F070B032S [IXYS]
Electric Fuse, 32A, 690VAC, 690VDC, 100000A (IR), Inline/holder,;型号: | F070B032S |
厂家: | IXYS CORPORATION |
描述: | Electric Fuse, 32A, 690VAC, 690VDC, 100000A (IR), Inline/holder, |
文件: | 总5页 (文件大小:211K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
WESTCODE An IXYS Company
French Ferrule Type Fuses 700V
Date:- 17 Mar, 2005
Data Sheet Issue:- 1
Ultra Rapid
Semiconductor Protection Fuse
French Ferrule Type
French Ferrule Fuses
Voltage Rating 700V
Current Rating from 1A to 50A
Size 14x51
Key Features:
Extremely high interrupting rating fuses protection of power semiconductors as per IEC Standard
60269.1 and 4.
660V to 690V voltage rating complying with IEC 33
Non Magnetic construction
gR Characteristics with current ratings from 1A to 32A in accordance with VDE 636-23
¾
¾
¾
Clearing all overloads
Improved safety and protection
Enabling selective co-ordination among all distribution circuit fuses
All models available with or without trip-indicator
gRC fuses from 8A to 50A are 700VAC-DC UL recognised
Data Sheet F070BxxxN/S Issue 1
Page 1 of 5
March, 2005
WESTCODE An IXYS Company
Main Characteristics:
Voltage
French Ferrule Type Fuses 700V
Current
rating
IN(A)
1
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Tested
Interrupting
rating
Total Clearing
I2t @ UN (kA2s)
Watt Losses
0.8IN IN
Size
Ref:
UN (V)
F070B001N
F070B002N
F070B004N
F070B006N
F070B008N
F070B010N
F070B012N
F070B016N
F070B020N
F070B025N
F070B032N
F070B040N
F070B050N
0.31
1
1.4
4.3
0.17
0.35
0.60
1.4
2
0.33
0.77
1.3
4
6.7
1.4
2.4
4.3
5.4
13
30
6
19
2.5
8
30
1.5
3.0
14x51
without
trip
10
12
16
20
25
32
40
50
44
1.75
2.25
2.5
3.3
690
65
4.25
4.8
100kA @ 690V
110
175
300
550
1210
2250
indicator
27
2.75
3.0
5.25
5.8
53
97
3.5
7.0
210
390
4.5
8.8
5.0
10
Current
rating
IN(A)
1
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Tested
Interrupting
rating
Voltage
UN (V)
Total Clearing
I2t @ UN (kA2s)
Watt Losses
0.8IN IN
Size
Ref:
F070B001S
F070B002S
F070B004S
F070B006S
F070B008S
F070B010S
F070B012S
F070B016S
F070B020S
F070B025S
F070B032S
F070B040S
F070B050S
0.8
1.5
7.2
1.4
2.4
4.3
5.4
13
3.5
6.7
0.17
0.33
0.77
1.3
0.35
0.60
1.4
2
4
33
6
19
2.5
8
30
1.5
3.0
10
12
16
20
25
32
40
50
14x51
44
1.75
2.25
2.5
3.3
with Trip
indicator
690
65
4.25
4.8
100kA @ 690V
110
175
300
550
1210
2250
27
2.75
3.0
5.25
5.8
53
97
3.5
7.0
210
390
4.5
8.8
5.0
10
Notes: Minimum operating voltage for integrated trip indicator = 20V
Data Sheet F070BxxxN/S Issue 1
Page 2 of 5
March, 2005
WESTCODE An IXYS Company
Electrical Characteristics:
French Ferrule Type Fuses 700V
Times vs current characteristics
The following curves indicate, for each rated current, pre-arcing time as a function of RMS value of pre-
arcing current I.
Tolerance for mean pre-arcing current: ±10% = ratings from 1, 2, 4A
± 8% = ratings from 6 to 63A
Fuses with gR characteristics can eliminate all overloads. They do not show a minimum breaking
capacity but limit currents of non-operation or operation in compliance with standard VDE 636/23.
I ≤ 4
I ≥ 6
Total clearing I²t:
Horizontal curves show maximum values of total clearing I2t (I2tt) for each rated current as a function of
prospective current Ip @ 690V cosϕ = 0.15 (for 63A @ 600V cosϕ = 0.15). Oblique lines indicate total
clearing duration Tt, with associated pre-arcing duration in brackets.
Data Sheet F070BxxxN/S Issue 1
Page 3 of 5
March, 2005
WESTCODE An IXYS Company
French Ferrule Type Fuses 700V
Cut off Characteristics:
The curves below show, for each rating, value of peak let-through current IC as a function of available
fault current Ip.
I ≤ 4
I ≥ 6
Corrective Factor:
Peak Arc Voltage:
Mean curves showing variation of total clearing
time (I2tt) and total clearing duration Tt as a
function of operating voltage U.
(1) 63A rating – 600V
Curves showing peak value Um of arc voltage
which appears across fuse-link as a function of
operating voltage U @ cosϕ = 0.15.
(2) (2) 1-50A rating – 690V
Data Sheet F070BxxxN/S Issue 1
Page 4 of 5
March, 2005
WESTCODE An IXYS Company
French Ferrule Type Fuses 700V
Outline Drawing & Ordering Information:
F070BxxxN/S – 1.8g
ORDERING INFORMATION
(Please quote code as below)
Voltage Rating (V)
Type
Current Rating IN(A)
With (S) or without (N) indicator
Size
14x51
700
B
001 to 050
S or N
Order code: e.g. F070B001N = Ferrule Type, 700V, 14mm x 51mm, 1 amp fuse without indicator.
IXYS Semiconductor GmbH
Edisonstraße 15
D-68623 Lampertheim
Tel: +49 6206 503-0
Westcode Semiconductors Ltd
Langley Park Way Langley Park
Chippenham Wiltshire SN15 1GE
Tel: +44 (0)1249 444524
Fax: +49 6206 503-627
E-mail: marcom@ixys.de
Fax: +44 (0)1249 659448
E-mail: WSL.sales@westcode,com
IXYS Corporation
3540 Bassett Street
Westcode Semiconductors Inc
3270 Cherry Avenue
www.westcode.com
www.ixys.com
Santa Clara CA 95054 USA
Tel: +1 (408) 982 0700
Fax: +1 (408) 496 0670
E-mail: sales@ixys.com
Long Beach CA 90807 USA
Tel: +1 (562) 595 6971
Fax: +1 (562) 595 8182
E-mail: WSI.sales@westcode.com
The information contained herein is confidential and is protected by Copyright. The information may not be used or disclosed
except with the written permission of and in the manner permitted by the proprietors Westcode Semiconductors Ltd.
© Westcode Semiconductors Ltd.
In the interest of product improvement, Westcode reserves the right to change specifications at any time without prior notice.
Data Sheet F070BxxxN/S Issue 1
Page 5 of 5