ATD-HL2F [GAMEWELL-FCI]
Addressable thermal sensor, fixed; 寻址热传感器,固定![ATD-HL2F](http://pdffile.icpdf.com/pdf1/p00130/img/icpdf/ATD-H_720863_icpdf.jpg)
型号: | ATD-HL2F |
厂家: | ![]() |
描述: | Addressable thermal sensor, fixed |
文件: | 总2页 (文件大小:220K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Velociti® Series
ATD-L2F, ATD-RL2F
Description
Addressable Thermal Sensor
The Gamewell-FCI Velociti® Series, addressable plug-in
thermal sensors with integral communication provide fea-
tures that surpass conventional sensors. Point ID capabil-
ity allows each sensor’s address to be set, providing exact
locations for pinpointing alarm locations and for selective
maintenance. ATD thermal sensors use an innovative ther-
mistor sensing circuit to produce 135°F/57°C fixed-temper-
ature (ATD-L2F). The ATD-RL2F provides a combination
15°/minute rate-of-rise with 135° fixed thermal detection
that is included in a low-profile package. The ATD-HL2F
provides fixed high-temperature detection at 190°F/88°C.
These thermal sensors provide cost-effective, addressable
property protection in a variety of applications.
ATD-L2F
The Velociti® Series uses a communication protocol that
substantially increases the speed of communication
between the sensors and Gamewell-FCI analog address-
able fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group has a
status change, the panel’s microprocessor stops the group
poll and concentrates on the single device. The net effect
is response speed up to five times greater than earlier
designs.
Features
•
•
•
Sleek, low-profile design
Visual rotary switch addressing
Built-in functional test switch activated by an external
magnet
Installation
ATD plug-in sensors use a separate base to simplify instal-
lation, service, and maintenance. A special tool allows
maintenance personnel to plug-in and remove sensors
without using a ladder.
•
Bicolor LEDs flash green whenever the sensor is
addressed, and light steadily red on alarm*
Optional relay, isolator, or sounder bases
Low standby current
•
•
•
•
•
Mount the base on a box which is at least 1.5" (3.8 cm)
deep. Suitable mounting base boxes include:
Addressable communication
•
•
•
•
4.0" (10.2 cm) square box.
Stable communication technique with noise immunity
Optional remote, single-gang LED accessory
(RA-400Z)
3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.
Single-gang box (except relay or isolator base).
With B501BH or B501BHT base, use a 4.0" (10.2 cm)
square box.
•
Suitable for installation in ducts
•
With B224RB or B224BI base, use a 3.5" (8.9 cm)
octagonal box, or a 4.0" (10.2 cm) octagonal or square
box.
Note: *Only the red LED is operative in panels that do not operate
in Velociti® mode.
NOTE: Because of the inherent supervision provided by
the SLC, end-of-line resistors are not required. Wiring “T-
taps” or branches are permitted for Style 4 (Class “B”)
wiring.
An ISO 9000-2000 Company
SIGNALING
Velociti® and E3 Series® are registered trademarks of Honeywell
International Inc.
FM
MEA
UL® is a registered trademark of Underwriters Laboratories Inc.
APPROVED
Approved
S2332 3023594 219-02-E Vol.VI 07270-0694:256
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2008 by Honeywell International Inc. All rights reserved.
www.gamewell-fci.com
9020-0620 Rev. C3 page 1 of 2
Specifications
Specifications
Size:
2.1" (5.3 cm) high x 4.1" (10.4 cm)
diameter installed in B501 base,
6.1" (15.5 cm) diameter installed in
ADB-FLF base
Bases and Options
ADB-FLF
6.1” (15.5 cm) diameter standard base
B501
B501BH or
B501BHT
4.1” (10.4 cm) diameter flangeless base
Sounder base assembly (B501BHT
produces a Temporal Pattern) includes
B501 base
Shipping Weight:
Operating
4.8 oz. (137 g)
Temperature:
ATD-L2F or
ATD-RL2F
ATD-HL2
Sensor Spacing:
B224RB
Relay Base
Up to 14 AWG (2.0 mm2)
Relay type: Form-C
Rating:
2.0A @ 30 VDC resistive
0.3 A @ 110 VDC inductive
1.0 A @ 30 VDC inductive
–4° F to 100° F (–20° C to 38°C)
–4° F to 150°F (–20 C to 66°C)
UL® approved for 50 ft. (15.2 m)
center to center
FM approved for 25 x 25 ft.
(7.6 x 7.6 m) spacing
B224RB
Relay Base
Dimensions:
B224BI
Relative Humidity:
ATD-L2F
10 – 93% (non-condensing)
Fixed-temperature setpoint
135°F (57°C)
6.2”: (15.7 cm) x 1.2” (3.0 cm)
Isolator Base
Dimensions:
ATD-RL2F
ATD-HL2F
Combination 135° F fixed
temperature and 15° (8.3°c) per
minute rate-of-rise°
Fixed-temperature setpoint
190°F (88°C)
6.2” (15.7 cm) x 1.2” (3.0 cm)
Maximum 25 devices between isolator
bases
Remote alarm indicator, LED
Black detector covers (box of 10)
RA-400Z
BCK-200
Electrical Specifications
Ordering Information
Voltage Range:
15 - 32 volts DC peak
Model
Description
Standby Current: 200 mA @ 24 VDC
ATD-L2F
ATD-RL2F
Addressable thermal sensor, fixed, 135° F
Addressable thermal sensor, combination
fixed,135° F and 15°/minute rate-of-rise.
Addressable thermal sensor, fixed, 190° F
(without communication)
max. avg.)
.0003 A @ 24 VDC
ATD-HL2F
(one communication every 5 seconds
with LED enabled)
LED Current
(max.)
Voltage Range
.0065 A @ 24 VDC (LED lit)
15 –32 volts DC peak
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0620 Rev. C3 page 2 of 2
www.gamewell-fci.com
相关型号:
©2020 ICPDF网 联系我们和版权申明