P110-6001 [ETC]

INTELLIMISTTM Residential Atomizing Humidifier and Control; INTELLIMISTTM住宅雾化加湿器与控制
P110-6001
型号: P110-6001
厂家: ETC    ETC
描述:

INTELLIMISTTM Residential Atomizing Humidifier and Control
INTELLIMISTTM住宅雾化加湿器与控制

文件: 总8页 (文件大小:142K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
INSTALLATION  
INSTRUCTIONS  
INTELLIMIST™  
Residential Atomizing  
Humidifier and Control  
Part Numbers: P110-6000 (INTELLIMIST Humidifier and Humidistat)  
P110-6001 (INTELLIMIST Humidifier and INTELLISTAT™ Control)  
NOTE: Refer to Humidistat or INTELLISTAT control Installa-  
tion and Operating Instructions for more information on those  
devices.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
PACKAGE CONTENTS  
INSTALLATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4  
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Humidifier and Filter Installation. . . . . . . . . . . . . . . . . . . . . . . .2  
Water Supply Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Drainage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Humidistat or INTELLISTAT Control  
QUANTITY  
1
ITEM  
Humidifier  
Humidistat (P110-6000) or  
INTELLISTAT Control (P110-6001)  
1
1
1
1
1
1
Spray Nozzle  
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
1/4-in. OD Plastic Tubing (20 ft)  
In-Line Water Filter  
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6  
Water Filter Mounting Bracket  
Mounting Kit Containing:  
1 — Humidifier Mounting Template  
8 — No. 6 Mounting Screws  
2 — Threaded Adapters  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should in-  
stall, repair, or service air-conditioning equipment.  
3 — Locking Nuts  
1 — Self Piercing Valve Installation Kit*  
1 — Teflon Tape  
2 — Plastic Water Filter Mounting Bands  
Untrained personnel can perform basic maintenance func-  
tions such as changing filters. All other operations should be  
performed by trained service personnel. When working on air-  
conditioning equipment, observe precautions in the literature,  
tags and labels attached to the unit or accessory, and other safe-  
ty precautions that may apply.  
*Contains the following: self-piercing valve, rubber gasket, 2 bolts  
and nuts, flange, brass nut, brass ferrule, brass insert.  
INSTALLATION  
Location — The INTELLIMIST humidifier should be lo-  
cated on the supply air plenum. Use only with central air-  
conditioning systems. See Fig. 2.  
Follow all safety codes. Wear safety glasses and work  
gloves.  
The humidifier must be mounted over the evaporator coil  
or evaporator coil drain pan. Water damage may result.  
Before installing an accessory or performing maintenance  
or service on humidifier, turn off main power switch to  
unit. Electrical shock can cause injury or death. There may  
be more than one disconnect switch.  
GENERAL  
Adequate air and moisture mixing is essential to ensure that  
water does not accumulate in ductwork.  
The INTELLIMIST humidifier is an atomizing humidifier.  
The INTELLIMIST humidifier is normally located in the  
supply plenum and adds up to 24 gallons of humidity per day  
to the supply air using MICROPULSE™ technology to assure  
maximum efficiency. The INTELLIMIST humidifier is  
designed for use with 1 to 7.5 ton HVAC systems. Only the  
following controls may be used with the INTELLIMIST hu-  
midifier: the P110-0009 Humidistat, and the P374-1600  
INTELLISTAT combination temperature and humidity con-  
trol. Humidifier dimensions are shown in Fig. 1.  
Make sure site can be supplied with the necessary power re-  
quirements. Ensure that there is adequate clearance for service.  
Humidifier must not be installed where freezing tempera-  
tures may occur. Do not install on furnace jacket or where hu-  
midifier or components may be exposed to hot surfaces.  
On vertical equipment, allow clearance for the humidifier,  
filter, and water line away from furnace exhaust vent.  
Always install downstream of electric heat elements and  
electronic air cleaner.  
Do not use the humidifier with any non-approved humidi-  
stat or control. Damage to the unit may result.  
Manufacturer reserves the right to  
discontinue, or change at any time,  
specifications or designs without notice  
REPLACEMENT COMPONENTS DIVISION  
© CARRIER CORPORATION 5-01  
PRINTED IN U.S.A.  
LITERATURE NUMBER HUM-55SI  
CATALOG NUMBER 570-452  
REPLACES: HUM-53SI  
and without incurring obligations.  
4. Place the humidifier mounting template on the supply  
air duct in the desired mounting location.  
5. Drill four mounting holes for no. 6 screws on template.  
Cut or drill 1-in. spray nozzle hole in duct per tem-  
plate. Remove template from duct and discard.  
R
Humidifer  
C
MODEL: P110-300  
W1  
W2  
U
L
US  
C
LISTED  
3.50”  
6. Slide plastic locking nut over end of spray nozzle.  
Push metal end of spray nozzle into back of humidifier  
nozzle connection. Tighten locking nut onto nozzle  
connection, locking spray nozzle to humidifier. Turn  
locking nut to finger tight, then tighten an additional  
1/4 turn with pliers or a wrench. Do not overtighten.  
Overtightening fittings will cause them to crack and  
split, which will create water leaks. See Fig. 3.  
DOUBLE  
O-RING  
PUSH-IN  
CONNECTOR  
COLLET  
3.50”  
NOTE: The nozzle assembly can still be rotated 360  
degrees after tightening.  
7. Route spray nozzle through 1-in. hole in duct. Mount  
humidifier to supply air duct using four no. 6 screws  
provided.  
1DIA.  
8. On vertical equipment, if the nozzle is spraying away  
from the coil, there should be a minimum of three feet  
from the nozzle to the top of the plenum. If this is not  
available, then point the nozzle of the humidifier  
directly into the evaporator coil.  
9. The water filter mounting bracket is installed below  
the humidifier. Mount the bracket to the supply duct or  
another suitable location using 2 screws provided.  
Bracket must be installed in vertical position.  
DOUBLE  
O-RING  
PUSH-IN  
CONNECTOR  
COLLET  
2.75”  
10. Cut a piece of tubing of correct length to run from the  
humidifier water intake valve to the top of the water  
filter. See Fig. 4.  
10.25”  
Fig. 1 Humidifier Dimensions  
11. The water filter should be cleaned before use. Run at  
least 3 gallons of water through the water filter in the  
correct direction, until the outlet water appears clear  
(not grey or cloudy).  
Humidifier and Filter Installation Perform the  
following procedure to install the humidifier and filter:  
1. Turn off all power to HVAC equipment.  
2. The humidifier should be installed on the supply ple-  
num, perferably near the coil. Mounting near the evap-  
orative coil, if applicable, will allow any excess  
moisture to exit the system via the condensate drain  
pan.  
3. On vertical equipment, allow clearance of the humidi-  
fier and related components such as the water filter and  
plastic water line, from the exhaust vent.  
12. Remove plastic cap from double o-ring push-in con-  
nector on top of water filter. Ensure tube ends are cut  
square and push tube into double o-ring push-in con-  
nector until a stop is felt. Plastic or copper tube may be  
used. To remove tube, hold collet (inner ring) against  
connector body and pull.  
13. Remove plastic cap from double o-ring push-in con-  
nector on bottom of humidifier.  
PLENUM  
AIRFLOW  
HORIZONTAL  
EQUIPMENT  
HUMIDIFIER  
FURNACE  
DRAIN PAN  
EVAPORATOR  
COIL  
SPRAYING INTO COIL  
MINIMUM OF  
3REQUIRED FOR  
THIS LOCATION  
PLENUM  
PLENUM  
HUMIDIFIER  
HUMIDIFIER  
ALTERNATE  
LOCATION  
VERTICAL  
EVAPORATOR  
N-COIL  
ALTERNATE  
LOCATION  
VERTICAL  
EVAPORATOR  
A-COIL  
DRAIN PANS  
AIRFLOW  
FURNACE  
AIRFLOW  
FURNACE  
SPRAYING ABOVE COIL  
Fig. 2 Mounting Location  
2
14. Ensure tube ends are cut square and push tube into  
double o-ring push-in connector on humidifier until a  
stop is felt. Plastic or copper tube may be used. To  
remove tube, hold collet against connector body and  
pull.  
HUMIDIFIER  
PLASTIC  
LOCKING  
NUT  
15. Place water filter in mounting bracket and lock into  
place with 2 plastic mounting bands. See Fig. 4.  
Water Supply Connection After the humidifier  
and filter installation, the water supply connection needs to be  
completed. Perform the following procedure to connect the wa-  
ter supply:  
DOUBLE  
O-RING  
PUSH-IN  
SPRAY  
NOZZLE  
1. Locate 20-ft, plastic, water supply tube provided.  
CONNECTOR  
2. Remove plastic cap from double o-ring push-in con-  
nector on bottom of water filter. Ensure tube ends are  
cut square and push tube into double o-ring push-in  
connector until a stop is felt. Plastic or copper tube  
may be used. To remove tube, hold collet (inner ring)  
against connector body and pull.  
COLLET  
WATER INLET  
Fig. 3 Spray Nozzle Installation  
3. Select a convenient location within 20 ft of water filter  
for the self-piercing needle valve. Attach to either cold  
or hot water pipe. Attach valve body, rubber gasket,  
and flange to pipe with two bolts and nuts provided.  
See Fig. 5.  
HUMIDIFIER  
NOTE: Self-piercing water valve will only pierce  
1
copper pipes. For all other pipe material, a /8-in. hole  
PUSH-IN  
CONNECTORS  
PLASTIC  
TUBING  
will need to be drilled in pipe.  
4. Turn the valve all the way closed. Self-piercing valve  
will pierce the copper pipe and create a hole for water  
flow. Do not open valve at this time.  
5. Connect other end of tube to water valve. Slide brass  
nut over tube end with threaded end facing end of tube.  
Slide brass ferrule over tube end. Push brass insert into  
end of tube. Position ferrule over brass insert. Ferrule  
and insert will form a compression fitting to prevent  
leakage.  
MOUNTING  
BANDS  
WATER  
FILTER  
MOUNTING  
BRACKET  
WATER  
SUPPLY  
TUBING  
PUSH-IN  
CONNECTOR  
6. Push end of tube into water valve. Slide brass nut over  
ferrule and tighten onto brass connector on valve,  
attaching tube to valve.  
7. Open the valve to allow water flow through the valve  
to the humidifier water filter.  
Fig. 4 Water Filter Installation  
8. Check all fittings for leaks and tighten if necessary.  
Copper tubing may used in place of plastic tubing if  
required. Make sure plastic tubing is secured away  
from any heated surfaces or exhaust vents.  
SELF PIERCING  
VALVE BODY  
BRASS  
INSERT  
FERRULE  
BRASS  
NUT  
Drainage The humidifier should be mounted over the  
evaporator coil or evaporator coil drain pan. This will provide  
adequate drainage. Water damage may result if a drain pan is  
not provided under the humidifier installation location.  
Wiring The humidifier is wired differently when con-  
nected to the P110-0009 Humidistat, and the P374-1600  
INTELLISTAT™ control. Refer to the respective Installation  
Instructions.  
Use field-supplied wire. Follow NEC (National Electric  
Code) and all local codes.  
RUBBER  
GASKET  
TUBE  
WATER  
PIPE  
Refer to Fig. 6A-8 for wiring connections to the Humidistat  
and the INTELLISTAT control.  
FLANGE  
Humidistat or INTELLISTAT Control Configu-  
ration The Humidistat or INTELLISTAT control must be  
installed and configured before the humidifier will operate. Re-  
fer to the Humidistat or INTELLISTAT control installation in-  
structions for information on installing, calibrating and config-  
uring the control.  
NOTE: All parts are included in self-piercing valve installation kit.  
Fig. 5 Water Supply Valve Connections  
3
P374-1600  
P110-0009  
HUMIDISTAT  
INTELLISTAT  
THERMOSTAT  
24VAC  
W3  
R
C
R
C
R
C
G
W1/O/B  
HUM  
H1  
W2  
Y1  
Y2  
FURNACE  
HUMIDIFIER  
H1  
H2  
R
W1  
C
G
C
R
H1  
C
H2  
HUMIDIFIER  
NOTE: If only one wire is available from the furnace to the Humidis-  
tat, W1 may be obtained from the thermostat.  
FURNACE  
Fig. 7 Wiring to P374-1600 INTELLISTAT™  
Fig. 6A Wiring to P110-0009 Humidistat  
Control  
(With Thermostat)  
THERMOSTAT  
ADD  
P110-0009  
HUMIDISTAT  
Y1  
A
P110-0009  
WIRE  
R
HUMIDISTAT  
G
C
PART A  
C
HUM  
H1  
C
R
R
W1  
HUM  
H1  
ADD  
A
WIRE  
PART B  
HUMIDIFIER  
FURNACE  
24VAC  
W1  
C
H1  
H2  
C
R
W1  
Y1  
G
H1  
H2  
R
24VAC  
Fig. 6B Wiring to P110-0009 Humidistat  
C
(Without Thermostat)  
HUMIDIFIER  
FURNACE  
NOTE: When only 5 wires are available to the thermostat and Humi-  
distat, a P474-0410 Add-A-Wire accessory may be used as shown.  
P110-0009  
HUMIDISTAT  
Fig. 8 Wiring with Add-A-WireAccessory  
R
C
HUM  
H1  
FURNACE  
W1  
HUMIDIFIER  
H1  
H2  
C
C
R
24VAC  
R
NOTE: The C and R terminals on the INTELLIMISThumidifier are  
not connected internally. They are provided for an easy tie-off point’  
when using one multi-conductor cable from the humidifier to the  
Humidistat. In this case H2 would need a jumper to C.  
Fig. 6C Wiring to P110-0009 Humidistat  
(Without Thermostat, Terminals R and C Are Used)  
4
day, the fan must be run in the non-heating modes to increase  
the humidity in the rooms. (See Tables 1 and 2.)  
This can be accomplished in one of three ways.  
OPERATION  
To start up the humidifier, open all supply water valves to  
allow water flow to the humidifier. Set the Humidistat or  
INTELLISTAT™ control to highest demand (99% humidity).  
When the humidifier is on (mist spray is activated), the red  
LED on the humidifier will be on.  
When connected to an INTELLIMIST™ or Humidistat  
control, the red LED will go on and off with the MICRO-  
PULSE™ control sequence.  
Spray mist operational check: Remove screws from humidi-  
fier and remove from unit. Attach a 2-ft. section of tube to bot-  
tom of humidifier and top of filter. Hold humidifier outside of  
the plenum and check to see that the spray mist is functioning  
correctly. Reinstall humidifier and replace original tubing.  
Reset the Humidistat to the recommended setting once  
the humidifier is operating correctly. (See Troubleshooting  
section.)  
For homes that are in very dry climates with low humidity  
levels (below 20% relative humidity [RH]), it may take 4 to 6  
weeks to notice an increase in humidity in the home. In low  
humidity areas all the moisture has evaporated from the wood,  
drywall, carpets, draperies, and furniture. Until this moisture is  
replaced, these materials will absorb moisture from the air,  
causing very little relative humidity rise in the home.  
As with any whole-house humidifier, the humidifier can  
only increase the moisture in the house when the fan is  
running. Therefore, in climates where little heating is required  
and the heating/fan system is therefore run very few hours per  
1. The INTELLISTAT control can be set to ON (see  
INTELLISTAT control Installation Instructions), then  
the INTELLISTAT will run the fan and humidifier any  
time the humidity is below the set point.  
2. The fan (see INTELLISTAT control Installation  
Instructions) can be programmed to run so many min-  
utes per hour during certain hours of the day. The  
humidifier will run any time the fan runs and the  
humidity is below the set point.  
3. The fan can be run continuously with the fan ON  
button. The humidifier will then run constantly on a  
call for humidity.  
Even though the INTELLIMIST humidifier can put out up  
to 24 gallons of water into the air per day, it may not be possi-  
ble to increase the humidity to a high level, especially if the  
outside humidity is fairly low. For instance, when outdoor air at  
40 F and 20% relative humidity is heated up to 72 F, the result-  
ing humidity in the house is 8%. The amount of humidity that  
can be added to the air is limited by the airflow in the ductwork  
and the temperature of the air. Hot air (furnace is running) can  
hold 6 times as much moisture as the air can hold when only  
the fan is running. It is much easier to increase the humidity in  
the house with the furnace running versus when only the fan is  
running. Both applications are limited by the amount of mois-  
ture that can be put into the air going through the ductwork  
without the moisture actually condensing in the ductwork.  
Table 1 Recommended Indoor Humidity Levels  
Table 2 Outside Temperature at Which  
Condensation is Likely to Occur  
OUTSIDE TEMP (F)  
RECOMMENDED RH  
WINDOW TYPE/CONDENSING TEMP (°F)  
INDOOR RH  
40  
30  
45%  
40%  
35%  
30%  
25%  
20%  
15%  
(% RH)  
Single Pane  
Double Pane  
Triple Pane  
50  
45  
40  
35  
30  
25  
20  
15  
10  
43  
38  
34  
28  
22  
15  
8
18  
11  
2
10  
0
20  
10  
10  
25  
35  
0
8  
20  
30  
10  
20  
LEGEND  
Relative Humidity  
RH  
0
11  
LEGEND  
Relative Humidity  
NOTE: With a constant indoor temperature of 70 F.  
RH  
5
In rare cases where white powder is noticed on the interior  
of the house, this is an indication that the water filter needs to  
be replaced.  
Only use Totaline® replacement parts.  
• Water filters (Part Number P110-0002 [6-in.],  
P110-0008 [13-in.])  
• Nozzle/Tube assembly (Part Number P110-0012)  
• Replacement nozzle (Part Number P110-0001)  
MAINTENANCE  
The water supply should be tested for water hardness to de-  
termine filter replacement schedule. Water hardness kits are  
available from local home improvement centers or hardware  
stores. If the water hardness is 15 grains per gallon or under, the  
water filter should be replaced once a year. If the water hard-  
ness is higher than 15 grains per gallon, the water filter should  
be replaced every 3 months during heating season. If the hu-  
midifier is being run continuously (not just during heating sea-  
son), then the water filter should be replaced every 6 months.  
TROUBLESHOOTING  
Refer to the table below for troubleshooting.  
PROBLEM  
POTENTIAL CAUSE  
REMEDY  
Humidity Reading Will  
Not increase  
Low existing moisture  
Allow more time for moisture to increase. It may take several weeks to notice an  
increase in humidity in your home. This is due to the fact that virtually all moisture  
has evaporated from wood, drywall, carpets, draperies, and furniture. Until this  
moisture is replaced, materials will absorb moisture from the air, causing very little  
humidity rise in the rooms.  
Clogged filter  
Flush filter with up to three gallons of water (or until the water flow is clear) to pre-  
vent micro fine particles from clogging the sprayer nozzle.  
Cracked or split fittings  
The plastic fittings supplied with the humidifier should be finger tightened, plus 1/4  
turn with pliers. The brass compression fittings should be tightened with a wrench,  
and then re-checked for leaks.  
Improper position of spray  
nozzle  
Correct position of humidifier spray nozzle. On short plenums, if the spray is hitting  
the end of the plenum, turn spray toward the coil.  
Humidifier installed on a  
heat pump  
The lower air temperature of the heated air absorbs less water.  
Too Much Moisture in  
Duct  
Incorrect controller  
Pulse not turned on  
Verify that either the Totaline Humidistat (P110-0009) or INTELLISTATcontrol  
(P374-1600) are being used. Any other controller will cause a continuous (non-  
pulsed) spray.  
Check humidistat or INTELLISTAT control to make sure pulse is turned on. If  
pulse is set to off, humidifier sprays constantly, producing too much water.  
Tonnage not properly set  
Improper wiring  
Set controller to correct tonnage to match the air handler.  
Ensure HUM wire from humidistat is connected to W or W1 terminal on furnace,  
but NOT to G or fan terminal.  
Humidifier Will Not  
Spray  
Blocked nozzle  
No signal or power  
Remove and rinse nozzle.  
Check the controller to make sure there is a humidity demand. Three raindrops will  
be displayed on the humidistat. A small vertical bar will display in the lower left cor-  
ner of display on the INTELLISTAT control. If symbol appears, check wiring.  
6
INTELLIMISTRESIDENTIAL ATOMIZING HUMIDIFIER  
LIMITED ONE-YEAR WARRANTY  
One-Year Warranty This CARRIER CORPORATION (herein referred to as COMPANY) product is warranted  
to be free from defects in material and workmanship. If it appears within one year from the date of original installa-  
tion, whether or not actual use begins on that date, that the product does not meet this warranty a new or remanu-  
factured part at the COMPANYS sole option, to replace any defective part will be provided without charge for the  
part itself; PROVIDED the defective part is returned to our distribution through a qualified servicing dealer.  
THIS WARRANTY DOES NOT INCLUDE LABOR OR OTHER COSTS incurred for diagnosing, repairing,  
removing, installing, shipping, servicing or handling of either defective parts or replacement parts. Such costs may  
be covered by a separate warranty provided by the installer.  
THIS WARRANTY APPLIES ONLY TO PRODUCTS IN THEIR ORIGINAL INSTALLATION LOCATION AND  
BECOMES VOID UPON REINSTALLATION.  
LIMITATIONS OF WARRANTIES ALL IMPLIED WARRANTIES (INCLUDING IMPLIED WARRANTIES OF  
FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY) ARE HEREBY LIMITED IN DURATION TO  
THE PERIOD FOR WHICH THE LIMITED WARRANTY IS GIVEN. SOME STATES DO NOT ALLOW LIMITATIONS  
ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE MAY NOT APPLY TO YOU. THE  
EXPRESSED WARRANTIES MADE IN THIS WARRANTY ARE EXCLUSIVE AND MAY NOT BE ALTERED.  
ENLARGED, OR CHANGED BY ANY DISTRIBUTOR, DEALER, OR OTHER PERSON WHATSOEVER.  
ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORK-  
ING HOURS. ALL REPLACEMENT PARTS, WHETHER NEW OR REMANUFACTURED, ASSUME AS THEIR  
WARRANTY PERIOD ONLY THE REMAINING TIME PERIOD OF THIS WARRANTY.  
THE COMPANY WILL NOT BE REPONSIBLE FOR:  
1. Normal maintenance as outlined in the installation and servicing instructions or owners manual including filter  
cleaning and/or replacement and lubrication.  
2. Damage or repairs required as a consequence of faulty installation, misapplication, abuse, improper servicing,  
unauthorized alteration or improper operation.  
3. Failure to start due to voltage conditions, blown fuses, open circuit breakers or other damages due to the  
inadequacy or interruption of electrical service.  
4. Damage as a result of floods, winds, fires, lightning, accidents, corrosive environments or other conditions  
beyond the control of the Manufacturer.  
5. Parts not supplied or designated by the Manufacturer, or damages resulting from their use.  
6. Manufacturer products installed outside the continental U.S.A., Alaska, Hawaii, and Canada.  
7. Electricity or fuel costs or increases in electricity or fuel costs from any reason whatsoever including additional  
or unusual use of supplemental electric heat.  
8. ANY SPECIAL INDIRECT OR CONSEQUENTIAL PROPERTY OR COMMERCIAL DAMAGE OF ANY NATURE  
WHATSOEVER. Some states do not allow the exclusion of incidental or consequential damages, so the above  
limitation may not apply to you.  
This warranty gives you specific legal rights, and you may also have other rights which may vary from state to state.  
Model No.  
Unit Serial No.  
Date of Installation  
Name of Owner  
Installed by  
Address of Installation  
7
Your Assurance of Quality  
ALL Totaline® products are backed with a one-year  
warranty by Carrier Corporation, the worlds largest  
manufacturer of air conditioning, heating, and  
refrigeration products.  
Manufacturer reserves the right to  
REPLACEMENT COMPONENTS DIVISION  
© CARRIER CORPORATION 5-01  
PRINTED IN U.S.A.  
LITERATURE NUMBER HUM-55SI  
CATALOG NUMBER 570-452  
REPLACES: HUM-53SI  
discontinue, or change at any time,  
specifications or designs without notice  
and without incurring obligations.  

相关型号:

P1100-3S

Peripheral IC
ETC

P1100-3S-16.0M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-3S-8.0M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-3SE

Micro Peripheral IC
PLETRONICS

P1100-HC-1.0M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-11.0592M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-12.0M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-12.288M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-12.50M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-12.8102M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-14.7456M

CMOS Output Clock Oscillator,
PLETRONICS

P1100-HC-17.0M

CMOS Output Clock Oscillator,
PLETRONICS