NON-CODED, MANUAL
FIRE ALARM STATIONS
Model MS-2, MS-2H
FEATURES
The MS-2 manual fire alarm stations are
dual action devices. These stations re-
quire that the outer door be lifted to ex-
pose the actuation door which is then
pulled forward to operate the alarm toggle
switch. The actuation door is now locked
in the readily observable “alarm” position.
To reset the station, a key (common to
FCI control panels) must be inserted and
turned ¼ turn clockwise, opening the
station. Closing the station resets the
switch automatically.
• Single and Dual Action Versions
• Tumbler Lock for Test and Reset
Keyed Alike with FCI Control Panels
• Rugged Metal Construction
• Positive Indication of Operation
over 180° Viewing Angle
• Surface or Semi-flush Mounting
• Shock and Vibration Resistant
• Institutional Version (MS-2L)
• Optional “FIRE SUPPRESSION
SYSTEM RELEASE” Markings
(MS-2H)
MS-2
An optional breakglass rod is available
for positive indication of station operation.
Model MS-2L (Institutional)
• Optional DPST Switch (MS-2-D)
Operation of the Model MS-2L institu-
tional station requires that a special key
be used to release the actuation door
before it can be operated.
MS-2H
Model MS-2-D (Multiple Contact)
The MS-2-D features a DPST switch for
multiple signaling via wire lead connec-
tions.
MS-6
Model MS-6 (Single Action)
The MS-6 station is a single action de-
vice, requiring only the pulling of the ac-
tion door to release the compressed but-
ton switch. It is available either with ter-
minals (MS-6T) or wire leads (MS-6).
The station resets in the same
manner as the MS-2. The reset key is
common to FCI control panels.
An ISO 9001 Company
Specifications are provided for information only, are
not intended to be used for installation purposes and
are believed to be accurate. However, no responsi-
bility is assumed by Gamewell-FCI for their use.
Specifications subject to change without notice.
© 2006
All Rights Reserved.
9020-0358 Rev. I
Page 1of 2
MS SERIES
AGENCYAPPROVALS
UL (Std 38)
File S2465
FM (MS-2)
OJ3A9.AY/12880
1D4A7.AY
(MS-6, MS-6T)
C.S.F.M.
NYC-BS&A (MS-2)
NYC-MEA (MS-6)
7150-0694:107
960-81-SA
103-93-E
SPECIFICATIONS
Extruded 6063/T5 aluminium
Clear anodize
Material (MS-2, MS-6)
Doors (MS-2, MS-6)
Switch Type
MS-2
Enclosed toggle
Enclosed push button
Silver plated bronze or copper
MS-6
Contact Material
Contact Ratings
MS-2
6 amp. max. @ 30 VDC (resistive)
0.5 amp. max. @ 30 VDC (resistive)
MS-6
Dimensions (overall)
MS-2, MS-6
5” H x 3.4” W x 2.8” D (12.7 cm x 8.64 cm x 7.11 cm)
ORDERING INFORMATION
Part No.
1100-0615
1100-0634
Model
MS-2
MS-2H
Description
Dual action fire alarm station
Dual action station with
“FIRE SUPPRESSION SYSTEM RELEASE” markings
Institutional fire alarm station
Dual action station with DPST switch
Single action station, wire leads
Single action station, terminals
Surface back box for MS-2, MS-6 stations
1100-0621
1100-0617
1100-0632
1100-0633
2520-0023
1120-0206
MS-2L
MS-2-D
MS-6
MS-6T
BB-2
Package of two replacement breakglass rods for MS-2 station
Specifications are provided for information only, are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Gamewell-FCI, for their use. Specifications subject to change without notice.
© 2006 All Rights Reserved
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell.fci.com
9020-0358 Rev. I Page 2 of 2
相关型号:
©2020 ICPDF网 联系我们和版权申明