ST-3 [GAMEWELL-FCI]

Intelligent Low-Flow Photoelectric Duct Smoke Detectors; 智能低流量型光电管烟雾探测器
ST-3
型号: ST-3
厂家: GAMEWELL-FCI BY HONEYWELL    GAMEWELL-FCI BY HONEYWELL
描述:

Intelligent Low-Flow Photoelectric Duct Smoke Detectors
智能低流量型光电管烟雾探测器

光电
文件: 总4页 (文件大小:225K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
SS-PD and SS-PDR  
Intelligent Low-Flow Photoelectric  
Duct Smoke Detectors  
Features  
• Air velocity rating from 100 to  
4,000 feet per minute (0.5 to  
20.32 m/sec.).  
• Patented telescopic sampling  
tube.  
SS-PD  
• Easily accessible code wheels  
for addressing detector.  
Description  
The Gamewell SS-PD and SS-PDR  
• Outside mounting tabs.  
Intelligent Low-Flow Photoelectric  
Smoke Duct Detectors provide low-  
flow technology that enables duct  
smoke detection throughout a broad  
range of airflow environments in HVAC  
applications. The low-flow technology  
can detect smoke at air speed veloci-  
ties of 100 feet per minute (0.5 m/sec.)  
or greater, while continuing the same  
reliable performance to 4,000 feet per  
minute (20.32 m/sec.). The intelligent  
low-flow duct detectors sample air cur-  
rents passing through a duct and gives  
dependable performance for shutdown  
• Mounts to round or rectangular  
ducts from 1’ to 12’ (0.3 to 3.7  
meters) wide.  
• Transparent cover for conve-  
nient visual inspection.  
SS-PDR  
Listings  
Listings and approvals below  
apply to the SS-PD and SS-  
PDR Intelligent Low-Flow  
Photoelectric Duct Smoke  
Detectors. In some cases,  
certain modules may not be  
listed by certain approval  
agencies, or listing may be in  
process. Consult factory for  
of fans, blowers, and air conditioning systems, preventing the spread of toxic smoke  
an fire gases through the protected area.  
The SS-PD and SS-PDR provide a remote alarm output for use with auxiliary  
devices such as the RA400 remote LED annunciator, as well as remote test capa-  
bility with the RTS451 or RTS451KEY Remote Test Stations.  
The SS-PD is a photoelectric duct detector with SmartScanTM protocol. The SS-  
latest listing status.  
PDR additionally incorporates a relay.  
• UL Listed: file S1115.  
Applications  
• CSFM approved:  
file 3240-1288:167.  
Duct smoke detectors have specific limitations, they are:  
NOT a substitute for open area smoke detectors.  
NOT a substitute for early warning detection.  
• MEA approved: file 384-02-E  
Vol. III.  
NOT a replacement for a building’s regular fire detection system.  
Please call Gamewell for a copy of System Sensor’s application guide, Proper Use  
of Smoke Detectors in Duct Applications, (A05-1004-00).  
Installation  
Wiring: For signal wiring (the wiring between detectors or from detectors to auxil-  
iary devices), it is recommended that single conductor wire be no smaller than 18  
AWG (0.75 mm²). The duct smoke detector terminals accommodate wire sizes up  
to 12 AWG (3.25 mm²). Flexible conduit is recommended for the last foot (30.48  
cm) of conduit; solid conduit connections may be used if desired.  
Smoke detectors and alarm system control panels have specifications for Signal-  
ing Line Circuit (SLC) wiring. Consult the control panel specifications for wiring  
requirements before wiring the detector loop. The SS-PD and SS-PDR detectors  
are designed for ease of wiring; their housing provides a terminal strip with clamp-  
ing plates.  
LED Features: If programmed with the system control panel, two LEDs on each  
duct smoke detector light to provide local visible indication.  
Page 1 of 4  
SS-PD and SS-PDR CS-2463 10/21/04  
Programming  
SS-PD: Current Requirements (using no accessories)  
Specifications  
specifications  
requirements for  
intelligent system  
control panels:  
The number of devices that can  
have their LEDs programmed to  
illuminate is limited by the fea-  
tures of the panel and the indi-  
vidual devices. The actual num-  
ber of devices is determined by  
the control panel and its  
ability to supply LED cur-  
rent. Refer to the control  
panel installation manual  
for details.  
Power  
24VAC, 120VAC, 220/240 VAC,  
Supply  
Voltage  
Max.  
Standby  
Current  
Max Alarm  
Current  
Alarm  
30-30VDC  
50/60 Hz 50/60 Hz  
50/60 Hz  
25 mA RMS  
30 mA RMS  
3 to 17 Sec.  
2 Sec.  
SS-PD  
Operating voltage range  
15 to 32 VDC.  
Standby current  
65 mA  
RMS  
44 mA  
RMS  
26 Ma  
87 mA  
182 mA  
RMS  
52 mA  
RMS  
300 µA @ 24 VDC (one communi-  
cation every 5 seconds with LED  
blink enabled).  
Operating temperature range  
32° to 131°F (0° to 55°C).  
Relative Humidity range  
10% to 93% (non-condensing).  
Duct air velocity  
100 to 4,000 feet/min (0.5 to 20.32  
m/s).  
Dimensions  
14.750" (37 cm) length x 5.500" (14  
cm) width x 2.750" (7 cm) deep.  
3 to 17  
Sec.  
3 to 17  
Sec.  
3 to 17  
Sec.  
Response  
Time  
Power Up  
Time  
2 Sec.  
2 Sec.  
2 Sec.  
SS-PDR: Relay Contact Ratings  
10 Amp @ 30 VDC  
Alarm  
Auxiliary  
Contacts *  
(DPDT)  
10 Amp @ 277 VAC (0.75 Pow er Factor)  
240 VAC @ 249 VAC (0.4 Pow er Factor)  
1/8 HP@ 120 VAC  
1/4 HP@ 240 VAC  
Options  
Supervisory  
Contact  
2.0 Amp @ 30 VDC (resistive)  
1. RTS-451, RTS-451KEY, RA400Z.  
2. PA400 (Review installation instruc-  
tions on power requirements).  
(SPST)  
Minimum sw itching current of 100 mA @ 5 VDC.  
SS-PDR  
Product Line  
Information  
Operating voltage range  
20 to 30 VDC, 24 VAC/VDC, 120/  
240 VAC auxiliary power (requires  
a separate auxiliary source).  
Model  
Description  
SS-PD  
Duct detector housing with SmartScan™  
Standby current  
photoelectric smoke detector.  
300 µA @ 24 VDC (one communi-  
cation every 5 seconds with LED  
blink enabled).  
Operating temperature range  
32° to 131°F (0° to 55°C).  
Relative Humidity range  
10% to 93% (non-condensing).  
Duct air velocity  
100 to 4,000 feet/min (0.5 to  
20.32 m/s).  
Dimensions  
14.750" (37 cm) length x 5.500" (14  
cm) width x 2.750" (7 cm) deep.  
SS-PDR  
Duct detector housing with SmartScan™  
photoelectric smoke detector, DPDT relay.  
A5053GM  
A5067  
Replacement photoelectric sensor board.  
Replacement power board (without relay).  
Replacement power board (with relay).  
The RA400Z  
A5060  
ST-1.5  
Metal sampling tube, duct widths 1' to 2'  
(see table at left for metric lengths).  
ST-3  
Metal sampling tube, duct widths 2' to 4'.  
Metal sampling tube, duct widths 4' to 8'.  
Metal sampling tube, duct widths 8' to 12'.  
Remote annunciator alarm LED.  
ST-5  
ST-10  
RA400Z  
RTS451  
Options  
Remote test station. Mounts in single-gang  
box. Includes red alarm LED and magnet  
test switch.  
The RTS451  
1. RTS-451, RTS-451KEY, RA400Z.  
2. PA400 (Review installation instruc-  
tions on power requirements).  
RTS451KEY Key-activated remote test station.  
F36-09-11  
M02-04-00  
S08-39-01  
Replacement filters.  
Replacement test magnet.  
Replacement photo insect screen.  
The RTS451KEY  
Page 2 of 4  
SS-PD and SS-PDR  
CS-2463 10/21/04  
Sample Wiring Diagrams  
SS-PD Duct  
Smoke Detector  
using a UL Listed  
control panel  
On to other  
Detectors on  
the Loop  
6821wir1.wmf  
SS-PD Duct  
6821wir2.wmf  
Smoke Detector  
with optional  
RA400Z  
SS-PD Detector  
Terminals  
SS-PD Detector Terminals  
SS-PD Duct  
Smoke Detector  
with RTS451/  
RTS451KEY  
SS-PD  
Please refer to manual  
I56-1978-002R for  
installation instructions.  
NOTE: For RTS451,  
Terminal 3 is not  
used. RTS451 does  
not have a Terminal  
6.  
SS-PDR  
For RTS451KEY,  
Terminals 3 and 6  
are not used.  
Please refer to manual  
I56-1979-003R for  
installation instructions.  
Outside Duct Width  
Inlet Tube*  
Up to 2 feet (0.6096 m)  
ST-1.5  
ST-3  
2 to 4 feet (0.6096 to 1.2192 m)  
4 to 8 feet (1.2192 to 2.4384 m)  
8 to 12 feet (2.4384 to 3.6576 m)  
ST-5  
ST-10  
*NOTE: Inlet tube is required and must be purchased separately.  
Order one inlet tube for each duct smoke detector ordered.  
SS-PD and SS-PDR CS-2463 10/21/04  
Page 3 of 4  
The Gamewell Company  
12 Clintonville Road  
Northford, CT 06472-1610  
Phone: 203-484-7161  
Fax: 203-484-7118  
Specifications and wiring information are provided for information only and are believed  
to be accurate. Gamewell assumes no responsibility for their use.  
Data and design are subject to change without notice. Installation and wiring instructions  
shipped with the product shall always be used for actual installation. For more  
information, contact Gamewell.  
www.gamewell.com  
A Honeywell Company  
© 2004 Gamewell  
Page 4 of 4  
SS-PD and SS-PDR CS-2463 10/21/04  

相关型号:

ST-3-10

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-120

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-16

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-20

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-28

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-36

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-48

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-3-56

Split Bobbin Power Transformer, 2.4VA, ROHS COMPLIANT
BEL

ST-302

PHOTOTRANSISTORS
ETC

ST-303

PHOTOTRANSISTOR | NPN | 880NM PEAK WAVELENGTH | LED-7A
ETC

ST-305

Photo transistors(a high-sensitivity NPN silicon phototransistor mounted in a clear sidelooking)
KODENSHI

ST-308

Photo Transistor, 960nm, 0.02A I(C),
KODENSHI