IPN = 100..1000 A  
Current Transducer HTA 100..1000-S  
For the electronic measurement of DC, AC and pulsed currents,  
with a galvanic isolation between the primary (high power) circuit  
and the secondary (electronic) circuit.  
Electrical data  
Primarynominal  
current rms  
IPN (A)  
Primary current  
measuring range  
IPM (A)  
Type  
RoHS since  
date code  
Features  
· Open loop transducer using  
Hall Effect  
· Panel mounting - Horizontal or  
Vertical  
· Insulated plastic case recognized  
according to UL 94-V0  
100  
200  
300  
400  
500  
600  
1000  
± 300  
± 600  
± 900  
± 1000  
± 1000  
± 1000  
± 1000  
HTA 100-S  
HTA 200-S  
HTA 300-S  
HTA 400-S  
HTA 500-S  
HTA 600-S  
HTA 1000-S  
46179  
46170  
46097  
46100  
46083  
46222  
46118  
ÎP  
VOUT  
RL  
Overload capability  
Output voltage (Analog) @ ± IPN  
Load resistance TA = 0 .. + 70°C  
TA = - 25 .. + 85°C  
Supply voltage (± 5 %)  
Current consumption  
Rated isolation voltage rms1)  
Rms voltage for AC isolation test, 50 Hz, 1 min  
Isolation resistance @ 500 VDC  
30,000  
± 4  
> 1  
> 3  
± 15  
< 25  
500  
3
A
V
kW  
kW  
V
mA  
V
kV  
Advantages  
· Very good linearity  
· Very good accuracy  
VC  
IC  
Vb  
Vd  
Ris  
· Low temperature drift  
· Wide frequency bandwidth  
· Very low insertion losses  
· High immunity to external  
interference  
> 500  
MW  
Accuracy - Dynamic performance data  
· Current overload capability  
· Low power consumption  
· Wide dynamic range, 100 to 1000 A  
in one package.  
X
Accuracy 2) @ IPN,TA = 25°C, @ ± 15 V  
Linearity error 2) (0 .. ± IPN)  
Electrical offset voltage @ IP = 0, TA = 25°C  
Hysteresis offset voltage @ IP = 0,  
after an excursion of 3 x IPN  
± 1  
± 0.5  
< ± 10  
%
%
mV  
e
L
VOE  
VOH  
< ± 10  
< ± 1  
mV  
mV/K  
Applications  
TCVOE  
TCVOUT  
tr  
di/dt  
BW  
Temperature coefficient of VOE TA = - 25 .. + 85°C  
Temperature coefficient of VOUT TA = - 25 .. + 85°C < ± 0.05 %/K  
Response time to 90 % of IPN step  
di/dt accurately followed  
Frequency bandwidth (- 3 dB) 3)  
· AC variable speed drives and servo  
motor drives  
· Static converters for DC motor drives  
· Battery supplied applications  
· Uninterruptable Power Supplies  
(UPS)  
< 3  
> 50  
DC .. 50  
µs  
A/µs  
kHz  
General data  
· Switched Mode Power Supplies  
(SMPS)  
· Power supplies for welding  
applications.  
TA  
TS  
m
Ambient operating temperature  
Ambient storage temperature  
Mass  
Standards Safety  
EMC  
- 25 .. + 85 °C  
- 25 .. + 85 °C  
230  
g
EN50178(1994)  
EN50082-2(1992)  
EN50081-1(1992)  
Application domain  
Deviation in output when tested to EN 61000-4-3  
< 25  
% of IPN  
· Industrial  
Notes : 1) OvervoltageCategory III, Pollution Degree 2  
2) Excludes the electrical offset  
3) Refer to derating curves in the technical file to avoid excessive core  
heating at high frequency  
Page 1/2  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.  
070110/4  
www.lem.com  
Dimensions HTA 100..1000-S (in mm. 1 mm = 0.0394 inch)  
Bottom view  
Left view  
Secondary terminals  
Terminal 1  
Terminal 2  
Terminal 3  
Terminal 4  
: supply voltage + 15 V  
: supply voltage - 15 V  
: output  
:0V  
Front view  
Mechanical characteristics  
Safety  
· General tolerance  
± 0.5 mm  
· Primary through-hole  
· Connection of secondary  
Ø 32 mm  
Molex 5045-04A  
This transducer must be used in electric/electronic equipment  
with respect to applicable standards and safety requirements  
in accordance with the following manufacturer's operating  
instructions.  
Remarks  
Caution, risk of electrical shock  
· VOUT is positive when IP flows in the direction of the arrow.  
· Temperature of the primary conductor should not exceed  
90°C.  
· This is a standard model. For different versions (supply  
voltages, secondary connections, unidirectional measure-  
ments, operating temperatures, etc.) please contact us.  
When operating the transducer, certain parts of the module can  
carry hazardous voltage (eg. primary busbar, power supply).  
Ignoring this warning can lead to injury and/or cause serious  
damage.  
This transducer is a built-in device, whose conducting parts  
must be inaccessible after installation.  
A protective housing or additional shield could be used.  
Main supply must be able to be disconnected.  
Page 2/2  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.  
070110/4  
www.lem.com  

相关型号:

HTA1000-S

Current Transducer HTA 100~1000-S
LEM

HTA120F12IGT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120F22IBAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120F22ICT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120F27HCAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120F2YGHAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120F32GEAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120F3XICAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120FX2GAAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120FXXGHT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120FY2GDT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS

HTA120FYYICAT

Parallel - Fundamental Quartz Crystal, 12MHz Nom, HC-49/US-SM, 2 PIN
CTS