70G-IDC24S [GRAYHILL]
Contact Closure DC Input Modules; 触点闭合DC输入模块型号: | 70G-IDC24S |
厂家: | GRAYHILL, INC |
描述: | Contact Closure DC Input Modules |
文件: | 总2页 (文件大小:112K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Contact Closure DC Input Modules
FEATURES
• Wire Dry Contact Sensors Directly
to Module, Eliminate External
Power Supply
• 2500 Vac Isolation
• Built-In Status LED
• UL, CSA, CE Mark, TÜV Certified
(TÜV not available on OpenLine®)
• Simplifies Field Wiring
CIRCUITRY:NegativeTrueLogic
G5
OpenLine®
I/O MODULE
PIN #
TYPICAL WIRING FOR MODULE 0
+
1
6
Vcc
VDC
2
A
+
–
+
–
INPUT
1
2
3
4
1
DEVICE
7
5
CH. A STATUS
GND
OPTICAL
HYSTERESIS
FILTER
TRANSFORMER
ISOLATION
ISOLATION
2
CONTACT
DEBOUNCE
+VCC
3
INPUT
DEVICE
B
3
4
8
9
CH. B STATUS
MODULE ID
+
OPTICAL
ISOLATION
OUTPUT
10KΩ
HYSTERESIS
DC
FILTER
OUTPUT
DRIVER
CIRCUIT
SUPPLY
–
4
5
GROUND
TERMINAL
BLOCK #
BASE
OR
RACK
0Ω
MODULE
OpenLine®
SPECIFICATIONS:
per MIL–STD–202, Method 213, Condition F
Storage Temperature Range:
-40°C to +125°C
Operating Temperature Range:
0°C to +60°C
Specifications apply over operating
temperature range unless noted otherwise.
Vibration: .15mm, 10 to 50 Hz per IEC68-2-6
Mechanical Shock: 50 G's, 0.5 mS, sinsoidal
per IEC68-2-27
Storage Temperature Range:
-40°C to +100°C
Operating Temperature Range:
-40°C to +85°C
AllModules
OutputSpecifications
Output Current Range: 1-50 mA
Breakdown Voltage: 50 Vdc minimum
Off State Leakage Current: 1 µA maximum
On State Voltage Drop: 0.45 Vdc at 50 mA
maximum
Available from your local Grayhill Distributor.
For prices and discounts, contact a local Sales
Office, an authorized local Distributor or Grayhill.
G5
General Characteristics
Isolation Voltage Field to Logic:
2500 Vac (rms) minimum
Vibration:20G'speakor.06"doubleamplitude
10–2000 Hz per MIL–STD–202, Method 204,
Condition D
Mechanical Shock: 1500 G's 0.5 mS half-sine
SPECIFICATIONS: By Part Number
Grayhill Part Number
Type/Function
G5, Dry Contact
70L-IDC5S
70G-IDC5S
70G-IDC24S
Specifications
Units
Maximum Dry Contact Voltage Rating
Minimum Dry Contact Current Rating
Maximum Turn-on Time
Vdc
mA
25
5
10
25
5
3.0
25
5
3.0
mSec
mSec
Ω
Maximum Turn-off Time
10
3.0
3.0
Contact Resistance (Output Low)
Contact Resistance (Output High)
Nominal Logic Voltage (Vcc)
Logic Voltage Range: G5
Max. Logic Supply Current
@ Nominal Vcc
≤ 1.25K
25K
5
≤1.25K
25K
5
4.5-6
41
≤ 1.25K
25K
24
15-30
41
Ω
Vdc
Vdc
mA
4.5-5.5
1201
1WHEN BOTH CHANNELS ARE ACTIVATED
I/O
20
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
Analog I/O Modules Engineering Information and Selection Chart
ANALOGI/OMODULES
12-bit value that is right justified and packed in
a 16-bit word that represents the equivalent
analog value sensed.
Analogoutputmodulesareusedinproportional
control of devices such as valves, motors, and
heaters. Analog input modules are used in data
gatheringandproportionalcontrolapplications.
Start Pulse: High for 6.4 µS Min., then low
for 3.2 µS
Data Packet: Each bit is 12.8 µS long.
High for first 3.2 µS of the bit.
Middle 6.4 µS determines the value of the
data bit (High = 1, Low = 0).
®
OpenLine thermocouple inputs linearize the
thermocouple reading and returns degrees to
the controller.
All modules are potted for industrial
environments. They operate under high
vibration (IEC68-2-6; 0.15 mm/sec2 at 10-
150Hz) mechanical shock (IEC68-2-27; 11
mS,sinusoidal30gS)andhighrelativehumidity
(IEC68-2-3; 5-95% non-condensing). They
feature a high level of noise immunity and
accuracy. All models provide isolation from
field to logic, field to power supply and module
to module.
Low for last 3.2 µS of the bit.
Stop Pulse: Low for 500 µS minimum
Times shown are 10%, except minimums.
SERIAL DATA FORMAT**
Openline® Analog Output
For analog output modules, the output of these
modules is zero scale on power up, then it is
the analog equivalent of the 12-bit value sent
to the module over the communication lines.
G5 Analog Input
G5voltageorcurrentinputmodulesareactually
frequency converters. The input to these
modules is a signal from a sensor. The output
from these modules is a squarewave whose
frequency varies linearly from 14.4 to 72 KHz
and is proportional to the input signal. The
controller must be able to measure this
frequency and convert it back to a signal level.
G5 Analog Output
The output (voltage or current level) of these
modules varies proportionally to the 12-bit
serial data string sent to them by a control
circuit. The data string is typically 213.2 µSec.
long as detailed in Figure 1. Once a data string
is received, the output is set and remains
constant until another data string is sent.
Therefore, the output level of the module could
be changed almost 4700 times a second.
OpenLine® Analog
OpenLine® analog modules communicate
serially with the controller. Each module has a
separatetransmitandreceivelinethatoperates
at 115,200 baud with no parity bits, 8 data bits,
and 1 stop bit (115.2K,N,8,1). The command
structure and responses for all modules are
detailed in Bulletin No. 743. Each module has
a microcontroller and non-volatile serial
EEPROM memory. The calibration data is
stored within the EEPROM, and may be
changed using the appropriate commands
and the 70L-PROG field calibration unit. The
software provided with the calibration unit
communicates with the modules through the
serial port of a PC. Calibration equipment is not
provided.
G5 thermocouple modules pass through the
thermocouple reading and do not linearize the
signal. Linearization must take place within the
controller.
For more information on programming Grayhill
analog output modules, request a copy of
Bulletin No. 581.
AgencyApprovals
OpenLine® analog modules are EN50082-2
and EN50081-2 compliant and meet the
requirements of 89/336/EEC EMC directive.
They are also EN60950 (61010-1) compliant.
Meetingtheserequirementsallowsthemodules
to bear the CE mark. Additionally, the modules
are CSA certified to CSA 22.2 No. 14-95M and
CSA 22.2 No. 213-M1987 Class I, Div. 2
Groups A, B, C and D and are UL recognized
to UL 508.
START
12 BIT DATA
END
OpenLine® Analog Input Modules
Upon request, analog input modules return a
9.6µS
153.6µS
500µS
Figure 1
PART NUMBER EXPLANATION: Analog I/O Modules
Module Type
73G = Analog Module, G5 Package, Single Channel
73L = Analog Module, OpenLine® Package, Dual Channel
Function
OV = Analog Output, Voltage
II = Analog Input, Current
IT = Analog Input, Temperature
OI
IV
=
=
Analog Output, Current
Analog Input, Voltage
73G-IV50M
Suffix
Analog Modules:
5
=
0–5 Vdc
5B = -5–5 Vdc
0–1 Vdc
10 = 0 - 10 Vdc
10B = -10 - 10 Vdc
020 = 0 to 20 mA
420 = 4 to 20 mA
5000 = 0 to 5 A
AC120 = 28 to 140 Vac
AC240 = 28 to 280 Vac
50M = 0–50 mV
100M = 0–100 mV
R100 = RTD
R3100 = 3 Wire RTD
R4100 = 4 Wire RTD
1
=
CJ = J type TC
CK = K type TC
CR = R type TC
CT = T type TC
I/O
21
Grayhill, Inc.
•
561 Hillgrove Avenue
•
LaGrange, Illinois 60525-5997
•
USA
•
Phone: 708-354-1040
•
Fax: 708-354-2820
•
www.grayhill.com