Monitoring Relays  
3-Phase, Phase Sequence/Loss - Asymmetry  
Types DPB02, PPB02  
• 3-phase phase sequence, phase loss and  
asymmetry monitoring relays  
• Detect when all 3 phases are present and have the  
correct sequence  
• Detect if asymmetry level is below the set value  
• Measure on own power supply  
• Selection of measuring range by DIP-switches  
• Adjustable asymmetry on relative scale  
• Adjustable delay function (0.1 to 30 s)  
• Output: 8 A relay SPDT N.E.  
• For mounting on DIN-rail in accordance with  
DIN/EN 50 022 (DPB02) or plug-in module (PPB02)  
• 22.5 mm Euronorm housing (DPB02)  
or 36 mm plug-in module (PPB02)  
DPB02  
PPB02  
• LED indication for relay, alarm and power supply ON  
Product Description  
3-phase or 3-phase+neutral Supply ranges from 208 to Housing  
line voltage monitoring relay 480 VAC covered by two Function  
for phase sequence, phase multi voltage relays.  
loss and asymmetry with  
built-in time delay function.  
Ordering Key  
DPB 02 C M23  
Type  
Item number  
Output  
Power supply  
Type Selection  
Mounting  
Output  
Supply: 208 to 240 VAC  
Supply: 380 to 480 VAC  
DIN-rail  
Plug-in  
SPDT  
SPDT  
DPB 02 C M23  
PPB 02 C M23  
DPB 02 C M48  
PPB 02 C M48  
Input Specifications  
Output Specifications  
Input  
Output  
SPDT relay  
250 VAC  
L1, L2, L3, N  
DPB02: Terminals L1, L2, L3, N  
PPB02: Terminals 5, 6, 7, 11  
Measure on own supply  
Rated insulation voltage  
Contact ratings (AgSnO2)  
Resistive loads  
µ
AC 1  
DC 12  
8 A @ 250 VAC  
5 A @ 24 VDC  
2.5 A @ 250 VAC  
2.5 A @ 24 VDC  
30 x 106 operations  
105 operations  
Measuring ranges  
208 to 240 VAC  
380 to 480 VAC (DPB02CM48) 323 to 550 VAC  
380 to 415 VAC (PPB02CM48) 323 to 475 VAC  
177 to 275 VAC  
Small inductive loads AC 15  
DC 13  
Mechanical life  
Electrical life  
Ranges  
Asymmetry  
2 to 22%  
of the nominal voltage  
(at 8 A, 250 V, cos ϕ = 1)  
Operating frequency  
7200 operations/h  
Dielectric strength  
Dielectric voltage  
2 kVAC (rms)  
Rated impulse withstand volt. 4 kV (1.2/50 µs)  
Specifications are subject to change without notice (06.11.00)  
2-51  
DPB02, PPB02  
Supply Specifications  
General Specifications (cont.)  
Power supply  
Rated operational voltage  
through terminals:  
Overvoltage cat. III  
(IEC 60664, IEC 60038)  
Indication for  
Power supply ON  
Alarm ON  
LED, green  
LED, red (flashing 2 Hz  
during delay time)  
LED, yellow  
L1, L2, L3, N  
5, 6, 7, 11  
(DPB02)  
(PPB02)  
M23:  
Output relay ON  
208 to 240 VAC ± 15%  
45 to 65 Hz  
380 to 480 VAC ± 15%  
45 to 65 Hz  
Environment  
Degree of protection  
Pollution degree  
IP 20  
M48:  
3 (DPB02), 2 (PPB02)  
-20 to 60°C, R.H. < 95%  
@ 475 VAC, 65 Hz  
-20 to 50°C, R.H. < 95%  
@ 550 VAC, 65 Hz  
-30 to 80°C, R.H. < 95%  
Operating temperature  
Rated operational power  
DPB02CM23, PPB02CM23  
DPB02CM48, PPB02CM48  
13 VA @ 230 VAC, 50 Hz  
13 VA @ 400 VAC, 50 Hz  
Supplied by L2 and L3  
Storage temperature  
Housing dimensions  
DIN-rail version  
Plug-in version  
22.5 x 80 x 99.5 mm  
36 x 80 x 87 mm  
General Specifications  
Weight  
Screw terminals  
Tightening torque  
Approx. 120 g  
Power ON delay  
1 s ± 0.5 s or 6 s ± 0.5 s  
Reaction time  
Max. 0.5 Nm  
Incorrect phase sequence or  
total phase loss  
Asymmetry  
Alarm ON delay  
Alarm OFF delay  
acc. to IEC 60947  
< 200 ms  
CE-marking  
Yes  
< 200 ms (delay < 0.1 s)  
< 200 ms (delay < 0.1 s)  
Accuracy  
(15 min warm-up time)  
± 1000 ppm/°C  
± 10% on set value ± 50 ms  
± 0.5% on full-scale  
Temperature drift  
Delay ON alarm  
Repeatability  
Mode of Operation  
Connected with the 3 phas- follows:  
es (and neutral) DPB02 and  
PPB02 operate when all 3  
tored. If the phase sequence Example 2  
is incorrect or one phase is (load monitoring)  
lost, the output relay releases  
max{|Vph-n|}  
nom. voltage  
phases are present at the when measuring phase-neu- immediately. Only 200 ms The relay releases in case of  
same time, the phase tral voltages.  
sequence is correct and the  
delay occurs. The failure is interruption of one or more  
indicated by the red LED phases or when the asym-  
asymmetry is under the set If the asymmetry exceeds flashing 5 Hz after the alarm metry exceeds the set level.  
level. the set level the red LED condition occurs.  
Asymmetry is defined as fol- starts flashing 2 Hz and the  
lows: output relay releases after Example 1  
the set time period. In any (mains network monitoring)  
case if phase-neutral mea-  
surement is selected both The relay monitors asymme-  
max{|Vph-ph|}  
nom. voltage  
when measuring phase- phase-phase and phase- try, phase loss and correct  
phase voltages and also as neutral voltages are moni- phase sequence.  
Function/Range/Level and Time Delay Setting  
Selection of function:  
Selection of measuring range:  
DIP-switch selector (3 to 4)  
34  
3 x 240 VAC (M23)  
3 x 480 VAC  
(DPB02CM48)  
Selection of asymmetry and  
time delay:  
DIP-switch selector (1 to 2)  
1
ON  
Power ON delay 6 ± 0.5 s  
3 x 208 VAC (M23)  
Centre knob:  
ON  
Power ON delay 1 ± 0.5 s  
3 x 380 VAC (M48)  
Setting of asymmetry on rela-  
tive scale.  
2
3 x 220 VAC (M23)  
3 x 400 VAC (M48)  
Phase-phase voltage  
Phase-neutral voltage  
Lower knob:  
Setting of delay on alarm time  
3 x 230 VAC (M23)  
3 x 415 VAC (M48)  
on absolute scale (0.1 to 30 s).  
2-52  
Specifications are subject to change without notice (06.11.00)  
DPB02, PPB02  
Wiring Diagrams  
Example 1  
Example 1  
N
N
L3  
L2  
L1  
L3  
L2  
L1  
µ
µ
L1 L2 L3  
16  
18  
4
3
5
6
7
m<3  
m<3  
U
U
L2  
L3  
L2  
L3  
N
11  
15  
1
Example 2  
Example 2  
N
N
L3  
L2  
L1  
L3  
L2  
L1  
µ
µ
5
6
7
4
3
L1 L2 L3  
16  
18  
m<3  
m<3  
U
U
L2  
L2  
L3  
L3  
11  
N
1
15  
PPB02  
DPB02  
Operation Diagrams  
L2-L1 or  
V
L2-L1-VL3-L2  
Asymmetry (+)  
Hysteresis  
L3-L2 or  
VL3-L2-VL1-L3  
Balanced  
Hysteresis  
Asymmetry (-)  
L1-L3 or  
VL1-L3-VL2-L1  
T
T
T
1 or 6 s  
1 or 6 s  
Relay ON  
Red LED ON  
L1  
L2  
L1  
L2  
L1  
L3  
L1  
L2  
L3  
L3  
L2  
L3  
Relay ON  
Red LED ON  
1 or 6 s  
Specifications are subject to change without notice (06.11.00)  
2-53  

相关型号:

PPB3781

LOW VOLTAGE SPEECH CIRCUIT
ERICSSON

PPB3781/02

LOW VOLTAGE SPEECH CIRCUIT
ERICSSON

PPBL102-2

Optoelectronic
ETC

PPBL102B

Optoelectronic
ETC

PPBL104-2

Optoelectronic
ETC

PPBL104B

Optoelectronic
ETC

PPBL105-2

Optoelectronic
ETC

PPBL105B

Optoelectronic
ETC

PPBL172-2

Optoelectronic
ETC

PPBL172B

Optoelectronic
ETC

PPBL174-2

Optoelectronic
ETC

PPBL174B

Optoelectronic
ETC