PP001073 [ETC]
FR-PVC Power and Control Cable;型号: | PP001073 |
厂家: | ETC |
描述: | FR-PVC Power and Control Cable |
文件: | 总3页 (文件大小:184K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
NYY-J Unshielded Multicore
FR-PVC Power and Control Cable
Application:
Power and control cable for fixed installation. Can be used indoors, outdoors, underground, in concrete and in water.
Construction:
Conductor:
Class 1 solid copper conductor according to BS EN 60228
(previously BS 6360)
Insulation:
PVC (Polyvinyl Chloride)
Filler:
PVC (Polyvinyl Chloride)
Sheath:
FR-PVC (Flame Retardant - Polyvinyl Chloride)
Cable Standards
Made in accordance with the following:
BS EN/IEC 60502-1, BS EN/IEC 60332-1-2
Characteristics:
Voltage Rating (Uo/U)
600/1000V
Temperature Rating:
Fixed
: -15°C to +70°C
: -5°C to +50°C
Flexed
Min. Bending Radius:
Fixed
: 12 × overall diameter
Core Identification:
Up to and including 5 core: colour coded or number coded
Sheath Colour:
Black
www.element14.com
www.farnell.com
www.newark.com
www.cpc.co.uk
Page <1>
23/09/15 V1.1
NYY-J Unshielded Multicore
FR-PVC Power and Control Cable
Dimensions:
Nominal Cross Nominal Thickness Nominal Thickness Nominal Overall
No. of
Cores
Nominal Weight
kg/km
Part Number
Sectional Area
mm²
of Insulation
mm
of Sheath
mm
Diameter
mm
PP001064
PP001065
PP001066
PP001067
PP001068
PP001069
PP001070
PP001071
PP001072
PP001073
1.5
2.5
4
0.8
0.8
1
10.4
11.3
13.1
11.6
12.1
14
166
212
299
198
252
355
465
232
302
428
3
4
5
1.5
2.5
4
0.8
0.8
1
1.8
6
1
15.4
12
1.5
2.5
4
0.8
0.8
1
13.1
15.2
Conductors
Class 1 Solid Conductors for Multi-Core Cables
Max. Resistance of Conductor at 20ºC
Circular, Annealed Copper Conductor
Plain Wires
Nominal Cross
Sectional Area
mm²
Ω / km
1.5
2.5
4
12.1
7.41
4.61
3.08
6
Electrical Characteristics:
Current Carrying Capacity
Current Carrying Capacity
Nominal Cross
Sectional Area
mm²
No. of
Cores
In Duct
In Air
Amps
Amps
1.5
2.5
4
26
18
25
34
3
34
44
www.element14.com
www.farnell.com
www.newark.com
www.cpc.co.uk
Page <2>
23/09/15 V1.1
NYY-J Unshielded Multicore
FR-PVC Power and Control Cable
Current Carrying Capacity
Nominal Cross
Sectional Area
mm²
No. of
Cores
In Duct
In Air
Amps
Amps
1.5
2.5
4
26
18
25
34
43
18
25
34
34
4
5
44
6
56
1.5
2.5
4
24
34
44
Ambient Temperature
Depth of Laying
: 30°C
: 0.5m
: 15°C
Ground Temperature
Thermal Resistivity of Soil : 12km/w
De-Rating Factors:
For Air Temperature other than 30°C
Air Temperature
De-Rating Factor
20°C
1.12
25°C
1.07
30°C
1
35°C
0.94
40°C
0.87
45°C
0.79
50°C
0.71
Part Number Table
Description
Reel Length Part Number
PP001064
NYY-J Multicore Cable, 3, 1.5mm²
NYY-J Multicore Cable, 3, 2.5mm²
NYY-J Multicore Cable, 3, 4mm²
NYY-J Multicore Cable, 4, 1.5mm²
NYY-J Multicore Cable, 4, 2.5mm²
NYY-J Multicore Cable, 4, 4mm²
NYY-J Multicore Cable, 4, 6mm²
NYY-J Multicore Cable, 5, 1.5mm²
NYY-J Multicore Cable, 5, 2.5mm²
NYY-J Multicore Cable, 5 , 4mm²
PP001065
PP001066
PP001067
PP001068
50m
PP001069
PP001070
PP001071
PP001072
PP001073
Important Notice : This data sheet and its contents (the “Information”) belong to the members of the Premier Farnell group of companies (the “Group”) or are licensed to it. No licence is granted
for the use of it other than for information purposes in connection with the products to which it relates. No licence of any intellectual property rights is granted. The Information is subject to change
without notice and replaces all data sheets previously supplied. The Information supplied is believed to be accurate but the Group assumes no responsibility for its accuracy or completeness, any
error in or omission from it or for any use made of it. Users of this data sheet should check for themselves the Information and the suitability of the products for their purpose and not make any
assumptions based on information included or omitted. Liability for loss or damage resulting from any reliance on the Information or use of it (including liability resulting from negligence or where the
Group was aware of the possibility of such loss or damage arising) is excluded. This will not operate to limit or restrict the Group’s liability for death or personal injury resulting from its negligence.
pro-POWER is the registered trademark of the Group. © Premier Farnell plc 2012.
www.element14.com
www.farnell.com
www.newark.com
www.cpc.co.uk
Page <3>
23/09/15 V1.1
相关型号:
©2020 ICPDF网 联系我们和版权申明