XP95-PD/-PDR,  
XP95-ID/-IDR  
Description  
Analog Addressable Duct  
Smoke Detectors  
The Gamewell-FCI analog addressable duct smoke detec-  
tors provide early detection of smoke and products with  
combustion present in air moving through an HVAC duct.  
Fans, blowers and complete systems may be shut down or  
activated in fire alarm mode by the Fire Alarm Control  
Panel (FACP) in the event of smoke detection.  
The Gamewell-FCI analog addressable duct smoke detec-  
tors may utilize either interchangeable photoelectric or ion-  
ization sensor heads. The external alarm indication is a  
light-emitting diode (LED), easily visible through the hous-  
ing. A manual reset switch is provided on the front of the  
sensor.  
XP95 Series  
Duct smoke detectors are also available with auxiliary relay  
contacts. The relay requires two additional wires for power  
and will activate when the sensor reaches alarm levels. All  
wiring must comply with local codes and regulations.  
Features  
Compatible with the Gamewell-FCI 600 Series analog  
addressable control panels  
Interchangeable “Plug-in” photoelectric or ionization  
heads  
XP95 Duct Smoke Detectors digitally transmit their address  
and the chamber’s analog value to the FACP for analysis.  
Address is stored in the sensor base  
Address is set by XPert addressing card  
Remote alarm LED option  
Two-wire supply- polarity insensitive  
Very low standby current  
LED alarm indication on sensor head  
Rugged steel backbox with clear plastic cover  
Large terminal connection screws  
No additional screens or filters to clean or replace  
Relay version available with optional remote test unit  
Three standard tube lengths available: 2.5, 5, or 10 ft.  
(0.762, 1.524, or 3.048 m)  
Air sampling is accomplished by two tubes which protrude  
into the duct. An exhaust tube of one standard length 7.5"  
(19.05 cm) is provided with the sensor housing. Intake sam-  
pling tubes, which must be ordered separately, are supplied  
in three standard lengths: 2.5, 5, or 10 feet  
(0.762, 1.524, or 3.048 m).  
Installation  
Duct mounting is accomplished by the use of a template  
and four sheet metal screws, provided. The duct detectors  
are compatible with the analog loops on Gamewell-FCI’s  
600 Series Analog Addressable Control Panels.  
Programming  
The only programming required for the XP95 Duct Smoke  
Sensors is address setting. This is accomplished through  
the use of the XPert addressing card which is inserted into  
the sensor base.  
An ISO 9000-2000 Company  
SIGNALING  
FM  
MEA  
Approved  
73-92-E  
APPROVED  
3242-1004:103 (photo)  
3242-1004:102 (ion)  
268A  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.  
©2007 by Honeywell International Inc. All rights reserved.  
www.gamewell-fci.com  
CS-2049 Rev. a1 page 1 of 2  
Programming (Continued)  
Specifications (Continued)  
When the sensor head is inserted into the base, the  
address is automatically relayed to the sensor. Changing  
the sensor does not require additional programming since  
the address remains on the XPert card located in the base.  
All other sensor-specific programming is accomplished at  
the FACP.  
Relay Versions Only:  
Relay Contacts:  
Two dry Form-C contacts  
Relay Contact Ratings:10 A @ 24 VDC resistive  
maximum  
Operating Voltage:  
Current:  
24 VDC  
Standby current:  
0.010 A @ 24 VDC  
Alarm current:  
0.055 A @ 24 VDC  
Engineer’s Specifications  
The contractor shall furnish and install, where indicated on  
the plans, analog addressable air duct smoke detectors.  
The sensors shall be listed by Underwriter’s Laboratories  
per UL 268A and UL-Listed as compatible with the Fire  
Alarm Control Panel (FACP). The sensors shall operate at  
air velocities from 300 to 4,000 feet (91.44 to 1219.20 m) per  
minute. The smoke sensor shall contain an integral LED  
that shall latch in when the unit goes into alarm, mounted at  
a 30° slant to provide a wide viewing angle.  
Ordering Information  
Model  
Description  
XP95-ID  
Two-wire air duct, ionization smoke detector  
24 VDC (RW-AAN)  
XP95-PD Two-wire air duct, photoelectric smoke  
detector 24 VDC (RW-AAP)  
30203-01 Remote LED alarm indicator (two VDCs);  
used with XP95-PD and XP95-ID  
XP95-IDR Four-wire air duct, ionization smoke detector  
24 VDC with relay (RW-ARN)  
A manual reset/test switch shall be located on the front of  
the device. The housing shall contain a sensor base which  
will accept photoelectric or ionization heads. All wiring must  
comply with local codes and regulations. The duct sensor  
housing shall have a metal chassis with a clear plastic  
cover and complete mechanical installation may be per-  
formed without removal of the cover. The duct smoke  
detector shall be the Gamewell-FCI model, XP95-ID(R) or  
XP95-PD(R) analog addressable duct smoke detector.  
XP95-PDR Four-wire air duct, photoelectric smoke  
detector 24 VDC with relay (RW-ARP)  
Remote LED alarm indicator (24 VDCs);  
used with relay versions  
30203  
30007-02 Remote test station with alarm LED;  
used with relay versions  
70896-02 Sampling tube, 2.5 feet (0.762 m)  
70896-05 Sampling tube, 5 feet (1.524 m)  
70896-10 Sampling tube, 10 feet (3.048 m)  
Specifications  
XP95-I  
XP95-P  
72247  
Ionization sensor head (replacement)  
Photoelectric sensor head (replacement)  
Duct detector enclosure (WP-1)  
(See Data Sheet CS-2308).  
Ambient Temperature: 32° F to 120°F (0°C to 49°C)  
Humidity:  
Material:  
10% to 85% R.H  
18 gauge steel backbox,  
clear plastic cover  
Dimensions:  
10.0" H x 8.25" W x 2.25" D  
(25.4 H x 21.0 W x 5.7 D cm)  
Maximum Net Weight: 4.0 lbs. (1.814 kg)  
Mounting: Template and necessary  
hardware supplied  
Radioactive Element: For Ionization versions only:  
Americium 241 (0.9 microcuries)  
Sensitivity:  
Factory set (ion); or adjustable  
via the IF600 control panel  
(photoelectric)  
Air Velocity:  
300 to 4,000 feet per minute.  
Pressure Differential: 0.01 to 1.2 inches (1.524 to 20.320  
meters per second) of water  
Standby Current:  
Photoelectric: 340 µA  
Ionization: 280 µA  
Photoelectric: 4 mA  
Ionization: 2 mA  
Alarm LED Current:  
Remote Alarm Output  
Range:  
20 mA maximum; diode gated  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
CS-2049 Rev. a1 page 2 of 2  
www.gamewell-fci.com  

相关型号:

72249-004H

Board Stacking Connector, 4 Contact(s), 2 Row(s), Male, Straight, Solder Terminal
AMPHENOL

72249-006HLF

Board Connector, LEAD FREE
AMPHENOL

72249-008H

Board Stacking Connector, 8 Contact(s), 2 Row(s), Male, Straight, Solder Terminal
AMPHENOL

72249-010H

Board Stacking Connector, 10 Contact(s), 2 Row(s), Male, Straight, Solder Terminal
AMPHENOL

72249-016HLF

Board Connector, LEAD FREE
AMPHENOL

72249-018H

Board Stacking Connector, 18 Contact(s), 2 Row(s), Male, Straight, Solder Terminal
AMPHENOL

72249-018HLF

Board Connector, LEAD FREE
AMPHENOL

72249-020H

Board Stacking Connector, 20 Contact(s), 2 Row(s), Male, Straight, Solder Terminal
AMPHENOL

72249-022HLF

Board Connector, LEAD FREE
AMPHENOL

72249-026HLF

Board Connector, LEAD FREE
AMPHENOL

72249-028H

Board Stacking Connector, 28 Contact(s), 2 Row(s), Male, Straight, Solder Terminal
AMPHENOL

72249-030HLF

Board Connector, LEAD FREE
AMPHENOL