LV100-2500 [LEM]

Voltage Transducer LV 100-2500; 电压传感器LV 100-2500
LV100-2500
型号: LV100-2500
厂家: LEM    LEM
描述:

Voltage Transducer LV 100-2500
电压传感器LV 100-2500

传感器
文件: 总2页 (文件大小:74K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Voltage Transducer LV 100-2500  
VPN = 2500 V  
For the electronic measurement of voltages : DC, AC, pulsed...,  
with a galvanic isolation between the primary circuit (high voltage)  
and the secondary circuit (electronic circuit).  
Electrical data  
VPN  
VP  
IPN  
Primary nominal r.m.s. voltage  
Primary voltage, measuring range  
Primary nominal r.m.s. current  
Measuring resistance  
2500  
0 .. ± 3750  
4
V
V
mA  
Features  
· Closed loop (compensated) voltage  
transducer using the Hall effect  
· Insulated plastic case recognized  
according to UL 94-V0  
· Primary resistor R 1 incorporated into  
the housing.  
RM  
RM min  
RM max  
with ± 15 V  
@ ± 2500 Vmax  
@ ± 3750 Vmax  
0
0
170  
90  
W
W
ISN  
KN  
VC  
IC  
Secondary nominal r.m.s. current  
Conversion ratio  
Supply voltage (± 5 %)  
Current consumption  
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn  
50  
mA  
2500 V / 50 mA  
± 15  
10 + IS  
9
V
mA  
kV  
Advantages  
Vd  
· Excellent accuracy  
· Very good linearity  
· Low thermal drift  
· High immunity to external  
interference.  
Accuracy - Dynamic performance data  
XG  
Overall Accuracy @ VPN , TA = 25°C  
Linearity  
± 0.7  
< 0.1  
%
%
e
L
Applications  
Typ  
Max  
± 0.2 mA  
± 0.2 ± 0.3 mA  
IO  
IOT  
Offset current @ IP = 0, TA = 25°C  
Thermal drift of IO  
· AC variable speed drives and servo  
motor drives  
0°C .. + 70°C  
tr  
Response time @ 90 % of VP max  
170  
µs  
· Static converters for DC motor drives  
· Uninterruptible Power Supplies  
(UPS)  
· Power supplies for welding  
applications.  
General data  
TA  
TS  
N
Ambient operating temperature  
Ambient storage temperature  
Turns ratio  
0 .. + 70  
- 25 .. + 85  
25000 : 2000  
10  
625  
60  
°C  
°C  
P
Total primary power loss  
Primary resistance @ TA = 25°C  
Secondary coil resistance @ TA = 70°C  
Mass  
W
kW  
W
R1  
RS  
m
850  
EN 50178  
g
1)  
Standards  
1)  
Note :  
A list of corresponding tests is available  
981102/2  
LEM Components  
www.lem.com  
Dimensions LV 100-2500 (in mm. 1 mm = 0.0394 inch)  
Front view  
Left view  
Secondary terminals  
Terminal + : supply voltage +15 V  
Terminal M : measure  
Terminal  
Terminal  
-
: supply voltage - 15 V  
: ground or earth  
Connection  
Top view  
Mechanical characteristics  
Remarks  
· General tolerance  
· Fastening  
· Connection of primary  
· Connection of secondary  
· Connection to the ground  
· Fastening torque  
± 0.3 mm  
· IS is positive when VP is applied on terminal +HT.  
· The primary circuit of the transducer must be linked to the  
connections where the voltage has to be measured.  
· This is a standard model. For different versions (supply  
voltages, turns ratios, unidirectional measurements...),  
please contact us.  
2 holes Æ 6.5 mm  
M5 threaded studs  
Faston 6.3 x 0.8 mm  
M5 threaded stud  
2.2 Nm or 1.62 Lb. -Ft.  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.  

相关型号:

LV100-2500_03

Voltage Transducer
LEM

LV100-250_03

Voltage Transducer
LEM

LV100-300

Voltage Transducer LV 100-300
LEM

LV100-3000

Voltage Transducer LV 100-3000
LEM

LV100-3000_03

Voltage Transducer
LEM

LV100-300_03

Voltage Transducer
LEM

LV100-3500

Voltage Transducer LV 100-3500
LEM

LV100-3500_03

LV100-3500
LEM

LV100-400

Voltage Transducer LV 100-400
LEM

LV100-4000

Voltage Transducer LV 100-4000
LEM

LV100-4000_03

Voltage Transducer
LEM

LV100-400_03

Voltage Transducer
LEM