Monitoring Relays
Frequency Monitoring
Types DFB01, PFB01
• Over/under frequency monitoring relays
• Measuring if power supply frequency is within set limits
• Measure on own power supply
• Measuring ranges
Voltage: 24 to 240 VAC
Frequency: 50 - 60 Hz
• Separately adjustable upper/lower level on relative
scale
• Adjustable delay on alarm or on recovery (0.1 to 30 s)
• Programmable latching or inhibit at set level
• Output: 8 A SPDT relay N.D. or N.E. selectable
• For mounting on DIN-rail in accordance with DIN/EN
50 022 (DFB01) or plug-in module (PFB01)
• 22.5 mm Euronorm housing (DFB01) or 36 mm
plug-in module (PFB01)
DFB01
PFB01
• LED indication for relay, alarm and power supply ON
Product Description
Ordering key
DFB 01 C M24
DFB01 and PFB01 are pre- even after the end of the Housing
cise frequency monitoring alarm condition. Inhibit func- Function
relays. The relays monitor tion can be used to avoid Type
their own power supply from relay operation when not Item number
24 to 240 VAC.
desired (maintenance, tran- Output
The advantage of using the sitions). The LED's indicate Power Supply
latch function is that the the state of the alarm and
relay can be kept energized the output relay.
Type Selection
Mounting
Output
Measuring range
Supply: 24 to 240 VAC
DIN-rail
Plug-in
SPDT
SPDT
50-60 Hz
50-60 Hz
DFB 01 C M24
PFB 01 C M24
Input Specifications
Output Specifications
Input
Output
Rated insulation voltage
Contact ratings (AgSnO2)
Resistive loads
SPDT relay
Own power supply DFB01:
PFB01:
A1, A2 (24 to 240 VAC)
2, 10 (24 to 240 VAC)
250 VAC
µ
Measuring ranges
Selectable by DIP-switches
2 Hz range
Upper level Lower level
AC 1
DC 12
8A @ 250 VAC
5 A @ 24 VDC
2.5 A @ 250 VAC
2.5 A @ 24 VDC
-0.2 to +2 Hz -2 to +0.2 Hz
50 Hz 49.8 to 52 Hz 48 to 50.2 Hz
60 Hz 59.8 to 62 Hz 58 to 60.2 Hz
Small inductive loads AC 15
DC 13
Mechanical life
Electrical life
≥ 30 x 106 operations
10 Hz range
-1 to +10 Hz -10 to +1 Hz
49 to 60 Hz 40 to 51 Hz
59 to 70 Hz 50 to 61 Hz
≥ 105 operations
50 Hz
60 Hz
(at 8 A, 250 V, cos ϕ = 1)
Operating frequency
Dielectric strength
Dielectric voltage
≤ 7200 operations/h
Contact input
DFB02
PFB02
Disabled
Enabled
Pulse width
Terminals Z1, Z2
Terminals 8, 9
> 10 kΩ
< 500 Ω
> 500 ms
≥ 2 kVAC (rms)
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Hysteresis
2 Hz range
10 Hz range
~ 0.05 Hz
~ 0.25 Hz
Specifications are subject to change without notice (12.12.05)
1
DFB01, PFB01
Supply Specifications
General Specifications
Power supply
Overvoltage cat. III
(IEC 60664, IEC 60038)
Power ON delay
Reaction time
1 s 0.5 s
Rated operational voltage
Through terminals:
DFB01: A1, A2
(input signal variation from
-10% to +10% or from
+10% to -10% of the range)
< 200 ms
24 to 240 VAC 15%
24 to 240 VAC 15%
PFB01: 2,10
Alarm ON delay
Alarm OFF delay
Dielectric voltage
Supply to output
Rated operational power
< 200 ms
4 kV
4 W
Accuracy
(15 min warm-up time)
200 ppm/°C
10% on set value 50 ms
0.02 Hz
Temperature drift
Delay ON alarm
Repeatability
Mode of Operation
DFB01 and PFB01 monitor Example 2
the frequency value of their (Latching mode - N.E. relay)
own power supply.
Indication for
Power supply ON
Alarm ON
LED, green
LED, red (flashing 2 Hz
during delay time)
LED, yellow
Output relay ON
The relay operates and the
Environment
Degree of protection
Pollution degree
Operating temperature
Storage temperature
yellow LED is ON as long as
the measured frequency is
(Non-latching mode - N.D. within the upper and lower
IP 20
Example 1
3 (DFB01), 2 (PFB01)
-20 to 60°C, R.H. < 95%
-30 to 80°C, R.H. < 95%
relay)
limits.
The relay releases and
Housing dimensions
DIN-rail version
Plug-in version
The relay operates and the latches in alarm position as
yellow LED is ON as soon soon as the measured fre-
as the measured frequency quency exceeds the upper
exceeds the upper set level set level or drops below the
or drops below the lower set lower set level for more than
level for more than the set the set delay time. The red
delay time. The relay releas- LED flashes until the delay
es when the measured fre- time has expired or the
quency comes back within measured value comes back
the upper and lower limits. within the limits. Provided
The red LED flashes until the that the frequency has
delay time has expired or dropped below the upper
the measured value falls off set level (minus hysteresis)
22.5 x 80 x 99.5 mm
36 x 80 x 94 mm
Weight
Screw terminals
Tightening torque
Approx. 150 g
Max. 0.5 Nm
acc. to IEC 60947
Approvals
CE-Marking
EMC
Immunity
Emission
UL, CSA
Yes
Electromagnetic Compatibility
According to EN 61000-6-2
According to EN 61000-6-3
the limits.
or exceeded the lower set
level (plus hysteresis), the
relay operates when the
interconnections
between
terminals Z1, Z2 or 8, 9 are
interrupted.
Function/Range/Level and Time Delay Setting
Adjust the system frequency Selection of level and time
Setpoint range
ON: 2 Hz
OFF: 10 Hz
setting DIP switch
3 and delay:
select the desired function
setting the DIP switches 1, 2 Upper knob:
and 4 as shown on the right. Setting of upper level:
To access the DIP switches -10 to +100% of the range.
open the grey plastic cover
Relay working mode
ON: Normally De-Energized
OFF: Normally Energized
as shown on the right.
Centre knob:
Setting of lower level:
-100 to +10% of the range.
System frequency
ON: 60 Hz
OFF: 50 Hz
Lower knob:
Setting of delay on alarm
time: 0.1 to 30 s.
Contact input
ON: Lacth function enable
OFF: Inhibit function enable
2
Specifications are subject to change without notice (12.12.05)
DFB01, PFB01
Wiring Diagrams
DFB01
PFB01
Operation Diagrams
Normally energized relay - Latch function
Dimensions
DIN-rail
Plug-in
94
90
22.5
99.5
36
28.5
28.5
Specifications are subject to change without notice (12.12.05)