VX1100 [ETC]
FREQUENZUMRICHTER 3 PHASEN VX 11KW ; FREQUENZUMRICHTER 3 PHASEN VX 11KW\n型号: | VX1100 |
厂家: | ETC |
描述: | FREQUENZUMRICHTER 3 PHASEN VX 11KW
|
文件: | 总8页 (文件大小:177K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
JAGUAR VX
Torque Vector System
Sensorless Vector Variable Frequency Inverters
- 0.4kW to 280kW
■
■
■
■
■
■
■
■
■
■
■
■
High performance, Torque Vector Control
Up to 250% torque at 1Hz
Low torque ripple at low speed
Fast torque response - 200mS, 0 - 100% load
Load speed regulation < 1% open loop
User friendly self tuning to motor
Ultra compact IP20 enclose (≤ 22kW)
Dual LED/LCD plain English display
User programmable I/O
Low motor noise profile
Auto energy saving function
Renowned IMO 5 year warranty
5
Specifications
JAGUAR VX ORDER CODES
JAGUAR VXP ORDER CODES
MOTOR RATING (kW)
VX40
-
VX75
-
VX150
-
VX220
-
VX400
VX550
VX750 VX1100 VX1500 VX1850 VX2200
-
4
-
VX750P VX1100P VX1500P VX1850P VX2200P
0.4
1.5
1.7
0.75
2.5
1.5
2.2
5.5
13
7.5
18
11
24
15
30
18.5
39
22
45
72
RATED O/P CURRENT (A)
100% RATED I/P CURRENT RMS
(AT 400V)*
3.7
5.5
9
2.9
5.5
7.7
12.6
18.2
24.4
36.3
48.5
59
HEAT LOSS (W)
45
50
65
85
110
140
200
315
340
450
510
(AT 2 KHz CARRIER FREQUENCY)
INPUT VOLTAGE/FREQUENCY
WEIGHT (Kg)
3 PHASE
380 TO 415V (+10%,-15%)
50/60 Hz (+5%,-5%)
10.6/6.5 10.6/11.5 10.6/11.5 10.6/12
0.95 0.94 0.95 0.96
0.2 - 400 Hz (‘P’ MODELS 0.2 - 120 Hz)
2.4
3.2
3.2
3.2
3.2
6.5
5.3/6.5
0.95
INPUT POWER FACTOR**
OUTPUT VOLTAGE FREQUENCY
0.96
0.95
0.94
0.93
0.94
0.95
3 PHASE
0 - V INPUT
JAGUAR VX ORDER CODES
JAGUAR VXP ORDER CODES
MOTOR RATING (kW)
VX30K VX37K
VX45K VX55K VX75K
VX90K VX110K VX132K VX160K VX200K VX220K
VX30KP VX37KP VX45KP VX55KP VX75KP VX90KP VX110KP VX132KP VX160KP VX200KP VX220KP VX280KP
30
60
58
37
75
71
45
91
85
55
75
90
110
210
203
132
253
243
160
304
293
200
377
363
220
415
400
280
520
508
RATED O/P CURRENT (A)
100% RATED I/P CURRENT RMS
(AT 400V)*
112
104
150
141
176
168
HEAT LOSS (W)
1200
1400
1600
1900
2300
2700
3000
3400
4000
4600
5000
6000
(AT 2 KHz CARRIER FREQUENCY)
INPUT VOLTAGE/FREQUENCY
WEIGHT (Kg)
3 PHASE
380 TO 415V (+10%,-15%)
50/60 Hz (+5%,-5%)
120/125 125/177
36
36/37
0.95
37/44
0.95
45/54
0.95
54/61
0.95
61/88
0.95
88
88/120
0.95
177
177
INPUT POWER FACTOR**
OUTPUT VOLTAGE FREQUENCY
0.95
0.95
0.95
0.95
0.95
0.95
3 PHASE
0 - V INPUT
0.2 - 400 Hz (‘P’ MODELS 0.2 - 120 Hz)
NOTES
*
FIGURES FOR INPUT ARE QUOTED WHEN USING A DC REACTOR FROM VX30K AND VX30KP UP, NO REACTOR < 30KW
**
AT 100% FULL LOAD CURRENT AND USING DC REACTOR
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Basic circuit configuration and terminals
WARNING! INVERTER MUST
BE EARTHED
Braking resistor (option)
RTS = Volt-free NC contact
for thermal protection.
for all inverters.
RTS
BU
DC Bus reactor
Terminal Markings for DC
Terminal Makings for DC
*
(Optional ≤22kW)
bus reactor and Braking
P(+)
GND
(PE)
DB
Resistor for Braking Unit
2
1
GND
(PE)
Braking unit (option).
0V
The marking of these
Applicable to VX1100, VX1500P, VX30K
and inverters larger than these.
terminals varies between
24V
different sizes of Jaguar VX
Link P1 to ( )
inverter. Please refer to
*
On-board braking IGBT and resistor applicable
only to VX40 to VX750 and VX750P to VX1100P.
Disconnect the internal resistor (R) before
connecting an external resistor.
P(+)
N(-)
if DC reactor
manual for specific details.
not required
P1
*
*
*
Input
contactor
R
L1
U
3-phase
power
supply
50Hz or
60Hz
V
L2
L3
M
W
Note (1)
GND
Power
(PE)
Current
detection
charge
LED
Connect via
(13) +10V DC
(12)
Z
(11)
0V
RF filter (if fitted)
Analog voltage
frequency ref.
input
SMPS
+24V DC
‘CRG’
Gate
drive
Voltage
detection
(Pot. 1kΩ, 1W)
Note (2)
A/D
Earth busbar
at MCC
DC voltage
detection
250Ω
(C1)
+ve
4-20mA
analog input
Keypad Panel
Programmable
analog
output
(FMA)
LED, LCD
displays
Keys
CPU
0 to 10V DC
(FMP)
(CM)
Pulse output
0V
Digital
output
Frequency
command
switch
PWM
generator
PRICE
(V1)
Note (3)
INFORMATION
AND ORDERING
Accel /
Decel
Auto-
voltage
regulator
(FWD)
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
4.7kΩ
regulator
(REV)
(THR)
(HLD)
(X1)
Torque
vector
calculator
Function
generator
BU
RTS
A/D
1
2
Protective
logic
CPU
Input
signal
Run
relay
output
(AX1)
(AX2)
Note (3)
(X2)
Control
inputs
(30C)
(30B)
(30A)
Trip
relay
output
(X3)
(X4)
(Y1E)
(Y2E)
(Y3E)
(Y4E)
(X5)
(BX)
Output
signal
Programmable
outputs
(RST)
0V
(Y5E)
(P24) or (CMS)
Note (6)
+24V DC
(CMC)
(P24) or (CMS) Note (6)
(CM)
Note (4)
0V
NOTES (1) For inverters rated ≤22kW the inrush contactor is replaced by an SCR. 0V Common Terminals (11) and
(2) Voltage detection circuit applicable for inverters ≥30kW only.
(3) Standard for inverters ≥30kW, optional for smaller models.
(4) Two terminals (CM) standard for inverters ≤22kW, one for ≥30kW.
(5) If motor thermistors are required, please consult IMO.
(CM) are optically isolated.
Relay status shown as at inverter
‘power ON’ or ‘healthy’.
(6) Internal +24V DC supply terminal designated P24 (≤22kW) or CMS (≥30kW).
Jaguar VX
Control circuit connections
Purpose
Terminal
Terminal Name
Speed reference 0V common
Potentiometer input
Description
11
12
For use with terminals 12, 13 and C1 (and V1, ≥30kW only)
Maximum speed demand is at +10V with a 0V to +10V DC
input. Input impedance 20kΩ (≤22kW), 22kΩ (≥30kW).
Analog
frequency
setting
13
Potentiometer supply
Current loop input
Regulated +10V DC power supply for 1kΩ min. speed control
potentiometer. Input 10mA max.
C1
Maximum speed demand is at 20mA with a 4-20mA DC
input, impedance 250Ω. Inverter output frequency is
proportional to current input signal, zero speed = 4mA.
V1*
CM†
FWD
Auxiliary freq. reference
0V common
Bipolar 0V to ±10V input.
0V common terminals for general use.
If FWD and
REV are both
closed or both
Forward and STOP command
FWD-P24 closed: Motor runs forward
open: Motor decelerates to rest
open, inverter
output STOPS.
REV
HLD
Reverse and STOP command
FWD/REV command hold
REV-P24 closed: Motor runs in reverse
open: Motor decelerates to rest
HLD-P24 closed: Latches momentary FWD or REV inputs
open: FWD/REV non-latching
BX
Coast-to-stop command
External Trip/Alarm input
BX-P24 closed: Inhibit inverter output instantaneously
open: Normal
THR
THR-P24 closed: Normal
open: Trip (OH2) inverter output instantaneously
Programmable
inputs
If RST-P24 closed for ≥100ms, inverter internal fault trips are
reset, and also alarm 30A/B/C (see below).
RST
Trip/Alarm RESET
X1
X2
X3
Programmable input 1
Programmable input 2
Programmable input 3
Preset speeds or motorised potentiometer
Preset speeds or mains-to-inverter changeover
Preset acc/dec command. LOC/REM changeover.
DC injection brake command.
X4
X5
Programmable input 4
Programmable input 5
Preset acc/dec times. 2nd motor V/F ratio. Data protection
enable/disable.
24V current source for programmable I/O terminals and for
FWD, REV, HLD, BX, THR, RST and X1 to X5.
P24
P24
+24V DC power supply
Analog meter
Output frequency, current, torque or load factor can be
selected. 0V to +10V DC at 2mA max. (Min. impedance 5kΩ)
FMA
FMP
Meter
outputs
Pulse output proportional to inverter output frequency. Pulse
frequency 6 to 100 x O/P Hz at +10V DC (adjustable).
Pulse frequency meter
Output:
Open-collector common
Programmable output 1
Programmable output 2
Programmable output 3
Programmable output 4
Programmable output 5
CMC
Y1E
Y2E
Y3E
Y4E
Y5E
0V
27V DC,
Up to 16 different outputs can be programmed
from the operating Functions representative of
dynamic operating conditions.
Factory defaults:
Y1E Inverter running
Y2E FAR
Y3E FDT
50mA per
O/P channel,
total 50mA
maximum.
Caution
Read Technical
Manual before
use.
Programmable
outputs
Y4E Overload early warning
Y5E Undervoltage
Relay changes state when an internal protection function is
active and when the inverter trips.
Contact: 250V AC, capacity 0.5A, cosφ 0.3
30A
30B
30C
Normally open
Normally closed
Common
Relay
outputs
Relay closes when inverter is running
Contact: 250V AC, capacity 0.5A, cosφ 0.3
AX1*
AX2*
Run relay
* Standard for ≥30kW only, optional for ≤22kW.
† Two CM terminals for ≤22kW, one for ≥30kW.
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Parameter list/function code table
Group No.
Name
LCD Display
Setting range
Unit Resol. Def.
Basic
Functions
00 Frequency command
00 FREQ COMND 0 = KEYPAD, or keys
1 = TERMINAL, 0 to +10V
—
—
0
2 = TERMINAL, 4 to 20mA
01 Operating mode
01 OPR METHOD 0 = KEYPAD, RUN/STOP keys
1 = TERMINAL, (FWD) & (REV)
—
—
0
02 Max. O/P frequency
03 Base freq., motor 1
04 Max. O/P V, motor 1
02 MAX Hz
VX, 50-400Hz VX…P, 50-120Hz
VX, 50-400Hz VX…P, 50-120Hz
Hz
Hz
V
1
1
1
50
50
03 BASE Hz -1
04 RATED V -1
0 = Output dependent on supply V*
320 to 480 = output V
400
05 Accel. time, motor 1
06 Decel. time, motor 1
05 ACC TIME 1
06 DEC TIME 1
0.01 to 3600
s
s
0.01 6.00
0.01 6.00
0.00 = ramp inhibit, or 0.01 to 3600
07 Torque boost, motor 1 07 TRQ BOOST 1 0.0 = auto; 0.1 to 20.0 fixed boost
—
0.1
0.0
[0.1]
08 Electronic thermal
08 ELECTRN OL 0 = Inactive
1 = Active for standard motor
—
—
1
O/L, type
2 = Active for inverter-rated motor
09 Electronic O/L, level
09 OL LEVEL
10 RESTART
20% to 105% of inverter rating
A
0.01
—
†
3
10 Restart after
momentary power
supply failure
0 = Inactive 1
1 = Inactive 2
2 = Active, smooth recovery
3 = Active, restart at set Hz
4 = Active, restart at start Hz
—
11 O/P freq. HI limit
12 O/P freq. LO limit
13 Min. O/P freq. (bias)
14 Freq. I/P ref. gain
15 Driving torque limit
11 H LIMITER
12 L LIMITER
13 FREQ BIAS
14 FREQ GAIN
VX, 0-400Hz VX…P, 0-120Hz
VX, 0-400Hz VX…P, 0-120Hz
VX, 0-400Hz VX…P, 0-120Hz
0.0 to 200.0%
Hz
Hz
Hz
%
1
1
1
70
0
0
0.1 100.0
15 DRV TORQUE 20 to 180, 999% (999 = no limit)
%
1
150
[120]
16 Braking torque limit
16 BRK TORQUE 0, 20 to 180, 999% (999 = no limit)
%
1
100
[100]
17 DC inj. brk. Start frequ. 17 DC BRK Hz
18 DC inj. brk. Brkg. level 18 DC BRK LVL
19 DC inj. brk. Brkg. time 19 DC BRK t
0.0 to 60.0Hz
Hz
%
s
0.1
0.1
0.1
0.0
0.0
0.0
0.0 to 100%
0.0 (brake inactive), or 0.1 to 30.0s
20 Pre-set multistep
to frequencies 1 to 7
26
20 MULTI Hz -1
to
26 MULTI Hz -7
VX
0.00, 0.20 to 400.0Hz
Hz
0.01 0.00
VX…P 0.00, 0.20 to 120.0Hz
(0.00 = preset disabled)
27 Intl. electronic thermal 27 DBR OL
O/L for intl. brkg. R
0 = Inactive
1 = Active for intl. R, invrs. ≤7.5kW
2 = Inactive
—
—
1 [0]
28 Slip compensation
28 SLIP COMP
-9.9Hz to +5.0Hz
Hz
—
0.1
—
2
0.0
0
29 Torque vector control
29 TRQ VECTOR 0 = Inactive 1 = Active
2 to 14 (even nos. only)
30 Number of motor poles 30 MTR POLES
4
Functions marked by heavy outlines can be set whilst the inverter is running. DEF = factory-set defaults. Resol = resolution.
Default values are for all inverters. Where VX…P defaults differ, they are shown in square brackets […].
* LCD display shows 0V
† Approx. rated current for inverter-rated motors
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Parameter list/function code table (continued)
Group No.
Name
LCD Display
Setting range
Unit Resol. Def.
31 Function Block 32 to 41
0 = Functions 32 to 41 hidden
1 = Functions 32 to 41 displayed
—
—
s
—
0
31 • 32—41 •
31
Prog. I/P
terminals
32 Select the functions of
terminals X1 to X5
0000 to 2222
—
0000
32 X1-X5 FUNC
3X ACC TIME X
Acc./Dec.
times
33 Accel time 2
34 Decel time 2
35 Accel time 3
36 Decel time 3
37 Accel time 4
38 Decel time 4
0.00 = Ramp inhibited, coasting
0.01 to 3600s
0.01 10.00
10.00
15.00
15.00
3.00
3.00
2nd
motor
39 Base freq., motor 2
40 Max. O/P V, motor 2
VX, 50-400Hz VX…P, 50-120Hz
Hz
V
1
1
50
39 BASE Hz -2
40 RATED V -2
0 = Output dependent on supply V*
320 to 480 = output V
400
41 Torque boost, motor 2
0.1 to 20.0 fixed boost
—
—
0.1
—
2.0
0
41 TRQ BOOST 2
42 Function Block 43 to 51
0 = Functions 43 to 51 hidden
1 = Functions 43 to 51 displayed
42 • 43—51 •
42
43 FMP terminal, pulse
rate multiplier
x6 to x100
—
1
x24
Digital
O/P
43 FMP PULSES
44 Voltage O/P adjustmt.
50% to 120%
65% to 200%
%
%
1
1
100%
100%
44 FMP V-ADJ
45 FMA V-ADJ
45 FMA terminal, voltage
adjustment
Analog
O/P
46 FMA terminal function
0 = O/P freq.
2 = O/P torque
1 = O/P current
3 = %FLT
—
—
Hz
—
—
0
46 FMA FUNC
47 Y1-Y5 FUNC
48 FAR HYSTR
47 Select the functions of
terminals Y1E to Y5E
00000 to FFFFF
01234
2.5
O/P term.
functions
48 FAR function (‘At
Speed’ window)
0.0 to 10.0Hz
0.1
49 FDT function (level)
50 FDT function (hyster.)
51 O/L alarm (level)
VX, 0-400Hz VX…P, 0-120Hz
Hz
Hz
A
1
50
1.0
†
49 FDT LEVEL
50 FDT HYSTR
51 OL WARNING
0.0 to 30.0Hz
0.1
Approx. 20 to 105% inverter rated
current
0.01
52 Function Block 53 to 59
0 = Functions 53 to 59 hidden
1 = Functions 53 to 59 displayed
—
—
0
52 • 53—59 •
52
53 Skip frequency 1
54 Skip frequency 2
55 Skip frequency 3
56 Skip hysteresis
57 Starting frequency
58 Holding time
VX, 0-400Hz VX…P, 0-120Hz
VX, 0-400Hz VX…P, 0-120Hz
VX, 0-400Hz VX…P, 0-120Hz
0 to 30Hz
Hz
Hz
Hz
Hz
Hz
s
1
1
0
0
53 JUMP Hz 1
54 JUMP Hz 2
55 JUMP Hz 3
56 JUMP HYSTR
57 START Hz
58 HOLDING t
59 FILTER
Frequency
control
1
0
1
3
0.2Hz to 60.0Hz
0.1
0.1
0.5
0.0
0.0 to 10.0s
59 Frequency I/P
reference filter
0.01 to 5.00s
s
0.01 0.05
Functions marked by heavy outlines can be set whilst the inverter is running. DEF = factory-set defaults. Resol = resolution.
Default values are for all inverters. Where VX…P defaults differ, they are shown in square brackets […].
* LCD display shows 0V
† Approx. rated current for inverter-rated motors
PRICE
INFORMATION
AND ORDERING
Jaguar VX
Parameter list/function code table (continued)
Group No.
Name
LCD Display
Setting range
Unit Resol. Def.
60 Function Block 61 to 79
0 = Functions 61 to 79 hidden
1 = Functions 61 to 79 displayed
—
—
—
—
—
—
s
—
—
—
0
0
0
60 • 61—79 •
60
LED &
LCD
displays
61 LEDs, function for
normal display
0 to 8
61 LED MNTR 1
62 LED MNTR 2
63 SPEED COEF
64 LCD MNTR
65 PATTERN
62 LEDs display at STOP
0 = Set point (flashing)
1 = Actual output value only
63 Coefficient for machine
speed and line speed
0.01 to 200.00 x Hz output
0.01 0.01
64 LCD display function
0 to 3: Drive status, standard screen
or bar graphs
—
—
0
0
Pattern
operations
65 Pattern operation,
mode select
0 to 3: Inactive or cyclic
66 Pattern stages 1 to 7
to
72
Operation time 0.00 to 6000s
FWD/REV codes F1 to F4
ACC/DEC codes R1 to R4
0.01 0.00
F1
6X STAGE X
73 ACC/DEC mode
0 to 2: linear, S-curve, non-linear
—
—
0
73 ACC PTN
74 Series brake motor
driving
Not available
—
74 SERIES BRK
Special
Functions
1
75 Energy saving
0 = Inactive 1 = Active
0 = Inactive 1 = Active
0 = Inactive 1 = Active
—
—
—
—
—
—
0 [1]
75 ENERGY SAV
76 REV LOCK
77 DATA INIT
76 REV phase sequ. lock
0
0
77 Data initialising (data
reset)
0 = GERMAN, 1 = ENGLISH
0 to 3
78 Language of displays
—
—
—
—
1
5
78 LANGUAGE
79 BRIGHTNESS
2 = SPANISH, 3 = ITALIAN
79 LCD display
brightness
0 (bright) to 10 (dark)
80 Function Block 81 to 94
0 = Functions 81 to 94 hidden
1 = Functions 81 to 94 displayed
—
—
—
—
0
80 • 81—94 •
80
Special
Functions
2
81 PWM carrier frequency
(motor sound)
0 (low) to 10 (high) carrier
frequency
10
81 MTR SOUND
82 Auto-restart, start delay
0.0 to 5.0s
s
0.1
1
0.1
10
82 RESTART 1
83 FALL RATE
83 Auto-restart, freq. fall
rate
0.00 to 100.00
Hz/s
84 Auto-reset, number of
restarts
0 to 7
—
—
0
84 AUTO RESET
85 Auto-reset, interval
86 Motor 1, frame size
2 to 20s
s
—
—
5
1
85 RESET INT
0 = 1 higher 1 = nominal
2 = 1 lower 3 = 2 lower
—
86 MOTOR CAP
Motor
characteristics
87 Motor 1, rated current
88 Motor 1, no-load current
89 Motor 2, rated current
90 Motor 1, tuning
0.00 to 2000A
A
A
0.1
0.1
†
†
†
0
†
†
87 MOTOR 1-Ir
88 MOTOR 1-Io
89 MOTOR 2-Ir
90 TUNING
0.00 to 2000A
0.00 to 2000A
A
0.1
0 = Inactive 1 = Active
0.00 to 50.00%
0.00 to 50.00%
—
%
%
—
91 Motor 1, %R1 value
92 Motor 1, %X value
0.01
0.01
91 %R1 SET
92 %X SET
Special
Functions
3
93
93 DD FUNC 1
94 DD FUNC 2
95 DATA PRTC
Manufacturer’s use
only
94
95
Data security
0 = Unlocked
1 = Data secure
—
—
0
Jaguar VX
Dimensions (mm) 0.4 to 280kW
Jaguar VX40
Jaguar VX550, VX750, and VX750P, VX1100P
130
195
110
96
220
196
37
6
97
7
12
10
KEYPAD OPERATION
KEYPAD OPERATION
Hz
r/min
Hz
r/min
%
A
m/min
%
A
m/min
V
V
PRG
RUN
PRG
RUN
260
238
FUNC
DATA
260
246
RESET
STOP
FUNC
DATA
RESET
STOP
10
162
10
6
87
7
Jaguar VX75 to VX400
Jaguar VX1100 to VX2200 and VX1500P to VX2200P
145
150
136
195
52
250
7
96
6
226
12
10
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
PRG
RUN
260
246
FUNC
DATA
RESET
STOP
PRG
RUN
400
378
FUNC
DATA
RESET
STOP
6
102
7
10
162
10
*N.B. JAGUAR VX inverters are designed
for use within shielded steel enclosures
78
68
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
125
REMOTE MOUNTING
STOP
KEYPAD WITH OPTIONAL
2M CONNECTOR CABLE
PRICE
115
PRG
RUN
INFORMATION
FUNC
DATA
RESET
STOP
AND ORDERING
Keypad panel
mounting dimensions.
Common to all modules.
Jaguar VX30K to VX220K, VX30KP to VX280KP
W
W1
D
V X
W
W 1
H
H 1
H 2
D
D 1
d
D1
-
30K D
340 240 550 530 500 290 185 10
340 240 550 530 500 290 185 10
375 275 550 530 500 290 185 10
375 275 675 655 625 275 170 10
530 430 675 645 610 290 185 15
530 430 740 710 675 300 180 15
2 holes
dmm diam.
-
-
37KP D
30KP D
CHARGE
-
-
45KP D
-
55KP D
-
75KP D
-
90KP D
37K D
KEYPAD OPERATION
Hz
r/min
%
A
m/min
V
-
45K D
Side vents on
inverters from
VX30K to VX75K
and VX30KP to
VX90KP only
H
PRG
RUN
-
55K D
FUNC
DATA
RESET
STOP
H1
-
75K D
H2
-
-
110KP D 530 430 740 710 675 330 205 15
90K D
-
-
132KP D 530 430 740 710 675 330 205 15
110K D
-
-
160KP D 530 430 1000 970 935 435 295 15
132K D
-
-
200KP D 530 430 1000 970 935 435 295 15
160K D
-
-
220KP D 680 580 1000 980 N/A 435 320 N/A
200K D
-
-
280KP D 680 580 1000 980 N/A 435 320 N/A
220K D
d
Jaguar VX
Optional accessories
Accessory
Filters
Function
A specially designed range of easily fitted low profile ‘footprint’ filters up to
22kW and stand alone filters up to 280kW are available to provide maximum
RF reduction. See page 363 for details.
Function Copy Unit
Saves and loads stored set-ups for up to 12 complete function sets. ‘Copy
Edit’, ‘verify’ and ‘write-protected’ modes available. Operates from an 85V to
265V AC supply. Target or donor drives do not need to be powered up to
transfer data.
Encoder Feedback Module
Enables Jaguar VX inverters to be operated in closed-loop control mode.
Speed control range 180 to 3600 rpm. Speed variation 0.2% at 3600 rpm.
Encoder output, 20 to 2000 pulses per revolution.
Relay Output Module
PID Control Mode Unit
Converts programmable outputs Y1E . . . Y5E to relay outputs.
Contact rating 0.3A at 250V AC, cosØ = 0.3.
Digitally adjustable P, I and D terms through the medium of a
supplementary function menu.
Reference input 0V to 10V DC
Feedback input 0V to 10V DC or 4-20mA DC.
Synchronisation Module
Serial Communication Module
FieldBus Modules
Provides a multi-synch tasking capability via rotary encoders for
Master/Slave and ‘Follower’ applications.
RS422 or RS485, multi-drop up to 31 Jaguar VX inverters of all sizes. Opto-
isolated.
Dedicated FieldBus units which allow the connection of multiple
Jaguar VX inverters to a site standard FieldBus link.
FieldBus systems available:
Modbus Plus
Interbus S
Profibus DP
DeviceNet
Regenerative Brake Units
Pod Extension Cable
Provides additional braking for high inertia loads for inverters 11kW to
280kW. (Units below 11kW have regenerative braking capability built in as
standard).
Allows the Jaguar VX keypad to be removed and mounted separately.
PRICE
INFORMATION
AND ORDERING