Features  
SS-F  
• Analog intelligent communications.  
Filtrex™ Hostile-Area Smoke Head —  
Analog Addressable Detector with SmartScan™  
• High-performance filter removes  
particulates down to 32 microns  
(32-micron inner filter and replace-  
able outer filter).  
• Air delivery system is separately  
powered and fully supervised.  
Description  
• Outer filter is easily field replace-  
able.  
Gamewell’s SS-F SmartScan™  
smoke detector provides early  
warning smoke detection in  
hostile environments where tra-  
ditional smoke detectors are not  
practical. Using a small air in-  
take fan and a high-perfor-  
mance replaceable filter, air and  
smoke are drawn into a photo-  
electric sensing chamber, while  
unwanted airborne particulate  
and water mist are removed.  
This feature allows the SS-F to  
operate in difficult applications,  
such as textile or paper mills,  
which due to environmental  
conditions tend to cause nui-  
sance alarms with standard  
smoke detectors.  
Tolerant of external air velocity.  
• Resistant to water vapor in  
applications where occasional  
non-direct water spray is per-  
formed.  
• Optional remote LED annunciator.  
• Rotary DECADE address switches  
with settings 01-99.  
• Dual bi-color (red/green) LEDs  
flash green when Normal and are  
steady red in Alarm (systems with  
SmartScan™ only).  
• Compatible with the Gamewell  
602, 610, 632, 654 and 658  
FACPs.  
• Requires auxiliary 24 VDC from  
system or remote power supply.  
SS-F Operation Overview  
Normal Operation — A miniature fan is pulsed on and off under microprocessor con-  
trol to conserve power, yet provide good smoke response. The system uses two filters  
(one replaceable) that remove particulates while allowing smoke to pass.  
Listings  
Listings and approvals below  
apply to the SS-F Filtrex Hostile  
Area Smoke Head Analog Addres-  
sable Detector with SmartScan™.  
In some cases, the module may  
not be listed by certain approval  
agencies, or listing may be in  
process. Consult factory for latest  
listing status.  
Filter Supervision — Periodically, the filter system is tested for blockage using a  
special thermal airflow sensor. In reasonably clean environments, the filter is ex-  
pected to last at least as long as the smoke-entry test period required by NFPA 72. In  
very dirty environments, the filter may need replacement more frequently.  
Filter Trouble Reporting — If SS-F determines that filter blockage is imminent, a  
warning trouble is indicated to the panel, followed by a return to normal. 72 hours after  
this warning, the detector will disconnect, giving a continuous trouble signal.  
Operation overview diagram:  
• UL Listed: file S1195.  
• CSFM approved:  
file 7272-1288:166.  
• MEA approved:  
file 230-01-E Vol. III.  
6346cros.wmf  
SS-F CS-2473 09/01/06  
Page 1 of 2  
Product Line Information  
Specifications  
SS-F  
Hostile-environment smoke detector head.  
Size  
2.875" (7.303 cm) high, 3.375" (8.573  
cm) high in base; diameter 4.0" (10.16  
cm), 6.125" (15.558 cm) diameter in  
base.  
SS-BF  
RF-FTX  
RA400Z  
Flanged adapter base, 6.125" (15.558 cm) diameter.  
Replacement outer filter cover assembly, box of 6.  
Remote LED annunciator, 3 – 32 VDC, fits U.S. single-gang electrical  
box.  
Weight  
7.3 oz. (207 g).  
M02-04-01 Test magnet.  
M02-09-00 Test magnet with telescope stick.  
Current draw, SLC  
DETECTOR: 300 µA @ 24 VDC (one  
communication every 5 seconds with  
LED enabled).  
Wiring Diagram  
Current draw, auxiliary 24 VDC (15  
to 30 VDC filtered; ripple voltage may  
not drop below 15 volts): 123 mA  
maximum, 27 mA average. For  
battery calculation purposes,  
average standby current is 27 mA.  
Operating voltage range  
15 – 32 volts DC peak.  
Operating temperature range  
0°C to 49°C (32°F to 120°F).  
6903wir.tif  
Relative humidity  
10% – 93%, noncondensing.  
Air velocity  
4,000 ft/1219.2 meters per minute  
maximum.  
Maximum altitude  
4,000 feet (1219.2 meters).  
Detector spacing  
Gamewell recommends spacing  
detectors in compliance with NFPA 72.  
In low-air-flow applications with  
smooth ceilings, space detectors 30  
feet (9.114 m) apart. For specific  
information regarding sensor spacing,  
placement, and special applications,  
refer to NFPA 72 or the Guide to  
Proper Use of System Smoke Detec-  
tors, available from  
6346top.tif  
6346expl.tif  
The SS-F detector contains both a  
permanent filter and a replaceable  
filter, a supervised fan, and a photo-  
electric detector; to fit into a flanged  
adapter base.  
systemsensor.com.  
Gamewell-FCI  
12 Clintonville Road  
Northford, CT 06472-1610  
Phone: 203-484-7161  
Fax: 203-484-7118  
www.gamewell-fci.com  
Specifications and wiring information are provided for information only and are believed  
to be accurate. Gamewell-FCI assumes no responsibility for their use.  
Data and design are subject to change without notice. Installation and wiring instructions  
shipped with the product shall always be used for actual installation. For more  
information, contact Gamewell-FCI.  
AHoneywell Company  
© 2006 Gamewell-FCI  
Page 2 of 2  
SS-F  
CS-2473  
09/01/06  

相关型号:

M02006

CMOS Pre-amplifier with AGC for Long-reach 155 Mbps Fiber-optics Based Transmitter
TE

M02006E-DIE

CMOS Pre-amplifier with AGC for Long-reach 155 Mbps Fiber-optics Based Transmitter
TE

M02006F-DIE

CMOS Pre-amplifier with AGC for Long-reach 155 Mbps Fiber-optics Based Transmitter
TE

M02024-BRF-001-A

2.5 Gbps High Sensitivity Transimpedance Amplifier with AGC
TE

M02024-BRF-001-A_15

2.5 Gbps High Sensitivity Transimpedance Amplifier with AGC
TE

M02040-15

3.3 5V Limiting Amplifier for Applications to 2.125 Gbps
TE

M02040-15EVM

3.3 5V Limiting Amplifier for Applications to 2.125 Gbps
TE

M02044CG-31

3.3/5V Limiting Amplifier for Applications from 100 Mbps to 622 Mbps
TE

M02044CG-31EVM

3.3/5V Limiting Amplifier for Applications from 100 Mbps to 622 Mbps
TE

M02046-15

3.3 5V Limiting Amplifier for Applications from 100 Mbps to 1.25 Gbps
TE

M02046-15EVM

3.3 5V Limiting Amplifier for Applications from 100 Mbps to 1.25 Gbps
TE

M02046-25

3.3 5V Limiting Amplifier for Applications from 100 Mbps to 1.25 Gbps
TE