240ACDR_48SC [GAPTEC]
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply;型号: | 240ACDR_48SC |
厂家: | GAPTEC |
描述: | 240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply |
文件: | 总5页 (文件大小:2060K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
240ACDR_SC Series
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
Industrial DIN Rail Power Supply
AC-DC Converter
240 Watt
High efficiency up to 94%
Universal AC input range
(85~264VAC)
Support 1+1 or N+1
redundant system
Built-in current sharing
function
Built-in current limiting
circuit
Over voltage protection (OVP)
Over load protection (OLP)
Short circuit protection (SCP)
Over temperature prot. (OTP)
Wide operating ambient
temperature (-25°C~70°C)
150% (360W) peak load
capacity
The 240ACDR_SC series features standard rail mounting, energy efficiency
and is highly cost-effective. The series offers stability and high noise
immunity especially for industrial control equipment, machinery and
other demanding environments for industrial equipment. This converter
offers a compact and light weight design with and standard rail installation
(32mm). Furthermore this series offers Easy Fuse Tripping due and a
built-in DC OK relay contact. The converter can be installed on TS-35/7.5
or TS-35/15.
Easy fuse tripping due to high
overload current
UL-60950-1 (E347551)
Common specifications
Short circut protection:
Temperature rise at full load:
Cooling:
Input specifications
Long-term mode, automatic recovery
40ꢀC MAX
Input voltage range
Input frequency
Power factor
85~264VAC, 127-375VDC
47~63Hz
110VAC
• 0.99 (typ)
230VAC
• 0.95 (typ)
Free air convection
-25ꢀC~+70ꢀC
Operation temperature range:
Storage temperature range:
Storage humidity range:
Temperature coefficient:
MTBF (using MIL-HDBK-217F):
Safety standards:
AC current
110VAC
• 3.0A (max)
230VAC
• 1.5A (max)
-40ꢀC ~+85ꢀC
< 95%
Inrush current
Leakage current
Cold start
110VAC
• 20A (typ)
230VAC
• 40A (typ)
0.03%/ꢀC MAX
Input—output: <0.25mA
Input—PG: <3.5mA
+25ꢀC >300,000 hours
meet UL508, UL60950, EN60950
150% of rated current
support
Power boost:
Output specifications
Parallel function:
Item
Test conditions
Full load
Min Typ
Max
3
Units
%
DC-OK:
V On: when output voltage is up to 90%
of rated output voltage
V Off: when output voltage is down to
80% of rated output voltage
Output voltage
accuracy
Voltage adjustment • 24V: 24~28V
range
• 48V: 48~56V
DC-OK relay contact rating:
Case material:
Max 30V/1A or 60V/0.3A or 30Vac/0.3A
resistive load
Line regulation
Vin= min. to max. at
full load
0.5
1
%
%
Heat-resistant Plastic (UL94-V0) and
metal
Load regulation
Ripple + Noise
Set-up time
0% to 100% load
see model specifications table
Dimensions (L*W*H):
Weight:
45*124*119mm
875g
• @230VAC
• @100VAC
3
3
s
s
Hold-up time
@230VAC, full load
20
ms
%
Isolation specifications
Overshoot and
undershoot
5
Item
Test condition
Min
Typ
Max
Units
VAC
Withstand voltage*
• Primary-Sec. ≤10mA
• Primary-PG ≤10mA
• Secondary-PG ≤20mA
3000
2500
500
Switching frequency
100
KHz
Isolation resistance
100
MΩ
Protection specifications
* Input-Output, tested for 1 minute, 500VDC and leakage current less than 1mA
Over-load
protection
110%~150% of rated current, constant current limiting for
some time (150% of rated current, last 3S) then PS
stop working for 7S, after 7S, if the load <=rated current,
PS will work normally, auto recovery
Example:
240ACDR_24SC
Over-voltage
protection
• 24V: 29~33V, constant voltage, auto recovery
• 28V: 58~63V, constant voltage, auto recovery
240 = 240 Watts
AC = AC/DC
DR = Din Rail
24 = Vout
S = Single Output
C = PFC (Power Factor Correction)
Over-temperature
protection
105 5ꢀC, detect on heat sink of power transistor; shut
down O/P, auto recovery after temperature goes down.
Note:
1. All parameters NOT specially mentioned are measured at rated input, rated load
and 25ꢀC of ambient temperature.
Page 1 of 5
240ACDR_SC – Rev. 2020-1.3
Specifications subject to change without notice.
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
240ACDR_SC Series
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
Industrial DIN Rail Power Supply
EMC specifications
EMC / Emission
Compliance to EN55022, EN55024, FCC PART 15 Class B
Compliance to EN61000-3-2, CLASS A
EMC / Harmonic current
EMC / Immunity
Compliance to EN61000-4-2, -3, -4, -5, -6, -8, -11; heavy industry level
The power supply is considered as a component which will be installed into a final equipment.
The final equipment must be re-confirmed that it still meets EMC directives.
Approval
Model
Power
[W]
Output
[Vo, VDC]
Rated Current
[A]
Current Range
[A]
Ripple&Noise* [mV, max]
Efficiency
[%, typ]
0~70ꢀC
-25ꢀC
UL (pending)
UL (pending)
240ACDR_24SC
240ACDR_48SC
240
240
24
48
10
5
0~10
0~5
240
480
94
93
480
480
* Measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uF & 10uF parallel capacitor.
Mechanical dimensions
240ACDR_SC
AC terminal blocks installation information
AC/DC terminal
Type
Terminal No.
Function
Wire specs
Rec. torque
5Nm
Screw terminal blocks
0.5-6mm2
0.5-4mm2
1
2
3
PG
N
Solid wire
20~10AWG
Strand wire
Wire Spec
L
AWG20-10 (PG wire >18AWG)
2.8mm
Max wire diameter
DC terminal blocks installation information
Recommended stripping length 7mm
Terminal No.
4&5
Function
Wire specs
Rec. torque
5Nm
Screwdriver
3.5mm Straight or Cross Screwdriver
5NM
DC OK Relay
contact
Recommended torque
20~10AWG
6&7
8&9
+V
-V
Page 2 of 5
240ACDR_SC – Rev. 2020-1.3
Specifications subject to change without notice.
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
240ACDR_SC Series
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
Industrial DIN Rail Power Supply
Typical characteristics
Output current vs. ambient temperature – 240ACDR_24SC
Output current vs. ambient temperature – 240ACDR_48SC
Ambient temperature (ꢀC)
short time working, 3s.
Ambient temperature (ꢀC)
continuous working
Functional block diagram
Functional diagram
Page 3 of 5
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
240ACDR_SC – Rev. 2020-1.3
Specifications subject to change without notice.
240ACDR_SC Series
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
Industrial DIN Rail Power Supply
Mounting method instruction
240ACDR_24SC
A1 is recommended output current.
A2 is the allowed max output current (PSU lifetime is around half of A1).
Below curves are tested under 230Vac (179~264Vac), when 110Vac input
(85~175Vac), all derating points drop 10ꢀC.
Mounting A
Mounting B
Mounting C
Mounting D
Mounting E
Page 4 of 5
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
240ACDR_SC – Rev. 2020-1.3
Specifications subject to change without notice.
240ACDR_SC Series
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
Industrial DIN Rail Power Supply
Mounting method instruction
240ACDR_48SC
Mounting A
Mounting B
Mounting C
Mounting D
Mounting E
Page 5 of 5
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
240ACDR_SC – Rev. 2020-1.3
Specifications subject to change without notice.
相关型号:
240ACDR_SC
240W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated Industrial DIN Rail Power Supply
GAPTEC
©2020 ICPDF网 联系我们和版权申明