70G-IDC24S [GRAYHILL]

Contact Closure DC Input Modules; 触点闭合DC输入模块
70G-IDC24S
型号: 70G-IDC24S
厂家: GRAYHILL, INC    GRAYHILL, INC
描述:

Contact Closure DC Input Modules
触点闭合DC输入模块

文件: 总2页 (文件大小:112K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Contact Closure DC Input Modules  
FEATURES  
• Wire Dry Contact Sensors Directly  
to Module, Eliminate External  
Power Supply  
• 2500 Vac Isolation  
• Built-In Status LED  
• UL, CSA, CE Mark, TÜV Certified  
(TÜV not available on OpenLine®)  
• Simplifies Field Wiring  
CIRCUITRY:NegativeTrueLogic  
G5  
OpenLine®  
I/O MODULE  
PIN #  
TYPICAL WIRING FOR MODULE 0  
+
1
6
Vcc  
VDC  
2
A
+
+
INPUT  
1
2
3
4
1
DEVICE  
7
5
CH. A STATUS  
GND  
OPTICAL  
HYSTERESIS  
FILTER  
TRANSFORMER  
ISOLATION  
ISOLATION  
2
CONTACT  
DEBOUNCE  
+VCC  
3
INPUT  
DEVICE  
B
3
4
8
9
CH. B STATUS  
MODULE ID  
+
OPTICAL  
ISOLATION  
OUTPUT  
10KΩ  
HYSTERESIS  
DC  
FILTER  
OUTPUT  
DRIVER  
CIRCUIT  
SUPPLY  
4
5
GROUND  
TERMINAL  
BLOCK #  
BASE  
OR  
RACK  
0Ω  
MODULE  
OpenLine®  
SPECIFICATIONS:  
per MIL–STD–202, Method 213, Condition F  
Storage Temperature Range:  
-40°C to +125°C  
Operating Temperature Range:  
0°C to +60°C  
Specifications apply over operating  
temperature range unless noted otherwise.  
Vibration: .15mm, 10 to 50 Hz per IEC68-2-6  
Mechanical Shock: 50 G's, 0.5 mS, sinsoidal  
per IEC68-2-27  
Storage Temperature Range:  
-40°C to +100°C  
Operating Temperature Range:  
-40°C to +85°C  
AllModules  
OutputSpecifications  
Output Current Range: 1-50 mA  
Breakdown Voltage: 50 Vdc minimum  
Off State Leakage Current: 1 µA maximum  
On State Voltage Drop: 0.45 Vdc at 50 mA  
maximum  
Available from your local Grayhill Distributor.  
For prices and discounts, contact a local Sales  
Office, an authorized local Distributor or Grayhill.  
G5  
General Characteristics  
Isolation Voltage Field to Logic:  
2500 Vac (rms) minimum  
Vibration:20G'speakor.06"doubleamplitude  
10–2000 Hz per MIL–STD–202, Method 204,  
Condition D  
Mechanical Shock: 1500 G's 0.5 mS half-sine  
SPECIFICATIONS: By Part Number  
Grayhill Part Number  
Type/Function  
G5, Dry Contact  
70L-IDC5S  
70G-IDC5S  
70G-IDC24S  
Specifications  
Units  
Maximum Dry Contact Voltage Rating  
Minimum Dry Contact Current Rating  
Maximum Turn-on Time  
Vdc  
mA  
25  
5
10  
25  
5
3.0  
25  
5
3.0  
mSec  
mSec  
Maximum Turn-off Time  
10  
3.0  
3.0  
Contact Resistance (Output Low)  
Contact Resistance (Output High)  
Nominal Logic Voltage (Vcc)  
Logic Voltage Range: G5  
Max. Logic Supply Current  
@ Nominal Vcc  
1.25K  
25K  
5
1.25K  
25K  
5
4.5-6  
41  
1.25K  
25K  
24  
15-30  
41  
Vdc  
Vdc  
mA  
4.5-5.5  
1201  
1WHEN BOTH CHANNELS ARE ACTIVATED  
I/O  
20  
Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com  
Analog I/O Modules Engineering Information and Selection Chart  
ANALOGI/OMODULES  
12-bit value that is right justified and packed in  
a 16-bit word that represents the equivalent  
analog value sensed.  
Analogoutputmodulesareusedinproportional  
control of devices such as valves, motors, and  
heaters. Analog input modules are used in data  
gatheringandproportionalcontrolapplications.  
Start Pulse: High for 6.4 µS Min., then low  
for 3.2 µS  
Data Packet: Each bit is 12.8 µS long.  
High for first 3.2 µS of the bit.  
Middle 6.4 µS determines the value of the  
data bit (High = 1, Low = 0).  
®
OpenLine thermocouple inputs linearize the  
thermocouple reading and returns degrees to  
the controller.  
All modules are potted for industrial  
environments. They operate under high  
vibration (IEC68-2-6; 0.15 mm/sec2 at 10-  
150Hz) mechanical shock (IEC68-2-27; 11  
mS,sinusoidal30gS)andhighrelativehumidity  
(IEC68-2-3; 5-95% non-condensing). They  
feature a high level of noise immunity and  
accuracy. All models provide isolation from  
field to logic, field to power supply and module  
to module.  
Low for last 3.2 µS of the bit.  
Stop Pulse: Low for 500 µS minimum  
Times shown are 10%, except minimums.  
SERIAL DATA FORMAT**  
Openline® Analog Output  
For analog output modules, the output of these  
modules is zero scale on power up, then it is  
the analog equivalent of the 12-bit value sent  
to the module over the communication lines.  
G5 Analog Input  
G5voltageorcurrentinputmodulesareactually  
frequency converters. The input to these  
modules is a signal from a sensor. The output  
from these modules is a squarewave whose  
frequency varies linearly from 14.4 to 72 KHz  
and is proportional to the input signal. The  
controller must be able to measure this  
frequency and convert it back to a signal level.  
G5 Analog Output  
The output (voltage or current level) of these  
modules varies proportionally to the 12-bit  
serial data string sent to them by a control  
circuit. The data string is typically 213.2 µSec.  
long as detailed in Figure 1. Once a data string  
is received, the output is set and remains  
constant until another data string is sent.  
Therefore, the output level of the module could  
be changed almost 4700 times a second.  
OpenLine® Analog  
OpenLine® analog modules communicate  
serially with the controller. Each module has a  
separatetransmitandreceivelinethatoperates  
at 115,200 baud with no parity bits, 8 data bits,  
and 1 stop bit (115.2K,N,8,1). The command  
structure and responses for all modules are  
detailed in Bulletin No. 743. Each module has  
a microcontroller and non-volatile serial  
EEPROM memory. The calibration data is  
stored within the EEPROM, and may be  
changed using the appropriate commands  
and the 70L-PROG field calibration unit. The  
software provided with the calibration unit  
communicates with the modules through the  
serial port of a PC. Calibration equipment is not  
provided.  
G5 thermocouple modules pass through the  
thermocouple reading and do not linearize the  
signal. Linearization must take place within the  
controller.  
For more information on programming Grayhill  
analog output modules, request a copy of  
Bulletin No. 581.  
AgencyApprovals  
OpenLine® analog modules are EN50082-2  
and EN50081-2 compliant and meet the  
requirements of 89/336/EEC EMC directive.  
They are also EN60950 (61010-1) compliant.  
Meetingtheserequirementsallowsthemodules  
to bear the CE mark. Additionally, the modules  
are CSA certified to CSA 22.2 No. 14-95M and  
CSA 22.2 No. 213-M1987 Class I, Div. 2  
Groups A, B, C and D and are UL recognized  
to UL 508.  
START  
12 BIT DATA  
END  
OpenLine® Analog Input Modules  
Upon request, analog input modules return a  
9.6µS  
153.6µS  
500µS  
Figure 1  
PART NUMBER EXPLANATION: Analog I/O Modules  
Module Type  
73G = Analog Module, G5 Package, Single Channel  
73L = Analog Module, OpenLine® Package, Dual Channel  
Function  
OV = Analog Output, Voltage  
II = Analog Input, Current  
IT = Analog Input, Temperature  
OI  
IV  
=
=
Analog Output, Current  
Analog Input, Voltage  
73G-IV50M  
Suffix  
Analog Modules:  
5
=
0–5 Vdc  
5B = -5–5 Vdc  
0–1 Vdc  
10 = 0 - 10 Vdc  
10B = -10 - 10 Vdc  
020 = 0 to 20 mA  
420 = 4 to 20 mA  
5000 = 0 to 5 A  
AC120 = 28 to 140 Vac  
AC240 = 28 to 280 Vac  
50M = 0–50 mV  
100M = 0–100 mV  
R100 = RTD  
R3100 = 3 Wire RTD  
R4100 = 4 Wire RTD  
1
=
CJ = J type TC  
CK = K type TC  
CR = R type TC  
CT = T type TC  
I/O  
21  
Grayhill, Inc.  
561 Hillgrove Avenue  
LaGrange, Illinois 60525-5997  
USA  
Phone: 708-354-1040  
Fax: 708-354-2820  
www.grayhill.com  

相关型号:

70G-IDC5

DC Input Modules
GRAYHILL

70G-IDC5B

DC Input Modules
GRAYHILL

70G-IDC5D

DC Input Modules
GRAYHILL

70G-IDC5G

AC/DC Input Modules
GRAYHILL

70G-IDC5K

DC Input Modules
GRAYHILL

70G-IDC5NP

AC/DC Input Modules
GRAYHILL

70G-IDC5S

Contact Closure DC Input Modules
GRAYHILL

70G-ISW1

Jumper Bars for Grayhill G5 and Mini Series I/O Racks
GRAYHILL

70G-JUMP12

Jumper Bars for Grayhill G5 and Mini Series I/O Racks
GRAYHILL

70G-JUMP8

Jumper Bars for Grayhill G5 and Mini Series I/O Racks
GRAYHILL

70G-OAC15

AC Output Modules
GRAYHILL

70G-OAC15-L

AC Output Modules
GRAYHILL