PM-Hx22  
www.sontay.com  
0-5Vdc Current transducer  
Technical Overview  
The PM-Hx22 series of current transducers can be used to  
monitor motors, pumps or other electrical loads where a  
linear voltage output signal is required. The output can be  
used to check operating status, failure, wear/strain and  
power for consumption analysis. The linear output signal is  
produced by the unit which is proportional to the current  
passing through the transducer.  
Features  
3 Selectable ranges  
Load trending  
For use inside a separate fire or electrical enclosure  
For use in a Measurement category III environment,  
or less, as per IEC 61010-1:2001  
Motor control  
Specification  
Product Codes  
PM-H722LC  
Output  
0-5Vdc (self powered)  
50/60Hz  
Range selectable 0-10 / 0-20 / 0-40A solid core  
0-5Vdc output  
Frequency  
Insulation class  
Accuracy  
600Vac RMS  
±2% of full scale  
2 seconds  
PM-H722HC  
Range selectable 0-50 / 0-100 / 0-200A solid core  
0-5Vdc output  
Response time  
Ambient:  
PM-H922LC  
Temperature -15 to 60°C  
Range selectable 0-30 / 0-60 / 0-120A split core  
0-5Vdc output  
Humidity  
Sensing aperture:  
Solid core  
0 to 95% non-condensing  
19mm dia.  
Split core  
28 x 23mm (self gripping iris)  
Dimensions:  
Sold core  
74H x 76W x 27D mm  
74H x 65W x 26D mm  
IP20  
Split core  
Protection  
Country of origin  
U.S.A  
International Tel: +44 1732 861225  
UK Sales Tel: 0845 345 7253  
International Fax: +44 1732 861226  
UK Sales Fax: 0845 345 7353  
Page 1  
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or  
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.  
90800066 Issue 1  
Data Sheet Ref: 90501177  
Issue: 5.1  
PM-Hx22  
www.sontay.com  
0-5Vdc Current transducer  
Installation  
Installation notes (continued)  
(Ring type shown). Fig 1.  
1. The PM-Hx22 range of current transducers should only  
be installed by a competent, suitably trained technician,  
experienced in installation with hazardous voltages.  
(>50Vac & <1000Vac or >75Vdc & 1500Vdc)  
2. Ensure that all power is disconnected before carrying out  
any work on the PM-Hx22 range. Never rely on status  
indicating devices only to determine if power is present  
in a conductor.  
Fig 2.  
3. When installing the split-core version ensure that there  
are no dirt particles that will prevent good contact be-  
tween the core pieces when the device is closed.  
4. Mount the sensor in a suitable location using the two  
mounting holes in the base of the unit or use the self-  
gripping iris which eliminates the need for drill mounting  
(split core only).  
Wiring example  
5. Maximum output cable size is 2.5mm², care must be  
taken not to over tighten the screw terminals.  
6. Insure that the range selection slider is in the correct  
position for the current being monitored. Excessive cur-  
rent can damage the sensor.  
Notes  
Low conductor current:  
If the load is low you can loop the conductor through the  
sensor to provide adequate current and ensure accuracy.  
Example:-  
Load is 2.5A, pass the cable through the aperture 3 times  
and you will have a total load of 7.5A and set the amp range  
selector switch to 10A. See fig 1.  
High conductor current and large diameter cables:  
If the load is greater than the maximum specified for the  
transformer or the cable diameter is greater than the aper-  
ture of the current switch, you must use a suitable current  
transformer. See fig 2.  
Example:-  
When monitoring loads greater than 200A (when using the  
PM-H722HC), install a suitable CT with a 5A secondary.  
Pass a cable connected to the secondary winding of the  
current transformer through the aperture ten times and set  
the amp range selector switch to 50A.  
International Tel: +44 1732 861225  
UK Sales Tel: 0845 345 7253  
International Fax: +44 1732 861226  
UK Sales Fax: 0845 345 7353  
Page 2  
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or  
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.  
90800066 Issue 1  
Data Sheet Ref: 90501177  
Issue: 5.1  
PM-Hx22  
www.sontay.com  
0-5Vdc Current transducer  
Dimensions  
Solid core:  
22mm  
19mm  
74mm  
65mm  
67mm  
5mm  
27mm  
Split core:  
23mm  
28mm  
74mm  
65mm  
66mm  
26mm  
81mm  
International Tel: +44 1732 861225  
UK Sales Tel: 0845 345 7253  
International Fax: +44 1732 861226  
UK Sales Fax: 0845 345 7353  
Page 3  
Whilst every effort has been made to ensure the accuracy of this specification, Sontay cannot accept responsibility for damage, injury, loss or  
expense resulting from errors or omissions. In the interest of technical improvement, this specification may be altered without notice.  
90800066 Issue 1  

相关型号:

PM-H722LC

0-5Vdc Current transducer
ETC

PM-H922LC

0-5Vdc Current transducer
ETC

PM-HPN01

HOME PHONE NETWORKING BANDPASS FILTER
PMI

PM-HPN02

HOME PHONE NETWORKING BANDPASS FILTER
PMI

PM-IND019

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND019E

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND020

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND020E

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND024

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND024E

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND025

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI

PM-IND025E

COUPLED INDUCTOR For Uses in ADSL POTS Low Pass Filters
PMI