LV100-2500 [LEM]
Voltage Transducer LV 100-2500; 电压传感器LV 100-2500型号: | LV100-2500 |
厂家: | LEM |
描述: | Voltage Transducer LV 100-2500 |
文件: | 总2页 (文件大小:74K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Voltage Transducer LV 100-2500
VPN = 2500 V
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
Electrical data
VPN
VP
IPN
Primary nominal r.m.s. voltage
Primary voltage, measuring range
Primary nominal r.m.s. current
Measuring resistance
2500
0 .. ± 3750
4
V
V
mA
Features
· Closed loop (compensated) voltage
transducer using the Hall effect
· Insulated plastic case recognized
according to UL 94-V0
· Primary resistor R 1 incorporated into
the housing.
RM
RM min
RM max
with ± 15 V
@ ± 2500 Vmax
@ ± 3750 Vmax
0
0
170
90
W
W
ISN
KN
VC
IC
Secondary nominal r.m.s. current
Conversion ratio
Supply voltage (± 5 %)
Current consumption
R.m.s. voltage for AC isolation test, 50 Hz, 1 mn
50
mA
2500 V / 50 mA
± 15
10 + IS
9
V
mA
kV
Advantages
Vd
· Excellent accuracy
· Very good linearity
· Low thermal drift
· High immunity to external
interference.
Accuracy - Dynamic performance data
XG
Overall Accuracy @ VPN , TA = 25°C
Linearity
± 0.7
< 0.1
%
%
e
L
Applications
Typ
Max
± 0.2 mA
± 0.2 ± 0.3 mA
IO
IOT
Offset current @ IP = 0, TA = 25°C
Thermal drift of IO
· AC variable speed drives and servo
motor drives
0°C .. + 70°C
tr
Response time @ 90 % of VP max
170
µs
· Static converters for DC motor drives
· Uninterruptible Power Supplies
(UPS)
· Power supplies for welding
applications.
General data
TA
TS
N
Ambient operating temperature
Ambient storage temperature
Turns ratio
0 .. + 70
- 25 .. + 85
25000 : 2000
10
625
60
°C
°C
P
Total primary power loss
Primary resistance @ TA = 25°C
Secondary coil resistance @ TA = 70°C
Mass
W
kW
W
R1
RS
m
850
EN 50178
g
1)
Standards
1)
Note :
A list of corresponding tests is available
981102/2
LEM Components
www.lem.com
Dimensions LV 100-2500 (in mm. 1 mm = 0.0394 inch)
Front view
Left view
Secondary terminals
Terminal + : supply voltage +15 V
Terminal M : measure
Terminal
Terminal
-
: supply voltage - 15 V
: ground or earth
Connection
Top view
Mechanical characteristics
Remarks
· General tolerance
· Fastening
· Connection of primary
· Connection of secondary
· Connection to the ground
· Fastening torque
± 0.3 mm
· IS is positive when VP is applied on terminal +HT.
· The primary circuit of the transducer must be linked to the
connections where the voltage has to be measured.
· This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
2 holes Æ 6.5 mm
M5 threaded studs
Faston 6.3 x 0.8 mm
M5 threaded stud
2.2 Nm or 1.62 Lb. -Ft.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
相关型号: