooth lockwasher and a hex nut.
-IREC4, -IREG4
IAL Series - Configurations
154
FIG.1
FIG.2
Barriers
CONFIGURATIONS (CONT.)
Relay Trip
This permits the overload sensing coil to be placed in a
circuit which is electrically isolated from the trip contacts.
The coil may be actuated by sensors monitoring pressure,
flow, temperature, speed, etc. Other typical applications
include crowbar, interlock and emergency/rapid shutdown
circuitry. Trip may be accomplished by voltage or current,
which must be removed after trip.
1.378
[35.00]
.303
[7.69]
1.098
[27.89]
.952
[24.18]
.670
[17.02]
.122
[3.11]
3.100
[78.74]
2.740
[69.60]
Voltage Trip
Sometimes called “dump circuits” or “panic trip circuits,”
these units make it possible to open main power contacts
with lower power inputs from one or more sources. This
configuration is becoming increasingly more important for
sensitive circuitry and denser packaging in automation
systems. Available in series, shunt or relay configurations.
FIG.3
FIG.4
Relay and ꢃual Coil
.79ꢀ
[20.19]
1.147
[29.13]
1.147
[29.13]
.04ꢀ
1.14]
.660
[16.76
.033
[.84]
.721
[18.31]
.721
[18.31]
.033
[.84]
.281
[7.14]
.722
[18.34]
2.560
[65.02]
2.560
[65.02]
1.330
[33.78]
1.940
[49.28]
NOTE:
THIS BARRIER CAN BE FLIPPED
TO COVER EITHER POLE.
PLEASE CONTACT FACTORY FOR
SPECIFIC PART NUMBER
2.640 MAX
BARRIER OPTIONS
Standard Optional
Rating Option
Barrier
Barrier
IEL
RELAY
DUAL COIL
240/415 VAC
415 VAC (VDE)
277/480 VAC
Fig. 1
Fig. 2
Fig. 2, 3 & 4
Fig. 3 & 4
Notes:
Tolerance .015 ꢀ.39ꢁ unless noted. Dimensions in brackets ꢀ ꢁ are millimeters.
A Terminal protrusion dimensions are referenced from back of mounting panel.
B Each screw terminal is supplied with a 10-32x.312ꢀ7.92ꢁ or M5 x 8mm screw,
flatwasher and external tooth lockwasher.
C Stud terminals are supplied with a flatwasher, external tooth lockwasher and
a10-32 or M5 hex nut (<=70A), 1/4 -20 or M6 hex nut (>70A).
1/4-20, M6 studs for AC
120/240 VAC multi-pole
125VDC
LEL
All multi-pole 50/60 Hz
Fig. 2
Fig. 2
Fig. 2
Fig. 3 & 4
Fig. 3 & 4
Fig. 3 & 4
All multi-pole 80 VDC, if opposite polarity
125VDC
Note: Optional barrier available with factory assigned part number. Contact
factory for assistance.
IAL Series - Configurations
155
http://airpax.sensata.com
Mid-Trip Handle
Positions
Panel Mounting
Detail
Mid-Trip Indication
Circuit protection, rapid fault location
and alarm capability are blended
together in the Airpax mid-trip
indication option. This option is
designed for automatic handle
movement to a middle position upon
electrical overload, allowing for easier
detection of the fault circuitand
minimizing downtime due to the
overload condition.
C
NO
NC
BREAKER IN ONOR MANUALLY
TURNED OFFPOSITION
MID-TRIP
POSITION
.ꢁꢁ7
.ꢀ18
2.931
[74.63
C
NO
NC
BREAKER INMID-TRIP
POSITION
TRIPPED)
(ELECTRICALLY
DIM.“A”
(SEE TABLE)
In the optional auxiliary switch
configuration, the switch allows an
alarm or signal to be forwarded when
the breaker trips and the handle
moves to the middle position. The
alarm can be disengaged by the
manual actuation of the handle to the
OFF position. Once the fault has been
corrected, the circuit breaker can be
reset to the ON position. The mid-trip
option is available in one, two or three
pole toggle handle packages and in
either standard panel screw or snap-in
mounting. Please see specification
tables of specific product for available
ratings.
.995
[25.27]
2.495
[63.37]
1.750
[44.45]
2.061
[52.35]
3.220
[81.79]
.687
[17.45]
Snap-In Mounting
The snap-in mounting adapter allows for
simplified mounting of most IEL/LEL
toggle handle products. Prior to
shipment, the adapter is attached to the
circuit breaker during our final product
assembly, allowing you to securely snap
the unit into a rectangular panel cut-out.
This eliminates the need for panel
mounting hardware and associated
assembly costs.
1.560
[39.62]
Available for units up to three poles,
with or without an option handle
guard.
PANEL MOUNTING OPTIONS
# of Poles
Dimension “A”
Panel Thickness
.760 .007
ꢀ19.30 .18ꢁ
.062 .005
ꢀ1.57 .13ꢁ
1 pole
Note: Tolerance .015 ꢀ.39ꢁ unless noted.
Dimensions in brackets ꢀ ꢁ are millimeters.
1.530 .007
ꢀ38.86 .18ꢁ
.062 .005
ꢀ1.57 .13ꢁ
2 pole
3 pole
Panel Mounting Detail
Tolerance .005 ꢀ.13ꢁ unless noted.
2.280 .007
ꢀ57.91 .18ꢁ
.062 .005
ꢀ1.57 .13ꢁ
IAL Series - Configurations
156
OPERATING CHARACTERISTICS
NOMINAL DCR /IMPEDANCE
Resistance (ohms)
DC Delays
Impedance (ohms)
AC, 50/60Hz Delays
Impedance (ohms)
AC, 400Hz Delays
Current Ratings
(Amps)
51, 52, 53, 59
45.8
61, 62, 63, 69
41, 42, 43, 49
0.20
28.5
71.94
2.85
0.76
0.12
0.032
0.010
0.006
0.0019
—
1.0
1.38
1.10
2.0
0.371
0.29
5.0
0.055
0.051
0.016
0.006
0.004
0.0018
0.00134
0.00133
0.00123
0.00114
0.00114
—
10.0
0.017
20.0
0.006
30.0
0.003
50.0
0.0019
0.00157
0.00147
0.00146
0.00135
0.00135
0.0005
0.0005
0.0004
0.0004
0.0004
0.0004
0.0003
60.0
70.0
—
80.0
—
90.0
—
100.0
125.0
150.0**
165.0**
175.0**
200.0**
250.0**
400**
Notes:
—
—
—
—
—
—
—
—
—
—
—
—
—
—
DCR and impedance based on 100% rated current applied and stablized a minimum of one hour.
No 53 delay on 125 amp single pole or 400 amp four pole devices
Tolerance: .02 amperes to 2.5 amperes, 20%ꢀ 2.ꢁ amperes to 20 amperes, 25%ꢀ 21 amperes to 50 amperes, 50%. Consult factory for special values and for coil
impedance of delays not shown
** Paralleled poles only, 400 amps only available on CELHP
IAL Series - Operating Characteristics
157
htp:/airpax.sensata.com
PERCENTAGE OF RATED CURRENT VS TRIP TIME IN SECONDS AT +25°C
Delay
41*
42*
43*
49*
51
100%
125%*
150%
200%
400%
600%
800%
1000%
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
No Trip
May trip
May trip
May trip
May trip
.5 to 6.5
2 to 60
.5 to 8
.15 to 1.9
2.2 to 25
12 to 120
.050 max.
.1 to 1.2
1 to 10
.02 to .4
.40 to 5
.006 to .25
.012 to 2
.012 to 2.2
.020 max.
.011 to .25
.04 to 1
.004 to .1
.006 to .2
.01 to .22
.020 max.
.004 to .1
.008 to .5
.015 to .55
.017 max.
.01 to .15
.015 to .8
.013 to .85
.017 max.
.004 to .15
.008 to .79
.015 to .88
.015 max.
.004 to .05
.006 to .15
.01 to .1
5 to 70
35 to 350
.100 max.
.3 to 3
1.5 to 20
.020 max.
.031 to .5
.15 to 2
.020 max.
.004 to .08
.006 to .1
.012 to .2
.017 max.
.008 to .1
.01 to .25
.013 to .5
.017 max
.004 to .1
.006 to .28
.011 to .5
.015 max
52
1.8 to 30
40 to 400
.100 max.
.35 to 7
6 to 60
53**
59
80 to 700
.120 max.
.7 to 12
15 to 150
.050 max.
.130 to 3
2 to 20
2 to 20
.23 to 9
.022 max.
.030 to 1
.2 to 3
.017 max.
.015 to .3
.02 to 2
61
62
10 to 120
50 to 700
.120 max
.44 to 10
1.8 to 100
50 to 600
.120 max
63
30 to 400
.100 max.
.3 to 7
10 to 150
.050 max.
.100 to 3
1 to 20
1.5 to 20
.022 max.
.030 to 1
.15 to 3
.4 to 10
69
.017 max.
.012 to .3
.015 to 2
.015 to 10
.016 max.
71
72
1.7 to 60
30 to 400
.100 max.
73
10 to 150
.050 max.
1.8 to 20
.023 max.
79
Notes:
All trip curves and trip currents are specified with the protector mounted in the normal vertical position at ambient temperature of +25° C. Protectors do not carry
current prior to application of overload. A: Ratings above 30 amps may deviate from the above limits by approximately 10% (130% for delay 49).
* No 53 delay on 125 amp single pole or 400 amp four pole devices
* 135% for delay 71, 72, 73 & 79
IAL Series - Operating Characteristics
158
DELAY CURVES
400Hz, DC, 50/60Hz Delay Curves (typ)
Inrush Pulse Tolerance
A choice of delays is offered for DC, 50/60Hz, 400Hz, or
combined DC/50/60Hz applications. Delays 49, 59, 69
and 79 provide fast-acting, instantaneous tripping and
are often used to protect sensitive electronic
equipment (not recommended where a known inrush
exists). Delays 41, 51, 61 and 71 have a short delay for
general purpose applications. Delays 42, 52, 62 and 72
are long enough for most transformers and capacitor
loads. Delays 43, 53, 63 and 73 are extra long for
special motor applications.
Pulse tolerance is defined as a single pulse of half sine wave
peak current amplitude of 8 milliseconds duration that will
not trip the circuit breaker.
The table on page 171 provides a guide to determine if the
inertia delay feature is required. Consult factory for further
assistance.
10000
10000
1000
1000
DELAY 61
DELAY 62
100
10
100
10
1
1
.1
.1
.01
.001
.01
.001
0
100 150 200
125
300
400
500
600
700
800
900
1000
0
100 150 200
125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
10000
1000
100
10
10000
1000
100
10
DELAY 69
DELAY 63
1
1
.1
.1
.01
.01
.001
.001
0
100 150 200
125
300
400
500
600
700
800
900
1000
0
100 150 200
125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
IAL Series - Delay Curves
159
htp:/airpax.sensata.com
DC Delay Curves (typ)
PULSE TOLERANCES
Delay
Pulse Tolerance
61, 62, 63, 71, 72, 73
61F, 62F, 63F, 71F, 72F, 73F
64, 65, 66 (0 - 50A)
10 times (approx.) rated current
12 times (approx.) rated current
25 times (approx.) rated current
20 times (approx.) rated current
18 times (approx.) rated current
64, 65, 66 (>50 - 80A)
64, 65, 66 (>80 - 100A)
10000
1000
100
10
10000
1000
100
10
DELAY 51
DELAY 53
1
1
.1
.1
.01
.01
.001
.001
0
100 150 200
125
300
400
500
600
700
800
900
1000
0
100 150 200
125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
10000
1000
100
10
10000
1000
100
10
DELAY 52
DELAY 59
1
1
.1
.1
.01
.01
.001
.001
0
100 150 200
125
300
400
500
600
700
800
900
1000
0
100 150 200
125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
IAL Series - Delay Curves
160
400Hz Delay Curves (typ)
*Available only in IAL/IUL/IEL; not available in LEL.
10000
10000
1000
100
10
1000
DELAY 41
DELAY 43
100
10
1
1
.1
.1
.01
.001
.01
.001
0
100 150 200
125
300
400
500
600
700
800
900
1000
0
100 150 200
125
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
10000
1000
100
10
10000
1000
100
10
DELAY 42
DELAY 49
1
1
.1
.1
.01
.01
.001
.001
0
100 150 200
125
300
400
500
600
700
800
900
1000
0
100 150 200
130
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
IAL Series - Delay Curves
161
htp:/airpax.sensata.com
DC/50/60Hz Dual-frequency Delay Curves (typ)
10000
1000
10000
1000
100
10
DELAY 71
DELAY 72
100
10
1
1
.1
.1
.01
.001
.01
.001
0
100 150 200
135
300
400
500
600
700
800
900
1000
0
100 150 200
135
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
10000
1000
100
10
10000
1000
100
10
DELAY 79
DELAY 73
1
1
.1
.1
.01
.01
.001
.001
0
100 150 200
135
300
400
500
600
700
800
900
1000
0
100 150 200
135
300
400
500
600
700
800
900
1000
PERCENT OF RATED CURRENT
PERCENT OF RATED CURRENT
IAL Series - Delay Curves
162
IAL/IUL/IEL/IDL/LEL SPECIFICATIONS
Trip Free
Moisture Resistance
Meet all the requirements of MIL-PRF-55629 when tested in
accordance with Method 106 of MIL-STD-202.
Will trip open on overload even when forcibly held in the ON
position. This prevents the operator from damaging the circuit
by holding the breaker on.
Shock
Trip Indication
Circuit protectors shall not trip when tested per MIL-STD-202,
Method 213, Test Condition I with 100% rated current applied
to delayed units and 80% rated current to instantaneous units.
The operating handle moves positively to the OFF or mid-trip
position on electrical overload.
Ambient Operation
IAL/IUL/IEL protectors operate in temperatures between –40°C
to +85°C.
Vibration
Circuit protectors shall not trip when vibrated per MIL-
STD-202, Method 204, Test Condition A with 100% rated
current applied to delayed units and 80% rated current to
instantaneous units.
Insulation Resistance
Not less than 100 megohms at 500 volts DC.
UL-1500 (Marine Ignition Protected)
Dielectric Strength
The IDL/IDLH is approved for Marine Ignition Protection (series
configuration only), covering ignition protected circuit break-
ers. This specification requires devices to be used in
accordance with the requirementsof U.S. Coast Guard and Fire
Protection Standard for Pleasure and Commercial Motor Craft,
ANSI/MFPA #302.
IAL/IUL/IEL protectors withstand 3750Vac (1250Vac for LEL),
60Hz for 60 seconds between all electrically isolated terminals
except auxiliary switch terminals shall withstand 600Vac, 60Hz
for REG and REC types. Four terminal dual coil and relay con-
struction (not offered in the LEL) will withstand 1500Vac.
Endurance
Operating as a switch, the operating life exceeds 10,000 oper-
ations, 6000 at rated load, 4000 without load, at a rate of 6 per
minute.
APPROXIMATE WEIGHT PER POLE
Electrical Characteristics
.050-100 amperes 80Vdc, 240Vac Max., 240/415Vac at 50
amperes Max., 50/60Hz and 400Hz. Consult factory for specific
product ratings. Units rated for 240/415Vac and above 50
amperes are not suitable for across-the-line motor starting.
Ounces
Grams
3.1
90
Poles
One through six poles available.
RECOMMENDED TORQUE SPECIFICATIONS
Construction
Series, shunt, relay dual coil and series with auxiliary switch
available in various delays and combinations.
Component
Torque (in-lbs)
6-32 Mounting Inserts
M3 Mounting Screws
10-32 Screw Terminals
M5 Terminal Screws
10-32 Stud Terminals
M5 Stud Terminals
6 to 8
Auxiliary Switch
4 to 5
When supplied shall be S.P.D.T. configuration. Non VDE
approved switches have a maximum UL rating of 10.0
amperes, 250 volts, 60Hz; 3.0 amperes, 50 volts DC (REC
type) or 0.1 amperes, 125 volts, 60Hz (REG type).
14 to 15
14 to 15
13 to 14
13 to 14
40 to 45
40 to 45
30 to 35
VDE approved switches have a maximum UL rating of 10.0
amperes, 250 volts, 60Hz (REC type); or 0.1 amperes, 125 volts,
60Hz (REG; type). The maximum VDE ratings are 1.0 amperes, 125
volts, 60Hz (REC type); 0.1 amperes, 125 volts, 60Hz (REG type).
1/4 - 20 Stud Terminals
M6 Stud Terminals
1/2 - 32 Mounting Bushing
Salt Spray (Corrosion)
Meet the requirements of MIL-PRF-55629 when tested in
accordance with Method 101 of MIL-STD-202.
Where applicable, mechanical support must be provide to the
terminals when applying torque
IAL Series - Specifications
163
htp:/airpax.sensata.com
IAL/IUL/IEL/IDL/LEL/LELHP SPECIFICATIONS
AGENCY APPROVALS - IAL/IUL/IEL
AGENCY APPROVALS - IDL/IDLP (MARINE)
Frequency
(Hz)
Minꢀ
VꢃE
(aꢄps)
UL 0.77 & CSA
(AIC)
VꢃE
(AIC)
Frequency
Voltage (Hz)
Minꢀ
Phase Poles
VꢃE
(aꢄps)
UL 0.77 & CSA
(AIC)
VꢃE
(AIC)
Voltage
61
Phase Poles TC OL UL/CSA
TC OL
UL/CSA
ꢀ.2-0..
0.0-01.
ꢀ.2-6.
ꢃC
-
0
0
0
0
2
0
0
0
0
0
0
0
0
0
0
2
0
0
0
0
0
0
0
0
0
0
2
2
2
2
2
0
0
0
0
2
0
0
0
0
0
0
0
.
.
.
.
.
0
0
0
0
.
0
0
0
0
.
.
0
0
0
.
.
0
0
0
.
0
.
0
ꢀ.2-0..
ꢀ.2-0..
ꢀ.2-1.
0.0-01.
ꢀ.2-7.
7.ꢀ0-0..
0.0-01.
210-ꢂ..
ꢀ.2-0..
ꢀ.2-1.
ꢀ.2-1.
ꢀ.2-7.
ꢀ.2-0..
ꢀ.2-0..
ꢀ.2-0..
ꢀ.2-0..
ꢀ.2-7.
ꢀ.2-0..
ꢀ.2-1.
ꢀ.2-1.
ꢀ.2-1.
ꢀ.2-8.
ꢀ.2-6.
ꢀ.2-0..
ꢀ.2-1.
ꢀ.2-1.
ꢀ.2-1.
ꢀ.2-1.
ꢀ.2-ꢂ.
ꢀ.2-1.
ꢀ.2-ꢂ.
ꢀ.2-1.
ꢀ.2-ꢂ.
ꢀ.2-1.
ꢀ.2-1.
ꢀ0.-7.
U2, 71..
U2, ꢂ...
U2, 1...
U2, 71..
U2, 71..
U2, 1...
U0, 0....
U2, 71..
U2, 1...
U0, 1...
U2, 0...
U2, 1...
U0, ꢂ...
Uꢂ, 01..
U0, 2...
Uꢂ, 01..
U0, 2...
U2, 2...
U2, ꢂ...
C2, 1...(0)
C2, 1...(2)
U0, 0...
U0, 1...
Uꢂ, 2...
U2, 2...
C2, 1...(0)
U2, 2...
C2, 1...(0)
U2, 2...
U2, 02..
C2, 1...(ꢂ)
C2, 1...(ꢂ)
C2, 1...(ꢂ)
C2, 1...(ꢂ)
U2, 01..
4...
48
ꢃC
-
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
-
-
-
-
-
-
-
U0, 1...
U0, 1...
U0, 0...
U2, 01..
U 0, 01..
U2, 01..
U0, 0...
-
-
-
-
-
-
-
61(4)
61(4)
61
ꢃC
-
0
-
-
48
ꢃC
-
2**
0
ꢃC
-
0
-
-
61
ꢃC
-
ꢃC
-
2**
-
-
8.
ꢃC
-
0
ꢀ.2-0..
ꢀ.2-0..
ꢀ.2-0..
ꢀ.2-6.
8.
ꢃC
-
0
ꢀ0.-1.
4...
021
21.
21.
1./6.
1./6.
1./6.
0
0
8.
ꢃC
-
0
-
-
0
2
8.
ꢃC
-
2
-
-
0&ꢂ
0
8.
ꢃC
-
ꢂ
-
-
021
ꢃC
-
2
-
-
21.
ꢃC
-
2+
-
-
ꢂ..
ꢃC
-
ꢂ++
ꢀ0.-1.
1...
021
1./6.
1./6.
1./6.
1./6.
0
0
-
-
021
0
0
-
-
AGENCY APPROVALS - IULQ (TAPPED COIL)
021(1)
02./24.
0
0
-
-
Frequency
Voltage (Hz)
021/21. 1./6.
Minꢀ
Phase Poles
VꢃE
(aꢄps)
UL 0.77 & CSA
(AIC)
VꢃE
(AIC)
0
2
-
-
TC OL
UL/CSA
021/21.(1) 1./6.
0
2 only
-
-
0
0
0
0
2/0-ꢂ./01
-
C2, 1...(0)
-
24.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
1./6.
4..
0&ꢂ
ꢂ
0
-
-
24.
2
-
-
21.
ꢂ
0
ꢀ0.-0..
2...
21.
ꢂ
0
ꢀ0.-0..
2...
21.
0
0
ꢀ0.-0..
2...
21.
ꢂ
2
ꢀ0.-0..
2...
AGENCY APPROVALS - IULD (DUST SEALED)
21.
ꢂ
0
ꢀ0.-0..
2...
Frequency
Voltage (Hz)
Minꢀ
Phase Poles
VꢃE
(aꢄps)
UL 0.77 & CSA
(AIC)
VꢃE
(AIC)
21.(1)
277
ꢂ
ꢂ only
-
-
TC OL
UL/CSA
ꢀ.2-0..
ꢀ.2-ꢂ.
0
0
0
2
2
2
2
2
2
2
2
0
-
-
21.
277
1./6.
1./6.
0&ꢂ
0
0
0
0
0
0
0
-
-
C2, 1...(ꢂ)
C2, 1...(ꢂ)
-
-
277
0&ꢂ
ꢂ
-
-
24./401
24./401
277/48.
277/48.
277/48.
27748.
48.
ꢀ0.-1.
2...
Notes:
0
ꢀ0.-1.
2...
** Paralleled poles; + 2 poles in series; ++ ꢂ poles in series; (0) With 021 A ꢄaxꢀ series fuse; (2) Series
coꢄꢅination with 2.3 or 223 series (0.. A ꢄaxꢀ); (ꢂ) With 0.. A ꢄaxꢀ series fuse; (4) With ꢅlocꢆed vent
construction (1) Non-standard constructionꢀ “Fit for further use” approval
ꢂ
-
-
-
-
-
-
-
-
-
-
-
-
-
-
ꢂ
ꢂ
0&ꢂ
0&ꢂ
ꢂ
48.
21.
0&ꢂ
AGENCY APPROVALS - LEL/LELHP
General notes:
Frequency
(Hz)
Minꢀ
VꢃE
(aꢄps)
UL483
(AIC)
VꢃE
(AIC)
Voltage
61
Phase
Poles
UL/CSA
ꢀ.1-1.
• All suppleꢄentary protectors are of the overcurrent (OC) type
ꢃC
-
0
-
71..
-
• The faꢄily of protectors has ꢅeen evaluated for end use application for use groups
(UG) A, B, C and ꢃ
61
ꢃC
-
2**
ꢂ**
0
0.0-01.
071-2..
ꢀ.1-0..
ꢀ.1-0..
021-01.
071-2..
ꢀ.1-7.
-
1. ...
1....
0....
1....
0....
0....
1...
-
61
ꢃC
-
-
-
8.
ꢃC
-
ꢀ0.-0..
2...
-
• The terꢄinals (FW) are suitaꢅle for factory wiring only (.)
8.
ꢃC
-
0
-
• The ꢄaxiꢄuꢄ voltage ratings for which the protectors have ꢅeen tested are shown in
the chart
8.
ꢃC
-
2**
ꢂ**
0
021-01.
2...
2...
ꢂ...
-
8.
ꢃC
-
010-2..
021
021/21.
021
021
02./24.
24.
ꢃC
-
ꢀ.1-7.
• The current is the aꢄperage range that the protectors have ꢅeen tested
ꢃC
-
2
ꢀ.1-1.
-
1...
• The tripping current (TC) for all of the protectors is either either “0” (in the range of
021% to 0ꢂ1% of aꢄpere rating) or “2” (ꢄore than 0ꢂ1% of aꢄpere rating)
1./6.
1./6.
1./6.
1./6.
0&ꢂ
0&ꢂ
0
0
ꢀ.1-4.
-
0....
1...
-
0
ꢀ.1-1.
ꢀ0.-1.
ꢀ0.-1.
-
2...
2...
-
2
ꢀ.1-7.
1...
• The overload rating (OL) – designates whether the protector has ꢅeen tested for
general use or ꢄotor starting applicationsꢀ
0&ꢂ
0
ꢀ.1-2.
1...
AGENCY APPROVALS - CELHP
8.
. – tested at 0ꢀ1 tiꢄes aꢄp rating for general use
ꢃC
-
4
4..
-
0.... AIC
(UL483A)
-
0 – tested at 6 tiꢄes AC rating or 0. tiꢄes ꢃC rating for ꢄotor starting
• The short circuit current rating (SC) – The short circuit rating in aꢄperes following a
letter and nuꢄꢅer designating the test conditions and any caliꢅration following the
short circuit test is defined ꢅelow:
AGENCY APPROVALS - CEL/CELP (COMMUNICATIONS)
Frequency
(Hz)
Minꢀ
VꢃE
UL 483A
(AIC)
VꢃE
Voltage
61
Phase
Poles
UL/CSA
ꢀ.1-1.
(aꢄps)
(AIC)
C – Indicates short circuit test was conducted with series overcurrent protection
U – Indicates short circuit test was conducted without series overcurrent protection
0 – Indicates a recaliꢅration was not conducted as part of the short circuit testing
2 – Indicates a recaliꢅration was perforꢄed as part of the short circuit testing
ꢃC
ꢃC
ꢃC
ꢃC
ꢃC
ꢃC
ꢃC
-
-
-
-
-
-
-
0
-
-
-
-
-
-
-
71..
-
-
-
-
-
-
-
61
2**
0
0.0-01.
ꢀ.1-0..
0.0-2..
2.0-21.
ꢀ.1-7.
1....
1....
0....
0....
1...
8.
8.
2**
ꢂ**
0
8.
021
8.
ꢂ – Indicates recaliꢅration was perforꢄed along with the dielectric and voltage
withstand for “Suitaꢅle for Further Use” rating
0
01ꢀ0-021
0....
IAL Series - Specifications
164
IAL/IUL/IEL DECISION TABLES
1
First Decision
SelectType andTerminal
The ordering code for IAL/IUL/IEL/LEL
circuit protectors may be determined by
following the decision steps in the
appropriate part number decision table
subsequent to this page.
Type
Description
Terminal
IAL
**IUL
***IEL
One handle per unit
Standard screw terminal,
no designation required
K
C
B
Stud terminals
Clip terminals
Bullet terminals
One handle per pole
IALH
**IULH
***IELH
One handle per unit
panel seal
IALN
The coding given permits a self-assigning
part number but with certain limitations.
Special applications may require a factory
assigned part number. Typical examples
are units with mixed ratings, combinations
of styles, or constructions not listed in the
third decision table, etc. With these, it is
suggested that order entry be by
description and/or drawings, and a part
number will be established. Additionally, it
is standard policy to establish a factory-
assigned part number whenever a
***IULN
One handle per unit,
rocker, bracket mounting
IALX
**IULX
***IELX
2
Second Decision
Poles
One handle per unit,
rocker, integral mounting
IALZX
**IULZX
***IELZX
1
Single pole
Two pole
11
One handle per unit
UL 1500
111
Three pole
*IDL
1111
Four pole*
One handle per pole
UL 1500
*IDLH
*Not available in toggle seal handle type.
Consult factory for 5 and 6 pole IEL part number.
One handle per unit
mid trip indication
***IML
One handle per pole
mid trip indication
Example:
***IMLH
descriptive drawing exists to provide cross
reference, traceability and manufacturing
control.
IEL 1 -1REC4- 61- 20.0 - 01 -V
One handle per unit,
rocker, accidental-off
protection
IALBX
**IULBX
***IELBX
One handle per unit,
mid trip indication, rocker,
accidental-off protection
1
2
3
4
5
7
**IMLBX
When specifying a circuit breaker for AC
motor start or high inrush applications, the
peak amplitude and surge duration should
be specified for factory assistance in rating
selection.
*UL Recognized
**UL Recognized, CSA Certiꢀed
***UL Recognized, CSA Certiꢀed, VDE Approved
4
Fourth Decision
Frequency & Delay
SW
-41
-42
-43
-49
-51
-52
-53
-59
-61
-62
-63
-69
-71
-72
-73
-79
Switch only
3
Third Decision
400Hz short delay
400Hz long delay
400Hz motor start
Internal Conꢀguration
For example the code shown is the code
for a single pole breaker with a series
construction and auxiliary switch,
designed for operation in a 50/60Hz
circuit. It has a short time delay, rating of
20 amperes and a marked black handle,
and is VDE approved.
Switch only (50, 70 or 100 amp switch)
-0
400Hz 150% instant trip
DC short delay
Series
-1
Series with auxiliary switch*
.110 quick connect
-1REC4
DC long delay
Series with auxiliary switch*
.187 quick connect
-1REC5
-1REG4
-1RS4
DC motor start
DC 125% instant trip
50/60Hz short delay
50/60Hz long delay
50/60Hz motor start
50/60Hz 125% instant trip
DC/60Hz short delay
DC/60Hz long delay
DC/60Hz motor start
Series with auxiliary switch
.110 quick connect
To determine the ordering number for your
particular IAL/IUL/IEL unit, simply follow
the steps shown. You may use this number
to place an order or as a reference for
further questions you may have.
Series with alarm switch,
electrical trip, .110 quick connect
terminals
Series with alarm switch,
electrical trip, .110 quick connect
terminals (mid-trip only)
-1RLS4
-1RS5
Series with alarm switch,
electrical trip, .187 quick connect
terminals
DC/60 Hz 135% instant trip
Shunt
-3
-4
For addition of inertial delay, add an ìFî to any
delay numeral.
Relay (not available in IEL/IELX)
Notes:
*
Only one auxiliary switch is normally supplied on two or three
pole units. Switch is located in the right-hand pole (viewed from
terminal end) unless otherwise speciꢀed.
V = VDE and CCC Approved
IEL, IELH and IELX circuit protectors are designed
to meet 8mm creepage clearance requirements for
installation Category 111, Pollution Degree 3, Case A as
measured in IEC 664. Intended for use in equipment to
comply with IEC 950, 601 and VDE 0804 & 0805.
The shaded areas denote VDE and CCC
(if applicable) Approval options.This approval
requires the addition of a V at the end of the
part number. The V will be added to any part
number formed entirely from shaded decisions.
If non-shaded areas are selected, the unit will not
be VDE or CCC Approved, but other approvals
still apply.
C = CCC Approved
This approval requires the addition of a C at the end
of the part number. The unit will not be VDE Approved.
Note: CCC Approval is pending.
Note: CCC Approval is pending.
IAL Series - Decision Tables
165
http://airpax.sensata.com
INDICATING
COLOR
5
Fifth Decision
6
Sixth Decision
ROCKER
HANDLE
COLOR
O
N
I
O
I
N
Rated Current
Optional
O
O
F
F
ROCKER
HANDLE
COLOR
O
O
F
F
INDICATING
COLOR
Standard hardware. No designation required.
Metric thread mounting inserts and terminals
Barrier
Use three numbers to print required
current value between .100 amps
minimum and 100 amps maximum.
-A
LINE
LINE
INDICATION “OFF”
Mounting/Indicator Code: F, G, H
-B
-C
-D
-E
-G
INDICATION “ON”
Mounting/Indicator Code: A, B, C
For example, use:
.100 or 2.00 or 10.0
(
)
277V (50/60Hz only) See note 3
LOAD
LINE
ON
ON
The VDE (lth) will be 95% of the
UL/CSA rated current.
LOAD
LOAD
LOAD
ON
LINE
OFF
LINE
LINE
OFF
O
O
O
ON
240/415V (50/60Hz only)
OFF
O
OFF
FIG.
1
FIG.
2
FIG.
5
FIG. 6
FIG.
3
FIG.
4
(
)
277V/480V (50/60Hz only) See note 4
MARKING DETAIL “A” (SEE TABLE)
Handle guard, (available in ZX, BX and snap-in
versions only)
-K
1/4 - 20 stud (M6 stud when -A option is selected)
(<=70A requires -K, if >70A do not use -K)
LINE
INDICATING
COLOR
-L
Handle lock
F
F
O
O
ROCKER
HANDLE
COLOR
-M
-P
Handle in opposite pole
Snap-in face plate adapter
120/240V 50/60Hz
I
N
O
7
Seventh Decision
Handle Color and Marking Selection
-U
-W
INDICATION “ON”
Mounting/Indicator Code: J, K, L
IAL, IUL, IEL, IALH,
IULH, IELH -Toggle Handle
Wire clamp supplied (VDE approved up to
and including 16.0 amps)
OFF
ON
OFF
O
LINE
O
LOAD LINE LOAD LINE LOAD LINE
O
ON
OFF
O
ON
OFF
ON
LOAD
-X
Marked*
ON-OFF
I-O
Handle guard with no actuation feature
(BX rocker only)
FIG.
1
FIG.
2
FIG.
5
FIG. 6
FIG.
3
FIG.
4
MARKING DETAIL “B” (SEE TABLE)
Color
Unmarked
-1
-2
Silver 5/16" (.312") bullet
Gold 5/16" (.312") bullet
Black
Yellow
Red
-00
-10
-20
-30
-40
-60
-90
-01 (STD)
-11
Notes:
1. One or more descriptions may be used as required.
2. When this is not used, table one may be substituted and U.S. thread and
two lockwashers will be supplied. Unit will be rated at 250V (50/60Hz only.)
3. VDE approved at 250Vac
-21
4. VDE approved at 415Vac
Blue
-31
Green
Orange
White
-41
LINE
-61
INDICATION “OFF”
Mounting/Indicator Code: M, N, P, R
-91
ON
LOAD
LINE
LINE LOAD
OFF
O
ON
O
OFF
O
FIG.
2
FIG.
3
FIG.
6
MARKING DETAIL “C” (SEE TABLE)
7
Seventh Decision
Rocker Handle Color, Indicator Color and Marking Selection (See Notes)
IALX, IULX, IELX, IALZX, IULZX, IELZX Rocker Handle (Single Rocker Color)
Vertical Mounting
Horizontal Mounting
Rocker
Handle
Color
On-Off
I-O
Fig.6
On-Off
I-O
Fig.3
Indicating
Color
Marking
Color
On-Off
Fig.4
I-O
Fig.5
Marking
Detail
On-Off
Fig.1
I-O
Fig.2
Unmarked
Indicates:
Black
Red
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
-00
-20
-40
-50
-90
-01
-21
-41
-51
-91
-02
-22
-42
-52
-92
-03
-23
-43
-53
-93
-04
-24
-44
-54
-94
-05
-25
-45
-55
-95
-06
-26
-46
-56
-96
White
White
Black
Black
Black
Grey
A
A
Orange
White
IALZX, IULZX, IELZX Rocker Handle (Dual Rocker Color)
Black
Black
Black
Black
Black
Black
White
Red
White
White
White
White
White
White
On
On
On
Off
Off
Off
-A0
-B0
-C0
-F0
-G0
-H0
-A1
-B1
-C1
-F1
-G1
-H1
-A2
-B2
-C2
-F2
-G2
-H2
-A3
-B3
-C3
-F3
-G3
-H3
-A4
-B4
-C4
-F4
-G4
-H4
-A5
-B5
-C5
-F5
-G5
-H5
-A6
-B6
-C6
-F6
-G6
-H6
Green
White
Red
Green
Black
Black
Black
White
Red
White
White
White
On
On
On
-J0
-K0
-L0
-J1
-K1
-L1
-J2
-K2
-L2
-J3
-K3
-L3
-J4
-K4
-L4
-J5
-K5
-L5
-J6
-K6
-L6
B
C
Green
IALBX, IULBX, IELBX, LELBX Rocker Handle (Dual Rocker Color)
Black
Black
Black
Black
White
Red
White
Red
Off
Off
Off
Off
-M0
-N0
-P0
-R0
N/A
N/A
N/A
N/A
-M2
-N2
-P2
-R2
-M3
-N3
-P3
-R3
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
-M6
-N6
-P6
-R6
Green
Yellow
Green
Yellow
Notes: A. Bezels of IALBX, IULBX, IELB, IELBX are black.
B. Consult factory for other marking options.
LEL DECISION TABLES
1
First Decision
5
Fifth Decision
SelectType andTerminal
Rated Current
Type
Description
Terminal
Use three numbers to print (.050 or 1.50 or 100)
Value between .050 amps and 100 amps.
Standard screw terminal,
no designation required
One handle per unit
One handle per pole
LEL
LELH
LML
K
C
B
Stud terminals
Clip terminals
Bullet terminals
One handle per unit, mid-trip
indication
6
Sixth Decision
LMLH
One handle per pole, mid-trip
indication
Optional
LELZX
LMLZX
LELBX
LMLBX
One handle per unit, rocker,
integral mounting
Metric thread mounting inserts
and terminals
-A
One handle per unit, rocker,
mid-trip indication, integral mounting
Example:
Barrier
-B
-F
-G
240V 50/60Hz
One handle per unit, rocker,
accidental-off protected
LEL 1 - 1REC4 - 61 - 20.0 - 01 -V
Handle guard, (available in ZX, BX and
snap-in versions only)
One handle per unit, rocker,
mid-trip indication, accidental-off
protected
1
2
3
4
5
7
1/4 - 20 Stud (M6 Stud when -A
option is selected) ( 50A requires -K,
>50A do not use -K)
-K
-L
Note: Other options available, consult factory.
Handle Lock
-M Handle in opposite pole
-P
Snap-in mounting plate adapter
4
Fourth Decision
-U
120/240Vac, 5000 A.I.C., 70A max.
2 pole only with barrier (VDE 250Vac)
Frequency and Delay
2
Second Decision
-51
DC short delay
125VDC
-V
-X
Poles
-52
-53*
-59
-61
-62
-63
-69
DC long delay
Handle guard with no actuate
"off" feature (see detail C)
1
Single pole
Two pole
DC motor start
11
Silver 5/16" (.312") bullet
Gold 5/16" (.312") bullet
-1
DC 125% instant trip
50/60Hz short delay
50/60Hz long delay
50/60Hz motor start
111
Three pole
-2
Notes:
1. One or more descriptions may be used as required.
2. When this decision is not used, decision 7 may be
substituted and U.S. thread will be supplied.
3.If (M5 or M6) studs are required, use “A” only on an LELK.
50/60Hz 125% instant trip
For addition of inertial delay, add an “F” to any
delay numeral.
*Not available above 100 amps.
3
Third Decision
Internal Conꢀguration
7
-1
Series
Seventh Decision
V = VDE and CCC Approved
-1REC4
-1REC5
-1REG4
Series with auxiliary switch
.110 quick connect
LELToggle Handle Color Selection
-01
-11
-21
-31
-41
-61
-91
Black w/ white markings
Yellow w/ black markings
Red w/ white markings
Blue w/ white markings
Green w/ white markings
Orange w/ black markings
White w/ black markings
The shaded areas denoteVDE and CCC (if applicable)
Approval options.This approval requires the addition of
aV at the end of the part number. TheV will be added to
any part number formed entirely from shaded decisions.
If non-shaded areas are selected, the unit will not be
VDE or CCC Approved, but other approvals still apply.
Series with auxiliary switch
.187 quick connect
Series with auxiliary switch
(gold contacts)
.110 quick connect
-1RS4
Series with alarm switch,
electrical trip,
.110 quick connect
C = CCC Approved
-1RLS4
Series with alarm switch,
electrical trip,
.110 quick connect*
The approval requires the addition of a C at the end
of the part number.The unit will not beVDE Approved.
See alternate 7th Decision for ZX and BX Rocker
Handles.
* Used only with mid-trip.
Notes: The LEL family of circuit breakers are designed
to meet 8mm creepage and clearance requirements for
installation Category 111, pollution degree 3, Case A as
measured in IEC 664. Intended for use in equipment designed
to comply with IEC 380, 435, 601 AND VDE 0730, 0804 & 0805.
LEL Series - Decision Tables
167
htp:/airpax.sensata.com
7
Seventh Decision
Rocker Handle Color, Indicator Color and Marking Selection (See Notes)
LELZX & LMLZX Rocker Handle (Single Rocker Color)
Vertical Mounting
Horizontal Mounting
Rocker
Handle
Color
On-Off
I-O
Fig.6
On-Off
I-O
Fig.3
Indicating
Color
Marking
Color
On-Off
Fig.4
Marking
Detail
I-O
Fig.5
On-Off
Fig.1
I-O
Fig.2
Unmarked
Indicates:
Black
Red
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
-00
-20
-40
-50
-90
-01
-21
-41
-51
-91
-02
-22
-42
-52
-92
-03
-23
-43
-53
-93
-04
-24
-44
-54
-94
-05
-25
-45
-55
-95
-06
-26
-46
-56
-96
White
White
Black
Black
Black
Grey
A
A
Orange
White
LELZX & LMLZX Rocker Handle (Dual Rocker Color)
Black
Black
Black
Black
Black
Black
White
Red
White
White
White
White
White
White
On
On
On
Off
Off
Off
-A0
-B0
-C0
-F0
-G0
-H0
-A1
-B1
-C1
-F1
-G1
-H1
-A2
-B2
-C2
-F2
-G2
-H2
-A3
-B3
-C3
-F3
-G3
-H3
-A4
-B4
-C4
-F4
-G4
-H4
-A5
-B5
-C5
-F5
-G5
-H5
-A6
-B6
-C6
-F6
-G6
-H6
Green
White
Red
Green
Black
Black
Black
White
Red
White
White
White
On
On
On
-J0
-K0
-L0
-J1
-K1
-L1
-J2
-K2
-L2
-J3
-K3
-L3
-J4
-K4
-L4
-J5
-K5
-L5
-J6
-K6
-L6
B
C
Green
LELBX Rocker Handle (Dual Rocker Color)
Black
Black
Black
Black
White
Red
White
Red
Off
Off
Off
Off
-M0
-N0
-P0
-R0
N/A
N/A
N/A
N/A
-M2
-N2
-P2
-R2
-M3
-N3
-P3
-R3
N/A
N/A
N/A
N/A
-M5
-N5
-P5
-R5
-M6
-N6
-P6
-R6
Green
Yellow
Green
Yellow
Notes: A. Bezels of IALBX, IULBX, IELB, IELBX are black.
B. Consult factory for other marking options.
LINE
INDICATING COLOR
ROCKER HANDLE
COLOR
ON
I
INDICATING COLOR
ON
I
O
OFF
ROCKER HANDLE
COLOR
OFF
O
O
OFF
ROCKER HANDLE
COLOR
INDICATING
COLOR
I
ON
LINE
LINE
LINE
INDICATION “OFF”
Mounting/Indicator Code: F, G, H
INDICATION “ON”
Mounting/Indicator Code: J, K, L
INDICATION “OFF”
INDICATION “ON”
Mounting/Indicator Code: A, B, C
Mounting/Indicator Code: M, N, P, R
ON
O
OFF
O
OFF
ON
LOAD
LINE
LOAD
LINE
ON
ON
LINE
LOAD
LINE
LOAD
ON
LINE
OFF
LOAD LINE
O
LOAD LINE
LINE LOAD LINE
OFF ON
LOAD LINE
LOAD
ON
OFF
O
ON
O
OFF
OFF
O
ON OFF
O
O
OFF
O
O
OFF
O
LOAD
ON
FIG. 2
FIG. 3
FIG. 6
FIG.
1
FIG. 2
FIG.
3
FIG.
4
FIG.
5
FIG. 6
FIG.
1
FIG.
2
FIG.
3
FIG.
4
FIG.
5
FIG.
6
Area reserved for
amperage marking.
MARKING DETAIL “B” (SEETABLE)
MARKING DETAIL “C” (SEE TABLE)
MARKING DETAIL “A” (SEETABLE)
LEL Series - Decision Tables
168
CEL DECISION TABLES
1
First Decision
5
Fifth Decision
SelectType andTerminal
Description
Rated Current
Type
Terminal
Use three numbers in build (.050 or 1.50 or 100).
CEL
One handle per unit, UL489A Listed
Standard screw terminal,
no designation required
Required value between .050 amps minimum
and 125 amps maximum.
CELH
CML
One handle per pole, UL489A Listed
K
C
B
Stud terminals
Clip terminals
Bullet terminals
Single pole only, one handle per unit
mid-trip construction, UL489A Listed
6
Sixth Decision
CMLH
One handle per pole
mid-trip construction, UL489A Listed
Optional
CELZX One handle per unit, rocker handle,
-A
Metric thread mounting inserts and
terminals
UL489A Listed
CMLZX Single pole only, one handle per unit,
rocker handle w/ RLS aux switch,
-B
Barrier
Example:
CEL 1 - 1REC4 - 51 - 20.0 - A - 01 -V
-G
Snap-in mounting plate adapter with
handle guard (ZX, BX and snap-in only)
mid-trip construction, UL489A Listed
CELBX One handle per unit, ꢁat rocker handle,
-K
1/4-20 Stud (M6 stud when metric option
-A selected) 50A requires -K, >50A do
not use -K
UL489A Listed
CMLBX Single pole only, one handle per unit,
ꢁat rocker handle w/ RLS aux switch,
mid-trip construction, UL489A Listed
1
2
3
4
5
6
7
-P
Snap-in mounting plate adapter
80VDC, 10000AIC, (required over 50A)
125VDC
-T
-V
2
-1
Silver 5/16” (.312”) bullet
Gold 5/16” (.312”) bullet
Second Decision
-2
Poles
Notes:
1
Single pole
Two pole
1. One or more descriptions may be used as required.
2. When this decision is not used, decision 7 may be
substituted and U.S. thread will be supplied.
11
111
Three pole
7
Seventh Decision
3
Third Decision
LELToggle Handle Color Selection
Internal Conꢀguration
-01
-11
-21
-31
-41
-61
-91
Black w/ white markings
Yellow w/ black markings
Red w/ white markings
Blue w/ white markings
Green w/ white markings
Orange w/ black markings
White w/ black markings
-1
Series
-1REC4
Series with auxiliary switch
.110 quick connect
V = VDE and CCC Approved
-1RLS4 ** Series with auxiliary switch
.110 quick connect, mid-trip only
The shaded areas denoteVDE and CCC
(if applicable) approval options. This
approval requires the addition of aV at
the end of the part number. TheV will be
added to any part number formed
entirely from shaded decisions. If
non-shaded areas are selected, the unit
will not beVDE or CCC Approved, but
other approvals still apply.
-1REC5
Series with auxiliary switch
.187 quick connect
-1RS4 ** Alarm switch, .110 quick connect
* Only one auxiliary switch is normally supplied on two
and three pole units switch is located in the right hand
pole (viewed from terminal end). Note, aux switch
followed by “R” indicates reverse mount option
** Not available for 125 amp single pole
See alternate 7th Decision for ZX and BX Rocker
Handles.
C = CCC Approved
4
The approval requires the addition of a
C at the end of the part number.The
unit will not beVDE Approved.
Fourth Decision
Frequency and Delay
-51
-52
-53*
-59
DC short delay
DC long delay
T =TÜV Approved
DC motor start
DC 125% instant trip
The approval requires the addition of a
T at the end of the part number. The
unit will only beTÜV EN60947-2
approved with a single pole,
For addition of inertial delay, add an “F” to any
delay numeral. Example: -51F
*Not available above 100 amps.
125 amp rating conꢀguration.
CEL Series - Decision Tables
169
htp:/airpax.sensata.com
7
Seventh Decision
Rocker Handle Color, Indicator Color and Marking Selection (See Notes)
LELZX & LMLZX Rocker Handle (Single Rocker Color)
Vertical Mounting
Horizontal Mounting
Rocker
Handle
Color
On-Off
I-O
Fig.6
On-Off
I-O
Fig.3
Indicating
Color
Marking
Color
On-Off
Fig.4
Marking
Detail
I-O
Fig.5
On-Off
Fig.1
I-O
Fig.2
Unmarked
Indicates:
Black
Red
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
-00
-20
-40
-50
-90
-01
-21
-41
-51
-91
-02
-22
-42
-52
-92
-03
-23
-43
-53
-93
-04
-24
-44
-54
-94
-05
-25
-45
-55
-95
-06
-26
-46
-56
-96
White
White
Black
Black
Black
Grey
A
A
Orange
White
LELZX & LMLZX Rocker Handle (Dual Rocker Color)
Black
Black
Black
Black
Black
Black
White
Red
White
White
White
White
White
White
On
On
On
Off
Off
Off
-A0
-B0
-C0
-F0
-G0
-H0
-A1
-B1
-C1
-F1
-G1
-H1
-A2
-B2
-C2
-F2
-G2
-H2
-A3
-B3
-C3
-F3
-G3
-H3
-A4
-B4
-C4
-F4
-G4
-H4
-A5
-B5
-C5
-F5
-G5
-H5
-A6
-B6
-C6
-F6
-G6
-H6
Green
White
Red
Green
Black
Black
Black
White
Red
White
White
White
On
On
On
-J0
-K0
-L0
-J1
-K1
-L1
-J2
-K2
-L2
-J3
-K3
-L3
-J4
-K4
-L4
-J5
-K5
-L5
-J6
-K6
-L6
B
C
Green
LELBX Rocker Handle (Dual Rocker Color)
Black
Black
Black
Black
White
Red
White
Red
Off
Off
Off
Off
-M0
-N0
-P0
-R0
N/A
N/A
N/A
N/A
-M2
-N2
-P2
-R2
-M3
-N3
-P3
-R3
N/A
N/A
N/A
N/A
-M5
-N5
-P5
-R5
-M6
-N6
-P6
-R6
Green
Yellow
Green
Yellow
Notes: A. Bezels of IALBX, IULBX, IELB, IELBX are black.
B. Consult factory for other marking options.
LINE
INDICATING COLOR
ROCKER HANDLE
COLOR
ON
I
INDICATING COLOR
ON
I
O
OFF
ROCKER HANDLE
COLOR
OFF
O
O
OFF
ROCKER HANDLE
COLOR
INDICATING
COLOR
I
ON
LINE
LINE
LINE
INDICATION “OFF”
Mounting/Indicator Code: F, G, H
INDICATION “ON”
Mounting/Indicator Code: J, K, L
INDICATION “ON”
Mounting/Indicator Code: A, B, C
INDICATION “OFF”
Mounting/Indicator Code: M, N, P, R
O
OFF
O
OFF
ON
LOAD
LINE
ON
ON
LINE
LOAD
ON
LINE
OFF
LOAD LINE
O
LOAD LINE
LINE LOAD LINE
OFF ON
LOAD LINE
LOAD
ON
ON
LOAD
LINE
LINE LOAD
OFF
O
ON OFF
O
O
OFF
O
OFF
O
ON
O
OFF
OFF
O
LOAD
ON
O
FIG.
1
FIG. 2
FIG.
3
FIG.
4
FIG.
5
FIG. 6
FIG.
1
FIG.
2
FIG. 3
FIG. 6
FIG.
3
FIG.
4
FIG.
5
FIG.
6
FIG. 2
Area reserved for
amperage marking.
MARKING DETAIL “B” (SEETABLE)
MARKING DETAIL “C” (SEE TABLE)
MARKING DETAIL “A” (SEETABLE)
CEL Series - Decision Tables
170
LELHP DECISION TABLES
V = VDE Approved
First Decision
SelectType with StudTerminals
The shaded areas denoteVDE approval
options. This approval requires the
addition of aV at the end of the part
number. TheV will be added to any part
number formed entirely from shaded
decisions. If non-shaded areas are
selected, the unit will not beVDE
LELPK
One handle per unit
LMLPK
LELZXPK
One handle per unit, mid-trip
One ZX rocker handle per unit (integral mounting)
LMLZXPK One ZX rocker handle per unit, mid-trip (integral mounting)
LELBXPK One BX rocker handle per unit (integral mounting)
LMLBXPK One BX rocker handle per unit, mid-trip (integral mounting)
approved, but other approvals still apply.
Example:
LELHPK 11 - 1REC4 - 51 - 125. - A - 01 - V
LELHPK
LMLHPK
One handle per pole
One handle per pole, mid-trip
1. One toggle handle per unit on 125A to 150A units (2-parallel pole)
2. 175A to 200A (3-parallel pole) requires handle in each pole, “H” selection
1
2
3
4
5
6
7
Second Decision
Poles
11
Two pole (up to 150 amps)
Three pole (160 to 200 amps)
111
7
Fourth Decision
Fifth Decision
Seventh Decision
Frequency and Delay
Rated Current (Amps)
Toggle Handle Color
Third Decision
DC 125% short delay (125 to 150 amp)
DC 135% short delay (160 to 200 amp)
DC 125% long delay (125 to 150 amp)
DC 135% long delay (160 to 200 amp)
DC 125% instant trip (125 to 150 amp)
DC 135% instant trip (160 to 200 amp)
125.
130.
135.
-01 Black w/ white markings
-11 Yellow w/ black markings
Internal Conꢀguration
Series
-51
-52
-59
-1
-21 Red w/ white markings
-31 Blue w/ white markings
-41 Green w/ white markings
-61 Orange w/ black markings
-91 White w/ black markings
-1REC4
Series with auxiliary switch
.110 quick connect
150.
175.
200.
-1REG4 Series, aux switch (gold contacts)
.110 quick connect
-1RLS4
Series with alarm aux switch
For addition of intertial delay, add an “F” to any
delay option. Example: - 59 becomes -59F
Additional ratings available.
.110 quick connect, mid-trip only
See LEL alternative 7th decision for
ZX & BX rocker handles
-1RLSG4 Series, alarm aux switch (gold
contacts), .110 quick connect,
mid-trip only
6
Sixth Decision
Optional (leave entry blank if none apply)
-1RS4
Series with alarm aux switch
.110 quick connect
-A
-G
-X
-P
Metric thread mounting inserts and terminals
Snap-in mounting plate adapter with handle guard (ZX, BX & snap-in only)
Handle guard with no actuate off feature (BX only, no mid-trip)
Snap-in mounting plate adapter
-1REC5
-1RLS5
Series with aux switch
.187 quick connect
Series with alarm aux switch
.187 quick connect, mid-trip only
Notes:
1. One or more descriptions may be used as required.
2. When this decision is not used, decision 7 may be substituted and U.S. thread will be supplied.
-1RS4
-1RS5
Series with alarm aux switch
.187 quick connect
Series with alarm aux switch
.187 quick connect, mid-trip
LELHP Series - Decision Tables
171
htp:/airpax.sensata.com
CELHP DECISION TABLES
V = VDE Approved
First Decision
SelectType
Terminal
The shaded areas denoteVDE approval
options. This approval requires the
addition of aV at the end of the part
number. TheV will be added to any part
number formed entirely from shaded
decisions. If non-shaded areas are
selected, the unit will not beVDE
Standard screw terminal,
no designation required
CELP
One toggle handle per unit
One toggle handle per pole
CELHP
CMLHP
K
C
B
Stud terminals
Clip terminals
Bullet terminals
One toggle handle per pole,
mid-trip construction
approved, but other approvals still apply.
CELZXP
CELBXP
One rocker handle per unit
One ꢁat rocker handle per unit
Example:
CELHPK 11 - 1REC4 - 51 - 125. - A - 01 - V
1. One toggle handle per unit is available only on 101A to 200A (two parallel pole construction)
2. 201A to 250A (three parallel pole constructions) require handles in each pole, “H” version
ꢀrst decision
3. Unit supplied with bullet terminals will not have buss bar installed, unless requested, buss bar
supplied standard to 150A only.
1
2
3
4
5
6
7
4. One handle per unit is available for 100A to 200A (two parallel pole constructions) and
201A to 250A (three pole constructions) (ZX & BX versions only)
5. 400 amps available with toggle handes only
Second Decision
Poles
11
Two pole (up to 150 amps)
Three pole (160 to 250 amps)
Four pole (400 amps)
111
1111
7
Fourth Decision
Fifth Decision
Seventh Decision
Third Decision
Frequency and Delay
Rated Current (Amps)
Toggle Handle Color
Internal Conꢀguration
DC 125% short delay (101 to 150 amp)
DC 135% short delay (160 to 250 amp)
DC 125% long delay (101 to 150 amp)
DC 135% long delay (160 to 250 amp)
DC 125% motor start (101 to 150 amp)
DC 135% motor start (160 to 250 amp)
DC 125% instant trip (101 to 150 amp)
DC 135% instant trip (160 to 250 amp)
125.
130.
135.
-01 Black w/ white markings
-11 Yellow w/ black markings
-51
-52
-53
-59
-0
-1
Switch only
Series
-21 Red w/ white markings
-31 Blue w/ white markings
-41 Green w/ white markings
-61 Orange w/ black markings
-91 White w/ black markings
-1REC4
Series with auxiliary switch
.110 quick connect
150.
175.
200.
-1RLS4 * Series with alarm aux. switch
.110 quick connect, mid-trip only
400.
-1RS4 * Series with alarm aux. switch
.110 quick connect
See LEL alternative 7th decision for
ZX & BX rocker handles
Additional ratings available.
-1REC5
Series with auxiliary switch
.187 quick connect
6
Sixth Decision
-1RLS5 * Series with alarm aux. switch
Optional (leave entry blank if none apply)
.187 quick connect, mid-trip only
-A
-B
-G
Metric thread mounting inserts and terminals
Barrier
-1RS4 * Series with alarm aux. switch
.187 quick connect
Snap-in mounting plate adapter with handle guard (ZX, BX & snap-in only)
Handle guard with no actuate off feature (BX only, no mid-trip)
Silver 5/16” (.312”) bullet
1. Only one auxiliary switch is normally supplied
on two and three pole units. Switch is located in
the right hand pole (viewed from terminal end
panel mount position).
-X
-1
2. When more than one aux. switch is required,
change the 1 (of the 1REC4) to 2 or 3. If switches
are mixed, then use “2R” or 3R”.
-2
Gold 5/16” (.312”) bullet
Notes:
1. One or more descriptions may be used as required.
* Not available at 400 amps
LELHP Series - Decision Tables
172