BB-XP [GAMEWELL-FCI]

Six-Relay Addressable Control Module; 六继电器可寻址控制模块
BB-XP
型号: BB-XP
厂家: GAMEWELL-FCI BY HONEYWELL    GAMEWELL-FCI BY HONEYWELL
描述:

Six-Relay Addressable Control Module
六继电器可寻址控制模块

继电器
文件: 总2页 (文件大小:298K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Features  
RCM-SS  
• Six addressable Form-C relay  
contacts.  
Six-Relay Addressable Control Module  
• Removable 12 AWG (3.25 mm²)  
to 18 AWG (0.9 mm²) plug-in  
terminal blocks.  
• Status indicators for each point.  
Description  
• Unused addresses may be  
disabled.  
Gamewell’s SmartScanTM RCM-SS  
six-relay control module provides  
an intelligent alarm system with six  
Form-C relays.  
• Rotary address switches.  
• Compatible with Gamewell’s  
602, 610, 632, 654 and 658  
FACPs with SmartScan™ SLC.  
The first module is addressed from  
01 to 94 while the remaining mod-  
ules are automatically assigned to  
the next five higher addresses. Pro-  
visions are included for disabling a  
maximum of three unused modules.  
A single isolated set of dry relay  
contacts is provided for each mod-  
ule address, which is capable of  
being wired for either a normally-  
open or normally-closed operation.  
The module allows the control panel  
to switch these contacts on com-  
mand. No supervision is provided for  
the controlled circuit.  
• Mount one or two modules in a  
BB-XP cabinet (optional).  
• Mount up to six modules on a  
CHS-6 chassis in a BB-25  
cabinet (optional).  
• Mounting hardware included.  
Listings  
Listings and approvals below  
apply to the RCM-SS Six-Relay  
Addressable Control Module. In  
some cases, the module may  
not be listed by certain approval  
agencies, or listing may be in  
process. Consult factory for  
latest listing status.  
Each RCM-SS module has panel-  
controlled green LED indicators. The panel can cause the LEDs to blink, latch  
on, or latch off.  
Product Line Information  
• UL Listed: file S521.  
RCM-SS: Six-relay control module.  
• CSFM approved:  
file 7300-1288:169.  
BB-XP: Optional cabinet for one or two modules. Dimensions, DOOR: 9.234"  
(23.454 cm) wide (9.484" [24.089 cm] including hinges), x 12.218" (31.0337 cm)  
high, x 0.672" (1.7068 cm) deep; BACKBOX: 9.0" (22.860 cm) wide (9.25"  
[23.495 cm] including hinges), x 12.0" (30.480 cm) high x 2.75" (6.985 cm); CHAS-  
SIS (installed): 7.150" (18.161 cm) wide overall x 7.312" (18.5725 cm) high inte-  
rior overall x 2.156" (5.4762 cm) deep overall.  
• MEA approved:  
file 368-01-E Vol. II.  
BB-25: Optional cabinet for up to six modules mounted on CHS-6 chassis (be-  
low). Dimensions, DOOR: 24.0" (60.96 cm) wide x 12.632" (32.0852 cm) high, x  
1.25" (3.175 cm) deep, hinged at bottom; BACKBOX: 24.0" (60.96 cm) wide x  
12.550" (31.877 cm) high x 5.218" (13.2537 cm) deep.  
CHS-6: Chassis, mounts up to six modules in a BB-25 cabinet.  
RCM-SS CS-2469 10/25/04  
Page 1 of 2  
Specifications  
Standby current  
Dimensions  
Current ratings  
• 3.0 A @ 30 VDC maximum, resistive,  
non-coded.  
• 2.0 A @ 30 VDC maximum, resistive,  
coded.  
• 1.0 A @ 30 VDC maximum, inductive  
(L/R = 2 ms), coded.  
• 0.5 A @ 30 VDC maximum, inductive  
(L/R = 5 ms), coded.  
• 0.9 A @ 110 VDC maximum, resistive,  
non-coded.  
• 0.9 A @ 125 VAC maximum, resistive,  
non-coded.  
• 0.7 A @ 70.7 VAC maximum, inductive  
(PF = 0.35), non-coded.  
1.45 mA (SLC current draw with all ad-  
dresses used; if some addresses are  
disabled, the standby current de-  
creases).  
6.8" (172.72 mm) high x 5.8" (147.32  
mm) wide x 1.0" (25.40 mm) deep.  
Shipping weight  
1.1 lb. (0.499 kg) including packaging.  
Mounting options  
Alarm current  
32 mA (assumes all six relays have been  
switched once and all six LEDs solid  
ON).  
CHS-6 chassis, BB-25 cabinet.  
Relay current  
30 mA/relay pulse (15.6 ms pulse dura-  
tion), pulse under panel control.  
Temperature range  
32°F to 120°F (0°C to 49°C).  
Humidity  
Relay contact ratings  
30 VDC; 70.7 VAC.  
10% to 85% noncondensing.  
• 0.5A@ 125 VAC maximum, inductive (PF  
= 0.35), non-coded.  
Wiring Diagram  
6926wir1.wmf  
Gamewell  
12 Clintonville Road  
Northford, CT 06472-1610  
Phone: 203-484-7161  
Fax: 203-484-7118  
Specifications and wiring information are provided for information only and are believed  
to be accurate. Gamewell assumes no responsibility for their use.  
Data and design are subject to change without notice. Installation and wiring  
instructions shipped with the product shall always be used for actual installation. For  
more information, contact Gamewell.  
www.gamewell.com  
A Honeywell Company  
© 2004 Gamewell  
Page 2 of 2  
RCM-SS  
CS-2469 10/25/04  

相关型号:

BB-XXXXDX

1 to 2 Watt Isolated DC-DC Converter Single / Dual Output
BOTHHAND

BB-XXXXSX

1 to 2 Watt Isolated DC-DC Converter Single / Dual Output
BOTHHAND

BB-ZP24D-250RM-SR

INDUSTRIAL GRADE RADIO MODEMS
ETC

BB-ZP9D-ANT1

NETWORKING ANTENNA RADIO MODEM
ETC

BB-ZP9D-DIN1

NETWORKNG CLIP ZLINX RADIO MODEM
ETC

BB-ZP9D115RMLR-A

INDUSTRIAL GRADE RADIO MODEMS
ETC

BB-ZXT24-RM

ZLINX 2.4GHZ WIRELESS RADIO MODM
ETC

BB-ZXT9-ANT

SPARE ANT 900MHZ RPSMA 3DBI
ETC

BB-ZXTMT

NETWORKING CONDUIT KIT XTREME
ETC

BB-ZZ-PROG1-USB

ZLINX PROGRAMMING MODULE
ETC

BB-ZZ-TB1

ZLINX IO SPARE TB KIT, DIP COVER
ETC

BB-ZZ24D-ANT1

NETWORKING ANTENNA IO ZLINX SPAR
ETC