FC-6324
SIX ZONE PANEL
CONVENTIONAL FIRE ALARM CONTROL
DESCRIPTION
The FC-6324 Fire Alarm Control panel is a proven, versa-
tile, six-zone control with space for an optional digital com-
municator. It meets the requirements of NFPA Standard 72
for Central Station, Protected Premises, and Remote
(DACT) Supervising Station Fire Alarm Systems. It is Listed
to UL Standard 864, inherently power limited and meets all
UL transient immunity requirements.
The many features of the FC-6324 control provide a cost
effective approach to systems design, and allow a great de-
gree of flexibility in one enclosure. These features include
six (6) Class B, Style B initiating circuits and three (3) Class
B, Style Y notification appliance circuits rated up to 2.5 amps
each with a system maximum of 2.5 amperes. Notification
appliance circuits can be configured as silenceable or
non-silenceable.
DIP switch programming is used throughout, eliminating
the need for computers and associated software.
A time delay of 30, 60, or 90 seconds is available for
waterflow switches.
FEATURES
· Inherently Power Limited
· DIP Switch Programming
The control is housed in a red steel enclosure with a win-
dow offering a view of LEDs displaying the status of vital
functions and allowing access to switches controlling system
operation. The surface mounted enclosure, with its slim ap-
pearance (3 3/8-inch depth) is designed to blend with any en-
vironment. Space is available for two (2) B-7R batteries.
Supervision of vital components, plug-in modules, func-
tional switches and standby batteries is provided.
The optional digital communicator includes a wide range
of selectable transmission formats to communicate to most
central stations. Other features of the communicator are: A
line-active indicator for each of two phone lines, “Kiss-Off”
signal LED, dual “low telephone voltage detect” circuitry,
and programmable event codes per format. The FC-6324
control is programmable for AC power loss delay required
for DACT operation.
· Choice of Output Patterns Including
ANSI S3.41
· Programmable Time Delay for
Waterflow Switches
· Periodic Trouble Reminder
· Walk Test Feature
· Optional Digital Communicator with
Multiple Reporting Formats
· Serial Annunciator Output
· Surface Mount Technology
A serial annunciator driver allows remote alarm annuncia-
tion to as many as four (4) Model FC-2866 remote annuncia-
tors.
Other optional modules include the FC-2880 I/O module
which provides 34 predefined open collector outputs that can
be used to drive LEDs or relays.
AGENCY APPROVALS
UL
S1869
CSFM
Approved
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control In-
struments, Inc. for their use. Specifications subject to change without notice. © 2000 All Rights Reserved
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
An ISO 9001 Certified Company
9020-0485/Ver. 1.6
FC-2880 Annunciator Driver Module
FC-2866 Remote Zone
Annunciator
FC-2104 Digital Alarm
Communicator Transmitter
CHARACTERISTICS AND DIMENSIONS
Supervisory current
Alarm current
Operating temperature
Relative humidity
Dimensions
.090 amp.
.295 amp.
32 - 120o F (0 - 49o C)
85% (non-condensing)
15 1/8”H x 12 13/16”W x 3 3/8” D
(38.4 cm x 33 cm x 8.5 cm)
ORDERING INFORMATION
Part Number
150-00003
Model
FC-6324
Description
Six Zone Control, 120 VAC operation
151-00003
151-00004
151-00005
151-00019
151-00017
151-00018
FC-2880
FC-2866
FC-2104
2190
5230
7860
Annunciator Driver Module
Remote Zone Annunciator, w/reset and silence switches
Digital Alarm Communicator Transmitter
Cabinet for FC-2104 DACT (optional)
Programmer for FC-2104 DACT
Cable w/spade lugs for connection
to Telco RJ31X plug. (Optional)
151-00020
151-00009
Quick connect cable to connect
5230 Programmer to FC-2104 DACT
FC-6324 PC
FC-7628
Replacement PC board
UL Listed EOL resistor
151-00011
151-00012
120 VAC Transformer (replacement)
230 VAC, 50 Hz Transformer (replacement)
FC-2104 DACT reporting formats are:
SIA 8 or 20
SK 3/1 1,400 or 2,300 Hz
Contact ID
SK 4/2
BFSK 1,400 or 2,300 Hz
9020-0485
2 of 2