PDI40C1FR0 [ETC]

;
PDI40C1FR0
型号: PDI40C1FR0
厂家: ETC    ETC
描述:

文件: 总4页 (文件大小:94K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Temperature Controls  
Single Loop PID-Controllers  
Type PDI 40  
• 4-dgt multi-range µP-based PID controller  
Temperature measurements in °C or °F  
• All software functions selectable by key-pad  
• PID, ON/OFF and neutral zone selectable controls  
• Autotuning, direct or reverse PID control and dynamic  
setpoint capability  
• One relay or SSR control output  
• One independent alarm setpoint (on request)  
• Front size: 48 x 48mm  
Product Description  
Ordering Key  
Model  
Measurement  
Power supply  
Control output (Out 1)  
Alarm output (Out 2)  
PDI40 T1 DRX  
4-dgt multi-range µP-based  
controller for temperature  
measurements in °C or °F and  
for process signals.  
Input from thermoresistance  
or thermocouple, PTC, 0/4  
to 20mA or 0 to 10VDC. Any  
parameter is fully programm-  
able by user-friendly key-pad.  
The PDI 40 includes auto-  
tuning, direct or reverse PID  
control and dynamic setpoint  
capability. The housing is easy  
to mount and ensures  
degree of protection of IP 54.  
a
Type Selection  
Measurements  
Power supply  
Control output (Out 1)  
Alarm output (Out 2)  
T1:  
T2:  
TC inputs: J, K, S  
RTD inputs:  
Pt100, Ni100  
PTC input: KTY81  
4 to 20 mA DC  
0 to 20 mADC  
0 to 10 VDC  
A:  
B:  
C:  
D:  
E:  
F:  
3:  
24 VAC, -10% +10%,  
50/60 Hz  
R:  
0:  
Relay  
SSR (12VDC)  
X:  
R:  
0:  
None  
Relay  
SSR (12VDC)  
1)  
48 VAC, -10% +10%,  
1)  
T3:  
C1:  
C2:  
V1:  
50/60 Hz  
115 VAC, -10% +10%,  
1)  
50/60 Hz  
230 VAC, -10% +10%,  
50/60 Hz (standard)  
120 VAC, -10% +10%,  
1)  
50/60 Hz  
240 VAC, -10% +10%,  
1)  
50/60 Hz  
24 VDC, -10% +10%  
1)  
with galvanic insulation  
1)  
On request  
Input Specifications  
Accuracy  
Temperature drift  
RTD (Pt100, Ni100)  
(@ 25°C ± 5°C, R.H. 60%) ± 0.5% f.s., ± 1 dgt  
TC (J, K, S)  
(@ 25°C ± 5°C, R.H. 60%) ± 0.5% f.s., ± 1 dgt  
PTC (RTY81, 990@25°C)  
(@ 25°C ± 5°C, R.H.60% )  
Process Signals (20mA, 10V)  
(@ 25°C ± 5°C, R.H.60% )  
RTD  
TC  
± 150 ppm/°C  
± 150 ppm/°C  
± 150 ppm/°C  
± 150 ppm/°C  
PTC (KTY 81, 990@25°C)  
Process signals  
Sampling rate  
Display  
Max. and min. indication  
RTD/TC/PTC  
1 time/second  
± 0.5% f.s., ± 1 dgt  
7-segment LED, h 12 mm  
± 0.5% f.s., ± 1 dgt  
Depending on range and type  
of the temperature probe  
Max. 7000 (700,0),  
Process signals  
Min. -999 (-99.9)  
Specifications are subject to change without notice (26.10.99)  
1
PDI 40  
Input Specifications (cont.)  
Compensation  
Input TC ranges  
Probe: TC-J  
RTD  
For 3-wire connections, line  
0°C/+32°F to +800°C/+1472°F  
0°C/+32°F to +1200°C/+2192°F  
0°C/+32°F to +1600°C/+2912°F  
resistance up to 10 Ω  
Cold junction, within the tem-  
perature range from 0 to 55°C  
Probe: TC-K  
Probe: TC-S  
TC  
Input process signal ranges  
-999 to 7000  
-99.9 to 700.0  
Input RTD ranges  
Probe: Pt100  
-200°C/-328°F to+600°C /+1112°F  
-99.9°C/°F to +600.0°C/+999.9°F  
-50°C/-58°F to +150°C/+302°F  
-50.0°C/-58.0°F to+150.0°C/+302.0°F  
Key-pad  
3 Keys: “S” to enter into the  
programming procedure;  
“UP/DOWN” for parameter  
selection; “S” + “UP/DOWN”  
for value programming  
Probe: Ni100  
Input PTC ranges:  
-50°C/-58°F to +150°C/+302°F  
Probe: KTY81 (990@ 25°C) -50.0°C/-58.0°F to +150.0°C/+302.0°F  
Output Specifications  
Output combinations  
- only one control output (Out 1)  
type: ON/OFF, PID;  
- one independent control  
output (Out 1) with additional  
alarm output: up, down alarm;  
- two dependent ON/OFF  
control outputs;  
- one ON/OFF control output (Out 1)  
with dependent relative or  
absolute alarm output:  
up, down alarm;  
Output Working  
Type of output  
Direct (cooling) or reverse (heating)  
Relay: 8A-AC1, 3A-AC3,  
250 VAC, 100.000 cycles  
SSR: 12 VDC/max. 12 mA  
Relay output: 2000 Vrms from  
output to: measuring input,  
AC power supply input.  
SSR output: no insulation from  
output to measuring input.  
2000 Vrms from output to  
AC power supply input.  
Insulation  
-
one control output with additional  
control output (dead band) to  
carry out the neutral zone control  
Alarm output  
1 (on request)  
Output types  
Alarm, ON/OFF, neutral zone  
Up alarm or down alarm  
0 to 100% of the input range  
Programmable minimum and  
maximum values  
Programmable hysteresis  
within the whole measuring  
range  
Programmable activation  
time delay (0 to 500 s)  
Programmable dead band  
within the whole measuring  
range  
Direct (cooling) or reverse  
(heating)  
Relay: 8A-AC1, 3A-AC3,  
250 VAC, 100.000 cycles  
SSR: 12 VDC/max. 12 mA  
Relay output: 2000 Vrms from  
output to measuring input,  
AC power supply input.  
SSR output: no insulation from  
output to measuring input.  
2000 Vrms from output to  
AC power supply input.  
Alarm functions  
Setpoint adjustment  
Limits of setpoint adjustment  
Control output  
Control types  
Setpoint adjustment  
Limits of setpoint adjustment  
1 (standard)  
PID, ON/OFF  
0 to 100% of the input range.  
Programmable minimum  
and maximum values  
Programmable proportional  
band within the whole input  
range (1 or 0.1 resolution);  
Programmable manual reset  
within the whole input range;  
Programmable integral time  
(0 to 3600 s);  
Programmable derivative  
time (0 to 3600 s);  
Programmable cycle time  
(1 to 500 s)  
Programmable hysteresis  
within the whole input range;  
Programmable activation time  
delay (0 to 500 s)  
Programmable dead band within  
the whole input range (available  
only if the 2nd output is present)  
ON/OFF control parameters  
Neutral zone control  
PID control parameters  
Output working  
Type of output  
ON/OFF control parameters  
Neutral zone control  
Insulation  
Software functions  
- step increase (dSI) parameter,  
programmable from 0 to  
100% of the input range  
- time interval (dSt) between  
two step increases pro-  
grammable from 1 to 3600 s  
Dynamic setpoint (see fig. 4)  
- Action only on 1st output,  
automatic increase of the  
set-point up to the pro-  
grammed one  
- Half band programming (drb)  
(0 to 100% of the input range)  
over which the dynamic  
set-point is active  
2
Specifications are subject to change without notice (26.10.99)  
PDI 40  
Software Functions (cont.)  
Scaling factor  
programming of the lower  
Autotuning  
Diagnostics  
Activation of autotuning  
feature or manual program-  
ming of the PID parameters  
The display flashes when  
the limits of the displayed  
range are exceeded.  
Over-range: EEEE  
limit of the displayed scale  
(only mA/V input) connected  
to 0 mA/V or 4 mA, programm  
ing of the higher limit of  
the displayed scale (only  
mA/V input) connected to  
20 mA/10 V.  
Offset programming value:  
from –999 to 999, selection  
of decimal point activation  
(1 or 0.1), °C/°F engineering  
unit selection, least digit  
approximation  
-
Under-range: - - - -  
Burn-out  
TC  
Opening of the probe connec-  
tion, EEEE indication  
Opening of the probe connec-  
tion, EEEE indication  
Probe short-circuit,  
RTD /PTC/mA/V  
- - - - indication  
Outputs  
In case of error the outputs  
are de-activated  
Supply Specifications  
General Specifications  
Dielectric strength  
120 VAC, 230 VAC, 240 VAC, Noise rejection  
3750 Vrms for 1 minute  
AC supply  
24 VAC, 48 VAC, 115 VAC,  
-10%+10%, 50/60 Hz  
2000 Vrms from power  
supply input to: measuring  
input, relay output  
NMRR  
CMRR  
40 dB, from 40 to 60 Hz  
100 dB, from 40 to 60 Hz  
Insulation  
EMC  
EN 50 081-1, EN 50 082-1  
EN 60730-1  
Safety standards  
Connector  
Housing  
Dimensions  
Material  
DC supply  
Insulation  
24 VDC, ±10%  
Fast-on 6,3 mm  
500 Vrms from power supply  
input to:  
measuring input, relay output  
48 x 48 x 107 mm  
ABS,  
self-extinguishing: UL 94 V-0  
Power consumption  
Operating temperature  
5 VA  
From 0° to +55°C  
(R.H. < 90% non-condensing)  
From -10° to +60°C  
(R.H. < 90% non-condensing)  
Degree of protection  
Weight  
Approvals  
IP 54 with gasket  
Approx. 250 g  
CE  
Storage temperature  
Insulation reference voltage  
300 Vrms to earth  
Dimensions  
Terminal Board  
Specifications are subject to change without notice (26.10.99)  
3
PDI 40  
Output Controls  
ON/OFF control  
ON/OFF control  
Fig. 1  
Fig. 2  
Neutral zone control  
Dynamic setpoint  
Fig. 3  
= negative hysteresis  
+ d = positive hysteresis  
dB = dead band  
Fig. 4  
-d  
drb = half band parameter  
dSI = step increase  
dSt = time interval between two step increases  
Front Panel Description  
2
” and ”  
Up and down keys for selecting programming parameters.  
- S + Up and down Keys for value programming.  
-
2. Display  
4-digit (maximum read-out 7000).  
3
Alphanumeric indication by means of 7-segment display for:  
- Displaying of the measured value, over-range, burn-out  
and programming indications.  
1
- Indication of programming parameters.  
3. LED’s  
4 red LEDs for the indication of:  
1. Key-pad  
- process variable under (–) the setpoint limit  
- process variable over (+) the setpoint limit  
- activation of the first output (out 1)  
- activation of the second output (out 2)  
1 green LED for the indication of the process variable equal  
to the setpoint.  
Set-up and programming procedures are easily controlled  
by the 3 pushbuttons.  
“S”  
- Key to enter the programming procedure  
(instrument configuration)  
4
Specifications are subject to change without notice (26.10.99)