SV210724 [ETC]

;
SV210724
型号: SV210724
厂家: ETC    ETC
描述:

文件: 总2页 (文件大小:72K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Level Sensors  
Amplifier, Conductive  
Types SV 110/210, SV 115/215 (Discharging)  
• Level control for conductive liquids  
• Max.-min. control of DISCHARGING  
• SV 110/210: Fixed sensitivity  
• SV 115/225: Adjustable sensitivity  
• 10 A SPDT or 8 A DPDT output relay  
• LED-indications: Power supply and relay ON  
• AC or DC power supply  
SV 110/210  
SV 115/215  
Product Description  
Ordering Key  
SV 110 024  
Level control relay for con- charging. Usable for one  
ductive liquids which can level detection with pin 5  
control two levels of dis- and 7 short-circuited.  
Housing  
Output  
Power supply  
Type Selection  
Plug  
Output  
Supply: 24 VAC  
Supply: 115 VAC  
Supply: 230 VAC  
Supply: 24 VDC  
Circular  
SPDT  
DPDT  
SPDT  
DPDT  
SV 110 024  
SV 210 024  
SV 115 024  
SV 215 024  
SV 110 115  
SV 210 115  
SV 115 115  
SV 215 115  
SV 110 230  
SV 210 230  
SV 115 230  
SV 215 230  
SV 110 724  
SV 210 724  
SV 115 724  
SV 215 724  
Input Specifications  
Supply Specifications  
Level probe supply  
Level probe current  
Sensitivity  
Max. 24 VAC  
Power supply  
Rated operational voltage  
through pins 2 and 10 230  
AC types  
Overvoltage cat. II (IEC 60664)  
Max. 2.5 mA  
230 VAC ± 15%  
50/60 Hz, -5/+5 Hz  
115 VAC ± 15%  
50/60 Hz, -5/+5 Hz  
24 VAC ± 15%  
50/60 Hz, -5/+5 Hz  
250 VAC (rms)  
SV110/SV210  
ON  
OFF  
ON  
From 22 to 29 k  
From 32 to 40 kΩ  
From 2-6 to 20-30 k(adj.)  
From 3-13 to 30-40 k(adj.)  
From 3-9 to 42-52 k(adj.)  
115  
024  
SV115/SV215  
OFF (AC)  
OFF (DC)  
Rated insulation voltage  
Rated impulse withstand volt. 4 kV (1.2/50 µs) (line/neutral)  
Power supply  
Rated operational voltage  
724  
Rated insulation voltage  
DC types  
Overvoltage cat. II (IEC 60664)  
General Specifications  
24 VDC ± 15% (pin 2 pos.)  
None  
Indication for  
Power supply ON  
Output ON  
LED, green  
Rated impulse withstand volt. 800 V (1.2/50 µs)  
LED, red (724 only red)  
Environment  
Degree of protection  
Pollution degree  
IP 20 B  
3 (IEC 60664)  
Operating temperature  
Storage temperature  
-20 to +50ºC (-4 to +122ºF)  
-50 to +85ºC (-58 to +185ºF)  
Approvals  
CE-marking  
UL, CSA  
Yes  
Specifications are subject to change without notice (25.06.99)  
1
SV 110/210, SV 115/215  
Output Specifications  
SV110/SV115  
SV210/SV215  
Output  
Rated insulation voltage  
SPDT relay  
250 VAC (rms)  
(cont./elec.)  
DPDT relay  
250 VAC (rms)  
(Cont./elec., cont./cont.)  
Contact ratings (Ag-CdO)  
µ (micro gap)  
µ (micro gap)  
Resistive loads  
AC 1  
DC 1  
or  
AC 15  
DC 13  
10 A/250 VAC (2500 VAC)  
1 A/250 VAC (250 W)  
10 A/25 VDC (250 W)  
2.5 A/230 VAC  
8 A/250 VAC (200 VA)  
0,4 A/250 VDC (100 W)  
4 A/25 VDC (100 W)  
2.5 A/230 VAC  
Small inductive loads  
5 A/24 VDC  
5 A/24 VDC  
Mechanical life  
Electrical life  
5 x 107 operations  
105 operations  
5 x 107 operations  
105 operations  
Operation frequency  
7200 operations/h  
7200 operations/h  
Insulation voltages  
Rated insulation voltage  
AC  
2.0 kVAC (rms)  
(cont./elect.)  
None  
4 kV (1.2/50 µs)  
(cont./elect.) (IEC 60664)  
800 V  
2.0 kVAC (rms)  
(cont./elect.)  
None  
4 kV (1.2/50 µs)  
(cont./elect.) (IEC 60664)  
800 V  
DC  
AC  
Rated impulse withstand voltage  
DC  
Mode of Operation  
Max. and min. control of tion of 2 levels. The relay a conductive material (pin 7) Example 2  
discharging.  
operates when the max. elec- can be connected to the con- If only one level is required,  
trode is in contact with the li- tainer. If the container is made pins 5 and 7 must be inter-  
quid. The relay releases when of a non-conductive material, connected to select either  
Example 1  
The diagram shows the level the min. electrode is no an additional electrode is max. or min. control.  
control connected as max. longer in contact with the li- needed, indicated by the dot-  
and min. control, i.e. detec- quid. By use of a container of ted line in the diagram.  
Wiring Diagrams  
SV 1xx/SV 2xx, two levels  
Example 1  
SV 1xx/SV 2xx, one level  
Example 2  
Max.  
Min.  
Max. or Min.  
Power Supply  
Power Supply  
Operation Diagram  
Accessories  
Power supply  
Conductive level probe: 1 or 2 electrodes  
VH..., VPC..., VPP...  
VN..., VNY..., VNI...  
Max. electrode in liquid  
Min. electrode in liq.  
Relay on  
VT..., VTI..., VS...  
2
Specifications are subject to change without notice (25.06.99)  