RAI-4 [GAMEWELL-FCI]

Duct Housing, 4-wire, less detector head; 管房, 4线,少探测头
RAI-4
型号: RAI-4
厂家: GAMEWELL-FCI BY HONEYWELL    GAMEWELL-FCI BY HONEYWELL
描述:

Duct Housing, 4-wire, less detector head
管房, 4线,少探测头

文件: 总2页 (文件大小:48K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
DH-60 SERIES  
FOUR-WIRE DUCT  
SMOKE DETECTOR HOUSING  
`
DESCRIPTION  
The FCI Model DH-60 Series air duct detector housing is  
intended for use on air handling ducts to sample air flow in  
the duct and allow for the detection of smoke and combus-  
tion particles. The housing is available in a 4-wire detector  
configuration, and accepts either the CPD-7051D ionization  
detector or the PSD-7155D photoelectric detector.  
Air sampling is accomplished via sampling and return  
tubes which extend into the ducts.  
The DH-60 4-wire detector can operate over a wide range  
of AC or DC power sources; 24 VAC, 24 VDC, 120 VAC or  
240 VAC. It is equipped with alarm relay auxiliary contacts  
which may be used directly for control applications, and has  
an integral, normally-energized trouble relay to supervise  
power and smoke detector head removal.  
Atransparent inspection port permits viewing of the detec-  
tor alarm indicator over a wide viewing angle and inspection  
of the conditions of cleanliness inside the detector mounting  
area.  
The housing can be installed on either rectangular or round  
ducts ranging from 8 inches to 12 feet in width. The sampling  
tube must extend over the entire width of the duct, and the  
unit is equipped with a 4.25 inch exhaust tube.  
Optional accessories include remote test stations and an-  
nunciators.  
FEATURES  
Accommodates Ionization  
or Photoelectric Detector Heads  
4-wire Configuration  
Field Selectable Single Station  
AC Operation: 24 VAC, 120 VAC  
or 240 VAC  
Air Velocity Ranging from  
500 to 4000 FPM  
CONSTRUCTION  
Mounts on Round or Rectangular  
Ducts from 8 inches to Twelve Feet  
Wide  
The duct detector housing is of rugged plastic with a clear  
polycarbonate cover. The housing is capable of mounting on  
either rectangular or round ducts without adapter brackets.  
Terminals are suitable for 14-18 AWG wiring.  
Clear Polycarbonate Cover for Visual  
Inspection  
Non-Polarized  
APPROVALS  
Remote Indication, Relay Test and  
UL (Std 268A)  
CSFM  
NYC MEA  
S1064  
Approved  
MEA 134-95-E Vol. III  
Reset Options  
Two (2) Heavy Duty (10 Amp.)  
Relay Contacts  
GENERAL SPECIFICATIONS  
Operating temperature  
Humidity  
32 to 100o F (0 to 37o C)  
10 to 93% RH  
Air velocity range  
Dimensions  
300 to 4000 FPM  
14.5 inches L x 5 inches W x 2.5 inches D  
(37 x 13 x 6.4 cm)  
Weight  
5.5 lbs. (3.2 kg)  
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed  
by Gamewell-FCI for their use. Specifications subject to change without notice. © 2006 All Rights Reserved.  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118  
www.gamewell-fci.com  
An ISO 9001 Certified Company  
9020-0369 Rev. H  
ELECTRICAL SPECIFICATIONS  
Contact ratings  
Alarm initiating contacts:  
Form A  
2A @ 30 VAC/VDC (resistive)  
Auxiliary alarm contacts:  
Form C (2 sets)  
10A @ 30 VDC (resistive)  
10A @ 277 VAC (resistive)  
1/8 HP @ 120 VAC  
1/4 HP @ 240 VAC  
Supervisory contacts:  
Form B  
0.3 A @ 30 VDC (resistive)  
0.3 A @ 30 VAC (resistive)  
Power requirements  
(Using no accessories)  
Max. standby current  
Max. alarm current  
20.4 - 26.4 VAC  
102-132 VAC  
204-264 VAC  
20-29VDC  
.070 A  
.160 A  
.030 A  
.040 A  
.020 A  
.025 A  
.020 A  
.060 A  
(Using max. accessories)  
Max. alarm current  
.220 A  
.050 A  
.035 A  
.090 A  
TESTING  
Using the RCM-505 or RCM-606 remote test  
unit - Insert the key and turn clockwise to the  
“TEST” position and hold until the LED lights.  
Reset: Turn the key counterclockwise to the  
“Reset” position and hold. The LED will extin-  
guish. Turn the key to the normal position and  
remove.  
Functional testing can be performed by one of the  
following methods:  
Hold a magnet in the slot marked “Test” on the  
housing until the LED lights. Confirm that the  
system control unit (if used) alarms properly  
and performs all auxiliary functions.  
Reset: Place a magnet in the slot marked  
“Reset”  
ORDERING INFORMATION  
Part No.  
Model  
Description  
Shipping  
Weight (lbs)  
5.5  
119-A0400  
110-38020  
112-30080  
DH-60  
Duct Housing, 4-wire, less detector head.  
Ionization Detector head  
CPD-7051D  
PSD-7155D  
2.0  
Photoelectric Detector head  
2.0  
138-02006  
138-02806  
RAI-4  
Remote Alarm Indicator red LED lights on alarm.  
Remote Alarm Indicator/Keyswitch as above except  
with added remote test and reset keyswitch  
Remote Power/Alarm Indicator/Keyswitch -  
as above except has added green “POWER” LED  
which is lit during normal conditions.  
1.0  
1.0  
RCM-505  
138-02906  
RCM-606  
1.0  
252-8GJ2B  
252-8GK2B  
252-8GL2B  
252-8GM2B  
252-8GN2B  
252-8GP2B  
FST-2  
FST-3  
FST-4  
FST-6  
FST-8  
FST-10  
12-inch Sampling Tube (For ducts less than 1 ft.)  
0.6  
1.0  
1.2  
2.0  
3.0  
3.5  
24-inch Sampling Tube (For ducts between 1 and 2 ft.)  
48-inch Sampling Tube (For ducts between 3 and 4 ft.)  
72-inch Sampling Tube (For ducts between 4 and 6 ft.)  
96-inch Sampling Tube (For ducts between 6 and 8 ft.)  
120-inch Sampling Tube (For ducts between 8 and 10 ft.)  
2 of 2  
9020-0369 Rev. H  

相关型号:

RAI00180670-DE

Born to drive machines
OMRON

RAI00350335-DE

Born to drive machines
OMRON

RAI00740335-DE

Born to drive machines
OMRON

RAI00880200-DE

Born to drive machines
OMRON

RAILCLAMP?

RailClamp? TVS Diodes for High-Speed Interfaces (86k)
ETC

RAJ20660AGNP

Integrated Driver - MOS FET (DrMOS)
RENESAS

RAJ2810024H12HPD

Intelligent Power Device for automotive Application with Highly accurate current detection function
RENESAS

RAK01K62.64KOHM+/-0.01%

RESISTOR, WIRE WOUND, 0.125W, 0.01%, 10ppm, 2640ohm, THROUGH HOLE MOUNT, AXIAL LEADED
VISHAY

RAK01K62.64KOHM0.01%

RESISTOR, WIRE WOUND, 0.125W, 0.01%, 10ppm, 2640ohm, THROUGH HOLE MOUNT, AXIAL LEADED
VISHAY

RAK01K626.4KOHM+/-0.01%

RESISTOR, WIRE WOUND, 0.125W, 0.01%, 10ppm, 26400ohm, THROUGH HOLE MOUNT, AXIAL LEADED
VISHAY

RAK1K626.4KOHM+/-0.1%

RESISTOR, WIRE WOUND, 0.125W, 0.1%, 10ppm, 26400ohm, THROUGH HOLE MOUNT, AXIAL LEADED
VISHAY

RAK1K626.4KOHM0.1%

RESISTOR, WIRE WOUND, 0.125W, 0.1%, 10ppm, 26400ohm, THROUGH HOLE MOUNT, AXIAL LEADED
VISHAY