LA50-SP1 [LEM]

Current Transducer; 电流传感器
LA50-SP1
型号: LA50-SP1
厂家: LEM    LEM
描述:

Current Transducer
电流传感器

传感器
文件: 总3页 (文件大小:94K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Current Transducer LA 50-S/SP1  
IPN = 50 A  
For the electronic measurement of currents : DC, AC, pulsed...,  
with a galvanic isolation between the primary circuit (high power)  
and the secondary circuit (electronic circuit).  
0634  
Electrical data  
Features  
IPN  
IP  
RM  
Primary nominal r.m.s. current  
Primary current, measuring range  
Measuring resistance  
50  
A
A
· Closed loop (compensated) current  
transducer using the Hall effect  
· Insulated plastic case recognized  
according to UL 94-V0.  
0 .. ± 100  
RM min RMmax  
with ± 15 V  
@ ± 50 A max  
@ ± 100 A max  
0
0
330  
100  
W
W
ISN  
KN  
VC  
IC  
Secondary nominal r.m.s. current  
Conversion ratio  
Supply voltage (± 5 %)  
Current consumption  
25  
1 : 2000  
± 15  
mA  
Special features  
V
mA  
· IP  
= 0 .. ± 100 A  
10 + IS  
· KN = 1 : 2000  
Advantages  
Accuracy - Dynamic performance data  
· Excellent accuracy  
· Very good linearity  
X
Overall accuracy @ IPN, TA = 25°C  
Linearity error  
± 0.5  
< 0.1  
%
%
eG  
· Low temperature drift  
· Optimized response time  
· Wide frequency bandwidth  
· No insertion losses  
· High immunity to external  
interference  
L
Typ Max  
IO  
IOT  
Offset current @ IP = 0, TA = 25°C  
Thermal drift of IO  
± 0.1 mA  
- 10°C .. + 70°C  
± 0.2 ± 0.4 mA  
tr  
Response time 1) @ 90 % of IPN  
< 1  
> 50  
DC .. 150  
µs  
A/µs  
kHz  
· Current overload capability.  
di/dt di/dt accurately followed  
f
Frequency bandwidth (- 1 dB)  
Applications  
General data  
· AC variable speed drives and servo  
motor drives  
TA  
TS  
RS  
m
Ambient operating temperature  
Ambient storage temperature  
Secondary coil resistance @ TA = 70°C  
Mass  
- 10 .. + 70  
- 25 .. + 85  
130  
°C  
°C  
W
g
· Static converters for DC motor drives  
· Battery supplied applications  
· Uninterruptible Power Supplies  
(UPS)  
45  
Standards  
EN 50178 : 1997  
· Switched Mode Power Supplies  
(SMPS)  
· Power supplies for welding  
applications.  
Application domain  
· Industrial.  
1)  
Note :  
With a di/dt of 50 A/µs.  
060911/7  
Page 1/3  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.  
LEM  
www.lem.com  
Current Transducer LA 50-S/SP1....  
Isolation characteristics  
Vd  
Vw  
R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn  
Impulse withstand voltage 1.2/50 µs  
4
>7.4  
kV  
kV  
Min  
dCp  
dCl  
CTI  
Creepage distance  
Clearance distance  
Comparative Tracking Index (Group II)  
8.70  
7.40  
400  
m m  
m m  
Application examples  
According to EN 50178 and IEC 61010-1 standards and following conditions :  
· Over voltage category OV 3  
· Pollution degree PD2  
· Non-uniform field  
EN 50178  
Rated isolation voltage  
600 V  
IEC 61010-1  
Nominal voltage  
600 V  
VW  
dCp, dCI,  
Single isolation  
Reinforced isolation  
300 V  
300 V  
Safety  
This transducer must be used in electric/electronic equipment  
with respect to applicable standards and safety requirements  
in accordance with the manufacturer's operating instructions.  
Caution, risk of electrical shock  
When operating the transducer, certain parts of the module can  
carry hazardous voltage (eg. primary busbar, power supply).  
Ignoring this warning can lead to injury and/or cause serious  
damage.  
This transducer is a built-in device, whose conducting parts  
must be inaccessible after installation.  
A protective housing or additional shield could be used.  
Main supply must be able to be disconnected.  
060911/7  
Page 2/3  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.  
LEM  
www.lem.com  
Dimensions LA 50-S/SP1 (in mm. 1 mm = 0.0394 inch)  
Left view  
Front view  
Connection  
Rep.  
A-B  
Clearance  
7.40 mm  
Creepage  
8.70 mm  
Top view  
Mechanical characteristics  
Remarks  
· General tolerance  
· Transducer fastening  
± 0.2 mm  
· IS is positive when IP flows in the direction of the arrow.  
· Temperature of the primary conductor should not exceed  
100°C.  
· Dynamic performances (di/dt and response time) are best  
with a single bar completely filling the primary hole.  
· In order to achieve the best magnetic coupling, the primary  
windings have to be wound over the top edge of the device.  
· To measure nominal currents of less than 50 A, the optimum  
accuracy is obtained by having several primary turns (nomi-  
nal current x number of turns < 50 At).  
2 holes Æ 3.2 mm  
2 M3 steel screws  
1.1 Nm or 0.80 Lb.-Ft.  
12.7 x 6.35 mm  
Molex 5045-04/AG  
Recommended fastening torque  
· Primary through-hole  
· Connection of secondary  
060911/7  
Page 3/3  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.  
LEM  
www.lem.com  

相关型号:

LA50-S_06

Current Transducer
LEM

LA5000

2 to 5V 60mA Low Saturation Voltage Regulators
SANYO

LA5000M

2 TO 10V 60MA LOW SATURATION VOLTAGE REGULATORS
SANYO

LA5002

2 to 5V 60mA Low Saturation Voltage Regulators
SANYO

LA5002M

2 TO 10V 60MA LOW SATURATION VOLTAGE REGULATORS
SANYO

LA5003

2 to 5V 60mA Low Saturation Voltage Regulators
SANYO

LA5003M

2 TO 10V 60MA LOW SATURATION VOLTAGE REGULATORS
SANYO

LA5004

2 to 5V 60mA Low Saturation Voltage Regulators
SANYO

LA5004M

2 TO 10V 60MA LOW SATURATION VOLTAGE REGULATORS
SANYO

LA5005

2 to 5V 60mA Low Saturation Voltage Regulators
SANYO