FF-SRT051FE [HONEYWELL]

Analog Circuit;
FF-SRT051FE
型号: FF-SRT051FE
厂家: Honeywell    Honeywell
描述:

Analog Circuit

文件: 总3页 (文件大小:578K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
FF-SRT Time Delay Module  
FF-SR Series  
FEATURES  
• Complies with the Machinery Directive  
98/37/EC, IEC 255, VDE 0435, and  
UL 508  
• Provides a delay after module is  
de-energized  
S
uitable for interfaces  
up to  
CATEGORY 1  
per EN 954-1  
• Output: one NC, one NO positive-guided  
contacts  
• Available with one or two time delay  
circuits (channels)  
• Available with fixed or selectable delay  
up to 30 seconds  
• LED status indication  
• Mechanical life up to ten million  
operations  
• Electrical life up to 300,000 operations  
• Switching current up to 8A  
• Voltage drop protection  
The FF-SRT Time Delay module provides a time delay before a safety interface is  
opened safely.  
If a two-channel version is used, the output contacts of the two time delay circuits  
are connected in series. When the displayed time has elapsed, the safety contacts  
within the module open safely, even if one of the other contacts is welded.  
• 45 mm (1.77 in.) width  
When power is applied to the module (A1/A2), the normally closed contact (15/16)  
will open immediately and the normally open contact (27/28) will close.  
APPLICATIONS  
• Time delay required before  
disconnection of safety interface circuit  
After power is removed from the module (A1/A2), the normally closed contact (15/  
16) will close and the normally open contact (27/28) will open after the fixed or set  
time has elapsed.  
For example, this module may be used with an emergency stop module. The emer-  
gency stop module will immediately forward the emergency stop condition to the  
machine control circuitry. The time delay module can be used to keep some non-  
safety related machinery operating (door locked) for a short period of time to avoid  
an unsafe condition or simplify the machine startup cycle.  
!
WARNING  
MISUSE OF DOCUMENTATION  
The information presented in this product sheet (or catalogue) is for reference only. DO NOT USE this document as system  
installation information.  
Complete installation, operation and maintenance information is provided in the instructions supplied with each product.  
Failure to comply with these instructions could result in death or serious injury.  
FF-SRT  
Industrial Safety Products •  
225  
FF-SRT Time Delay Module  
S
uitable for interfaces  
up to  
CATEGORY 1  
per EN 954-1  
SPECIFICATIONS  
• Time delay before disconnection of safety interface circuits  
General technical data  
Available time ranges  
Adjustable 1 channel: SRT _ _ 1R: 0.1 to 1 sec; 0.3 to 3 sec; 0.5 to 5 sec;  
1 to 10 sec; 3 to 30 sec.  
Fixed 1 channel: SRT _ _ 1F: 1; 5, 10, and 30 sec.  
Adjustable 2 channels: SRT _ _ 2R: 0.1 - 1 sec, 0.5 - 5 sec, 1 -10 sec.  
Fixed 2 channels: SRT _ _ 2F; 1, 5, 10 sec  
Repeatability precision  
+ 15 % from selected value  
Input  
Nominal voltage  
Nominal consumption  
Nominal frequency  
Contact complement  
Contact type  
120 Vac (-15%, +10%), 230 Vac (-20%, +10%), 24 Vdc (-10%, +20%)  
One channel model: 0.85 W, 4.5 VA; Two channel model; 1.7 W, 4.5 VA  
50 to 60 Hz  
Output  
1 NO contact, 1 NC contact  
Safety relay, positive-guided  
Switching Capability  
Current Range (min. to max.)  
Voltage Range (min. to max.)  
DC  
Power factor = 1 with resistive load  
30 mA to 8A  
10 to 110 Vdc  
10 to 250 Vac  
AC  
Switching capability (per AC15: EN 60947-5.1)  
NO contact: 3A / 250 Vac  
-
NC contact: 1 A / 250 Vac  
Typical Electrical Life Expectancy  
Power factor = 1 at 230 Vac/dc  
300,000 operations  
150,000 operations  
100,000 operations  
Limitation Factor (Note 1, Note 2)  
0.45  
3A  
5A  
10A  
Typical Power Factor (cos j)  
0.3  
0.5  
0.70  
0.7  
1.0  
0.85  
1.00  
Operating frequency  
Fuse rating  
2000 switching cycles/hour (max.)  
6 A time delayed  
Mechanical life  
Ten million switching operations  
General  
Temperature range  
Sealing  
-20°C to +60°C (-4°F to 140°F) at max. 90% humidity  
Housing IP 40; Terminals IP 20  
Housing material  
Vibration resistance  
Conductor connection  
Thermoplastic  
Amplitude 0.35 mm; Frequency 10 to 55 Hz  
2 x 2.5 mm2 solid (max.) [12 AWG] or 2 x 1.5 mm2 [16 AWG] (max.)  
stranded wire with sleeve DIN 46288  
Conductor attachment  
Mounting  
Flat terminal according to DIN 46206 and DIN 57609/VDE  
Quick install rail mounting EN 50022-35  
Weight  
200 g (0.44 lb.) for Vdc / 350 g (0.77 lb) for Vac  
CONTACT LIFE FOR 100%  
ORDERING INFORMATION  
LIMITATION FACTOR FOR  
INDUCTIVE LOADS  
power factor < 1 (cos ϕ)  
RESISTIVE LOAD (TYPICAL)  
FF-SRT  
Voltage:  
power factor = 1 (cos ϕ)  
2 = 24 Vdc  
E = 120 Vac  
G = 230 Vac  
R: Time adjustable  
F: Time fixed  
Number of channels:  
1 = 1 Channel  
2 = 2 Channel (24 Vdc only)  
Max delay time:  
01: 1 s  
03: 3 s  
Note: see table  
05: 5 s  
above for available  
time ranges  
10: 10 s  
30: 30 s  
Note 1: Total operations = Operations at power factor 1  
multiplied by the limitation factor. If the power factor is 0.5  
at 230 Vac, 2A (300,000 operations), the limitation factor is  
0.70. 300,000 x 0.70 = 210,000 total operations.  
Note 2: Install arc suppression device across load to avoid  
module contact arcing and ensure specified relay life ex-  
pectancy.  
Switching power P [kVA]  
Power factor  
226  
Industrial Safety Products •  
FF-SRT  
INSTALLATION DIAGRAM  
MOUNTING DIMENSIONS  
Width: 45 mm/1.77 in; Height: 74 mm/2.91 in; Depth: 121 mm/4.76 in  
45  
121 0.4  
Rail  
WIRING DIAGRAM  
ONE CHANNEL (FF-SRT_1__) TWO CHANNEL (FF-SRT_2__)  
FUNCTIONAL DIAGRAM  
U
U
H
A1/A2  
A1 15 27  
15  
A1 15 27  
15  
t
<
v
t
27  
28  
A1  
27  
28  
A1  
A2  
15-16  
A2  
A1  
27-28  
16  
A2  
16  
t
v
16 28  
A2  
16 28  
A2  
t v = time delay  
APPLICATION EXAMPLE  
+Vdc  
L1  
L2  
L3  
Power of  
Speed  
Driver  
Emer-  
gency  
Stop  
Fuses  
S
S
A1  
S
Delayed power removal  
via  
13  
23  
33  
41  
22  
A1  
27  
15  
12  
11  
(+)  
FF-SRT  
time delay module  
K1  
Honeywell FF-SRS5935  
Power  
S1  
Honeywell  
FF-SRT  
K2  
K3  
S2  
Instant stop  
via  
FF-SRS5935  
emergency stop  
module  
Internal  
switches  
Speed driver  
M
S21  
PE  
S
S
A2  
(-)  
A2  
28  
16  
33  
34  
14  
24  
34  
42  
To  
Speed  
Driver  
Start  
push-  
button  
K1  
K1  
-Vdc  
The example shows an emergency stop circuit with a motor using a speed driver. When an emergency stop condition occurs (e. g. the emergency  
push-button is pressed), the speed driver is shut down immediately via the emergency stop module FF-SRS5935 and the dangerous movement of  
the motor is stopped. When the delay time has elapsed, the power will be removed via the FF-SRT time delay module. External, positive guided  
relays have to be monitored in the S33/S34 loop by its normally closed contacts.  
FF-SRT  
Industrial Safety Products •  
227  

相关型号:

FF-SRT051FG

Analog Circuit
HONEYWELL

FF-SRT102F2

Analog Circuit
HONEYWELL

FF-SRT102FE

Analog Circuit
HONEYWELL

FF-SRT301R2

Analog Circuit
HONEYWELL

FF-SRT301RE

Analog Circuit
HONEYWELL

FF-SRT302FE

Analog Circuit
HONEYWELL

FF-SRT302RE

Analog Circuit
HONEYWELL

FF0115SA1

Card Edge Connector, 15 Contact(s), 1 Row(s), Female, Right Angle, 0.02 inch Pitch, Surface Mount Terminal, White Insulator, Socket
JAE

FF0115SA1E

Card Edge Connector, 15 Contact(s), 1 Row(s), Female, Right Angle, Surface Mount Terminal, LEAD FREE
JAE

FF0115SA2-E3000

Card Edge Connector, 15 Contact(s), 1 Row(s), Female, Right Angle, 0.02 inch Pitch, Surface Mount Terminal, Locking Mech, White Insulator, Socket
JAE

FF0120SA1

Card Edge Connector, 20 Contact(s), 1 Row(s), Female, Right Angle, 0.02 inch Pitch, Surface Mount Terminal, White Insulator, Socket
JAE

FF0120SA1-E3000

Card Edge Connector, 20 Contact(s), 1 Row(s), Female, Right Angle, 0.02 inch Pitch, Surface Mount Terminal, Locking Mech, White Insulator, Socket
JAE