SLP-RB [GAMEWELL-FCI]

Small Addressable Fire Alarm Control Panel;
SLP-RB
型号: SLP-RB
厂家: GAMEWELL-FCI BY HONEYWELL    GAMEWELL-FCI BY HONEYWELL
描述:

Small Addressable Fire Alarm Control Panel

文件: 总4页 (文件大小:142K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
S3 Series  
Control Panel  
Description  
Small Addressable  
Fire Alarm Control Panel  
The Gamewell-FCI, S3 Series Intelligent Fire Alarm Control  
Panel provides the latest innovative high-end processing  
power. The S3 Series is a digital, microprocessor-based  
system that offers a simple, intuitive solution for the small  
to mid-sized fire alarm applications.  
In standalone or network configurations, the S3 Series  
complies with most fire alarm application requirements. It  
supports either of the following types of networks.  
Up to 64 nodes using the 7100 Series panel.  
Up to 122 nodes using the S3 Series or E3 Series®  
panels.  
Use either twisted-pair wire or fiber-optic to network panels  
at a high-speed 625K baud ARCNET network bus.  
With flexible Boolean logic, intelligent detection, and Ether-  
net connectivity, this system provides power and versatility  
that surpasses comparable, small addressable fire alarm  
systems.  
S3 Series  
Features  
The basic S3 Series consists of an SLP (Smart Loop  
Panel) main board, LCD-SLP touchscreen display, SLC  
loop personality modules, and 7 amp power supply. The  
SLP provides either one or two SLC loops in Class A or B  
configuration that supports either of the following protocols:  
Listed per ANSI/UL® Standard 864 9th Edition.  
IBC Seismic Certified.  
Allows one SLC loop (expandable to two loops) that  
supports either System Sensor or Apollo devices in  
Class A or Class B (Style 4, 6 or 7).  
System Sensor supports up to 318 intelligent  
devices and each SLC loop supports the following.  
- up to 159 detectors.  
Up to 318 devices per loop using the System Sensor®  
protocol. If you add a second loop module, it increases  
the maximum device count to 636 devices.  
- up to 159 modules (expandable to 636 maximum  
per panel).  
Up to 126 devices per loop using the Apollo protocol. If  
you add a second loop module, it increases the maxi-  
mum device count to 252 devices.  
Apollo supports up to 126 intelligent detectors and  
modules per SLC. (Expandable to 252 maximum per  
panel).  
Four Class B or two Class A NACs can be wired and syn-  
chronized using the System Sensor, Cooper-Wheelock, or  
Gentex strobes. To retrofit the SLP on the existing audible/  
visual appliances, the on-board Electronic EOL (EEOL)  
automatically adjusts to the EOL resistor in the field.  
Includes a high resolution (4.3”) (10.92 cm) color touch-  
screen display.  
Supports a network system of up to 122 nodes  
(includes E3 Series® panels) or up to 64 nodes  
(includes 7100 Series).  
Provides 7.0 amp power supply (120VAC or 240VAC).  
Includes four Class B or two Class A built-in Notification  
Appliance Circuits (NAC). Provides selectable System  
Sensor, Cooper-Wheelock, or Gentex strobe synchroni-  
zation.  
Supports up to 32 serial annunciators (LCD, LED-only,  
LED Switch).  
A 4.3" (10.92 cm) color touchscreen display screen shows  
the following:  
Events on the system  
Status of analog addressable devices  
Complete diagnostic fault codes/messages  
Five programmable function buttons with LED status for  
accessibility to the following functions:  
- Disable/Enable  
- Bypass Output  
- Lamp Test  
- Trouble Acknowledge  
- Alarm Acknowledge  
- Custom-defined  
SIGNALING  
City of  
Chicago  
Approved  
7165-1703:0176 Class 1  
MEA  
S1869 APPROVED COA-#6162  
FM  
®
®
®
E3 Series , System Sensor and FocalPoint are registered trademarks of Honeywell  
International Inc.  
FDNY:  
Reference Certificate  
of Compliance  
VMA-45894-02C  
®
UL is a registered trademark of Underwriters Laboratories Inc.  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.  
©2016 by Honeywell International Inc. All rights reserved.  
www.gamewell-fci.com  
9021-60730 Rev. G page 1 of 4  
Features (Continued)  
Application  
The S3 Series Fire Alarm and Life Safety System is an  
easy-to-use intelligent fire alarm solution designed for the  
small to mid-sized buildings. Analog technology delivers  
the benefits of a simple system installation, while a user-  
friendly interface makes panel operation and system main-  
tenance quick and intuitive.  
Offers an Ethernet port for programming, a variety of  
system reports, and a FocalPoint® Graphic Workstation  
connectivity.  
Provides two fully-programmable Form-C contacts for  
Fire, Trouble, and Supervisory.  
TimeCap - Saves time and date up to 48 hours without  
any power or battery.  
Automatically adjusts to any NAC End-of-Line Resistor  
(EOL) value (1k-55k ohm) for legacy audible/visual  
appliances.  
Smart Panel Programming  
Using Boolean logic programming, the installer may cus-  
tomize the system to precisely suit the needs of the build-  
ing owner. Auto-programming allows the installer to  
instantly locate all the devices on the SLC loop.  
Removable display can be used as a remote annunciator.  
Suitable for pre-action deluge applications.  
Simple, Intuitive Display  
Optional Accessories  
DACT-E3 - Dialer  
The Digital Alarm Communication Transmitter sends digital  
signals over telephone lines to the central station. It con-  
nects to the SLP through an RS-485 bus. Using the Con-  
tact ID format, the DACT-E3 provides a four-digit account  
code followed by the code/numbers listed below:  
The front panel display provides a user-friendly interface  
for the operator's control. A 4.3” (10.922 cm) color touch-  
screen displays system status, event details and service  
modes. On the front of the panel, six LEDs show the follow-  
ing conditions.  
Fire  
Silenced  
AC Power  
Trouble  
Hazard (Gas or CO)  
Supervisory  
Three-digit Event Code  
Two-digit Group Number  
Three-digit Contact Number  
Five custom programmable switches allow the user quick  
access to common functions specific to the building like  
device disable, output bypass and device status.  
All codes are used to provide specific point identification.  
The DACT-E3 is compatible with digital alarm communica-  
tor receivers (DACRs) that receive the following signaling  
formats:  
Perfect for Retrofits  
The S3 Series is well-suited for retrofit applications. The  
SLP provides a simple way to upgrade your fire protection  
system. It is designed to be an upgrade solution for the leg-  
acy FCI 7100 and Gamewell 602 Series panels. An added  
feature is the SLP's EEOL. Using EEOL, the installers can  
automatically identify the EOL for existing audible/visual  
appliances.  
Contact ID  
3+1  
SIA  
4+2  
For more information, refer to the following data sheets:  
DACT-E3 Data Sheet, P/N: 9020-0610  
FML-E3/FSL-E3 Data Sheet, P/N: 9021-60783  
Flexibility for Future Growth  
RPT-E3-UTP - Network Repeater Card  
The S3 Series can be expanded to add a second SLC loop  
without replacing the entire system. Using the RPT-E3-  
UTP Network Repeater, you can network up to 64 nodes  
(122 nodes with the ANX node expander) using either  
twisted-pair or fiber-optic. The built-in Ethernet port allows  
the connection to the Gamewell-FCI’s FocalPoint  
Graphical Workstation.  
The Network Repeater allows the SLP fire control panels to  
connect to the broadband network from remote locations. It  
connects to other networked units using unshielded,  
twisted-pair wiring. The RPT-E3-UTP is available with two  
add-on fiber modules:  
FML-E3 connects to the network using either 62.5/125  
micron multi-mode fiber.  
FSL-E3 connects to the network using 9/125 micron  
single-mode fiber.  
Refer to the RPT-E3-UTP Data Sheet, P/N: 9020-0609.  
LCD-7100 - Remote Annunciator  
The Remote serial display features an 80-character dis-  
play. The LCD-7100 can be surface or flush-mounted on a  
standard 4-gang electrical box. You can use up to five  
LCD-7100 remote annunciators per SLP panel. For more  
information, refer to the LCD-7100 Data Sheet, P/N: 9020-0486.  
ASM-16 - Addressable Switch/LED Module  
There are 16 programmable switches available to perform  
any function the application requires. Each ASM-16 switch  
has 3 LEDs fully programmable in red, yellow, and green.  
These LEDs can be programmed to operate with a certain  
button press or operate independently as a status signal  
(e.g. ON, OFF, Activated, etc).  
Figure 1 LCD-SLP Display  
Up to 16 ASM-16 modules can be connected to the SLP  
panel. For more information, refer to the ASM-16 Data  
Sheet, P/N: 9020-0554.  
ANU-48 - 48 LED Driver Unit  
The ANU-48 provides output for eight remote panel  
switches and 48 remote LEDs for use in a remotely located  
UL® Listed annunciator enclosure. Up to 16 ANU-48 mod-  
ules can be connected to the SLP panel. For more infor-  
mation, refer to the ANU-48 Data Sheet, P/N: 9020-0596.  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
9021-60730 Rev. G page 2 of 4  
www.gamewell-fci.com  
Figure 2 illustrates the SLP-BB Cabinet Enclosure.  
Specifications  
Device Loops  
Up to two Class A or B, System Sensor  
units, each loop supporting up to 318  
device addresses.  
SLP-BB CABINET  
BACKBOX  
Or-  
Apollo units, each loop supporting up  
to 126 device addresses per loop.  
4 Class B or 2 Class A  
(2.0 A each circuit), 6.0 A total  
SLP-BB CABINET  
OUTER DOOR  
4
NAC circuits  
NAC Operating Voltage 24 VDC  
NAC Minimum Voltage 19.5 VDC @ 20.4 V battery voltage  
SLC Loop Circuit  
3
Operating Voltage  
Input Voltage  
24 V peak-to-peak  
120 VAC, 60 Hz 240 VAC 50-60 Hz  
Input Current  
120 VAC, 2.75 amps max.  
240 VAC, 1.4 amps max.  
2
1
Aux Power (Resettable) Two Auxiliary circuits, 24 VDC, 1.75 A  
20 1/8"H  
Supervised, Class 2 Power-Limited  
(maximum current of 1.75 is shared  
between two circuits).  
Aux Power  
(Non-Resettable)  
Base Panel Current draw Standby: 0.111 amps  
Alarm: 0.243 amps  
Operating Temperature 32°-120° F (0°-49° C)  
Relative Humidity  
93% (non-condensing)  
Battery Charger Voltage +24 VDC  
Battery Charger  
Capacity  
Alarm, Trouble & Supervisory  
Relay Contacts  
55 A/H batteries (cabinet  
accommodates 12 A/H batteries)  
4 1/2" D  
Form-C, 2 amps @ 24VDC (resistive)  
Cabinet Dimensions:  
SLP-BB Dimensions  
14 1/2” W x 20 1/8” H x 4 1/2” D  
(36.83 W x 51.18 H x 11.43 D cm)  
19 3/8” W x 19 3/8” H x 4.5” D  
(49.22 W x 49.22 H x 11.43 D)  
S3BB-RB Dimensions  
Figure 2 SLP Enclosure  
Supports up to 636 Velociti devices  
or 252 XP95 devices  
S3 Series  
Fire Alarm Control  
Panel  
DNR  
Networkable up to 122  
panels using twisted  
pair wire or fiber optics.  
MCS-COF  
Intelligent Duct  
Fire/Carbon Monoxide  
Detector  
Detector  
ASD-PL2F  
ASD-LS  
Photo Detector  
Laser Detector  
AMM-2IF  
AMM-2RIF  
Mini Monitor Module  
Dual Input/Output Module  
Local Energy  
E3 Series  
Panel  
Trip  
Ethernet  
AOM-2RF  
MS-7AF  
Relay Module  
Pull Station  
LCD-SLP  
LCD-7100  
LCD-E3  
Color Touchscreen  
Annunicator  
emote Annunicator  
Remote Annunicator  
FocalPoint  
Workstation  
ASM-16  
ANU-48  
LED Display Driver  
Laptop  
Programming  
LED Switch Control  
Figure 3 SLP Panel Configuration  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
www.gamewell-fci.com  
9021-60730 Rev. G page 3 of 4  
Ordering Information (Continued)  
Ordering Information  
Part Number  
Accessories  
DACT-E3  
Description  
Part Number Description  
SLP-BLK  
SLP-RED  
SLP-RED-G  
SLP addressable FACP in black SLP-BB  
enclosure.  
Requires either an SLC-PM or an  
SLC95-PM for SLC loops.  
SLP addressable FACP with red door  
and black SLP-BB backbox.  
Requires either an SLC-PM or an  
SLC95-PM for SLC loops.  
SLP addressable FACP  
Digital Dialer Communicator  
Transmitter for the S3 or E3 Series.  
LCD-SLP  
LCD Color Touchscreen display with  
five programmable switches.  
For use with the S3 Series panels.  
Remote annunciation requires the E3  
Series A2 cabinet.  
(E3BB-BA2, E3BB-RA2)  
RPT-E3-UTP  
Network repeater card with twisted-  
pair fiber connections require either an  
FML-E3 or an FSL-E3 card.  
Multi-mode fiber-optic card for one  
channel on the RPT-E3-UTP.  
Single-mode fiber-optic card for one  
channel on the RPT-E3-UTP.  
SLP motherboard  
For use with the replacement or the  
retrofit solutions.  
240VAC power supply with red door and  
black SLP-BB backbox.  
Requires either an SLC-PM or an  
SLC95-PM for SLC loops.  
FML-E3  
FSL-E3  
SLP-RB  
SLC-PM  
System Sensor Loop Card - 1 loop used  
for 159 sensors and 159 modules.  
For use with the SLP-E3 panels only.  
Apollo Loop Card-1 loop used for 126  
sensors and modules.  
SLC95-PM  
For use with the SLP-E3 panels only.  
FLPS-7-RB  
SLP 120VAC 7A power supply.  
For use with the replacement or the  
retrofit solutions.  
SLP-RETROFIT SLP Retrofit Kit for the 7100 B-Slim  
and IF602 panels.  
Includes the new door and the mount-  
ing plate. Requires the following:  
SLP-RB  
SLC-PM/  
SLC95-PM  
LCD-SLP  
FLPS-7-RB  
S3BB-RB  
SLP red cabinet with an inner door for  
the mounting display behind the  
plexiglass. Requires the following:  
SLP-RB  
SLC-PM/  
SLC95-PM  
LCD-SLP  
FLPS-7-RB  
LCD-7100  
ASM-16  
Remote Serial LCD Annunciator  
Remote Programmable Addressable  
Switch/LED Module  
ANU-48  
Remote LED Driver Module  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
9021-60730 Rev. G page 4 of 4  
www.gamewell-fci.com  

相关型号:

SLP-RED

Small Addressable Fire Alarm Control Panel
GAMEWELL-FCI

SLP-RED-G

Small Addressable Fire Alarm Control Panel
GAMEWELL-FCI

SLP-RETROFIT

Small Addressable Fire Alarm Control Panel
GAMEWELL-FCI

SLP.M13.GLLB

CONN RCPT FMALE 13POS SOLDER CUP
ETC

SLP004D

Low pressure sensors
SENSORTECHNIC

SLP004DD4

Low pressure sensors
SENSORTECHNIC

SLP010D

Peizoresistive Sensor, Gage, 0.361Psi Min, 0.361Psi Max, Through Hole Mount
HONEYWELL

SLP010DD4

Peizoresistive Sensor, Differential, 0Psi Min, 0.36Psi Max, 0-45mV, Rectangular, Through Hole Mount, DIP-6
HONEYWELL

SLP035A51

GENERAL PURPOSE VISIBLE DOME-STYLE LED,BLUE,CLEAR,LED-2D
ONSEMI

SLP036A51

GENERAL PURPOSE VISIBLE DOME-STYLE LED,BLUE,CLEAR,LED-2D
ONSEMI

SLP100-177-01

Material Rivet Nylon 6/6, Mandrel Polycarbonate
ETC

SLP100-221-01

Material Rivet Nylon 6/6, Mandrel Polycarbonate
ETC