CP2000AC54PE [LINEAGEPOWER]
Compact Power Line Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W; 紧凑型电源线输入: 100-120 / 200-240伏交流;输出: ± 54伏在2000W ; 5 VDC在4W型号: | CP2000AC54PE |
厂家: | LINEAGE POWER CORPORATION |
描述: | Compact Power Line Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W |
文件: | 总8页 (文件大小:264K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Data Sheet
August 2009
Compact Power Line
CP2000AC54 Front-End Power Supply
Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
Features
• Compact 1-RU form factor providing 20 W/in3
• Constant power from 52 – 58 Vdc
• 2000W from nominal 200 – 240 Vac
• 1200W from nominal 100 – 120 Vac
• Output voltage programmable from 44V – 58 Vdc;
output defaulted to 54V
• PMBus compliant dual I2C and RS485 serial bus
communications
• Power factor correction (meets EN/IEC 61000-3-2
and EN 60555-2 requirements)
Applications
• 48Vdc distributed power architectures
• Power over Ethernet
• Tested to IEEE802.3 Compliance, 2250 output***
isolation to chassis/signals for POE applications.
(see ordering info)
• Routers/Switches
• VoIP/Soft Switches
• LAN/WAN/MAN applications
• File servers
• Indoor wireless
• Telecommunications equipment
• Enterprise Networks
• SAN/NAS/iSCSI applications
• Advanced workstations
• DC Output over-voltage and over-current
protection
• AC Input over-voltage and under-voltage protection
• Over-temperature warning and protection
• Redundant, parallel operation with active load
sharing and redundant +5V Aux power
• Remote ON/OFF
• Hot insertion/removal (hot plug)
• Four front panel LED indicators
• UL* Recognized to UL60950-1, CAN/ CSA† C22.2
No. 60950-1, and VDE‡ 0805-1 Licensed to
IEC60950-1
• CE mark meets 2006/95/EC directive§
• Internal variable-speed fan control
The CP2000AC54 Front-End Power Supplies in the Compact Power Line platform are specifically
designed to operate as an integral part of a complete distributed power system. The high-density, front-to-
back airflow rectifier is designed for minimal space utilization and is highly expandable for future growth. It
is provided with many features including PoE isolation, RS485 and dual-redundant I2C communications
busses that allow it to be used in a broad range of applications. The flexible feature set makes this front-
end power supply an excellent choice for applications requiring modular ac-to-dc bulk intermediate
voltages, such as in distributed power.
*
UL is a registered trademark of Underwriters Laboratories, Inc.
†
‡
§
CSA is a registered trademark of Canadian Standards Association.
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user
equipment should be followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards.
*** For PoE applications, order the CP2000AC54PEZ, which is 100% factory hipot-tested per IEEE802.3.
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications
Input
Parameter
Min
Typ
Max
Units
Notes
Startup Input Voltage
1200W Operation
2000W Operation
The power supply automatically configures its
operating mode based on the voltage level it
reads on first turn ON. (This information is
retained as long as internal bias is maintained.)
85
175
Operating Voltage Range
1200W Configuration
2000W Configuration
2000W Configuration
85
175
150
120/200/240
200/240
275
275
175
If started within low input line range.
If started within high input line range.
Will derate to 80% of full load; will shutdown
below 150Vac.
Vac
Permitted Excursions
275
300
May not meet all requirements, but will
maintain output regulation.
Surges
300
47
325
63
May shut down but will not get damaged.
Input Frequency
Hz
A
13.3
11.2
11.8
9.9
At 100 Vac
At 120 Vac
At 200 Vac
At 240 Vac
Input Current
Measured at 25°C for all line conditions; does
not include X-Capacitors charging.
Inrush Transient
25
35
Apk
mA
Input Leakage Current
Power Factor
1.5
Measured at 265Vac, 60Hz
From 50% to 100% load.
0.98
85
88
90
93
At 100 Vac with Vout > 52V and Pout > 50%.
At 230 Vac with Vout > 52V and Pout > 50%.
Efficiency
%
Measurement starts at zero crossing of the ac
voltage. Alarm issued via PFW signal going LO
5 ms prior to output voltages going out of limits.
Measurements made at 65% full load and
voltage allowed to decay to 49.5V.
Holdup Time
15
20
ms
For loads below 1200W.
Main Output
Parameter
Min
Typ
Max
Units
Notes
Maximum Output Power
1200
2000
At low-line input from 100-120Vac nominal.
At high-line input from 200-240Vac nominal.
W
Output Voltage Setpoint
Setpoint Accuracy
54
Vdc
%
Output floats with respect to frame ground.
-1
-2
+1
+2
Overall Regulation
Includes all variations due to specified load
range, drift, and environmental conditions.
%
Output Voltage Margin
44
42
58
58
Vdc
Vdc
Configured by hardware setting.
Set either by I2C or RS485
Maximum Output Current
Current Share
23
38.5
At 1200W, 52V and 100-120Vac.
At 2000W, 52V and 200-240Vac.
A
Maintains tolerance to the average of all other
rectifiers. Loads > 25%FL
10
%FL
Lineage Power
2
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Output (continued)
Parameter
Min
Typ
Max
Units
Notes
Output Ripple
RMS (5Hz to 20MHz)
Peak-to-Peak (5Hz to 20MHz)
Psophometric Noise
250
500
2
mVrms
Measured with 20MHz bandwidth under any
mVpk-pk condition of loading. Minimum load is 1A.
mVrms
External Bulk Load Capacitance
External capacitance can be increased but the
0
5,000
power supply will not meet its turn-ON rise time
requirement.
µF
Turn-On
Delay
Monotonic Turn_On from 30% to 100% of Vnom
above -5°C operation. Monotonic Turn_On from
60% to 100% of Vnom below -5°C operation.
5
100
5
s
ms
s
Rise Time1 - Standard (PMBus)
-Telecom (RS-485)2
Overshoot
2
%
Load Step Response
∆I
∆I/∆t slew rate 1A/µs.
Settling time to within regulation requirements.
50
%FL
Vdc
ms
2.0
2
∆V
Response Time
Overload
Power Limit
2000
102
W
%FL
Down to -52Vdc
Hiccup current limit. (FL = 38.5A)
Current Limit Inception3
108
Over-voltage
Delayed
Immediate
Latchoff
60
65
Vdc
Vdc
200msec delayed shutdown to be implemented.
Instantaneous shutdown above this point.
Three restart attempts may be implemented within a one minute window prior to a latched
shutdown
Over-temperature
Warning
5
°C
°C
Implemented prior to commencement of an OT
shutdown
Below the maximum rating of the device being
protected
Shutdown
20
Auto-recoverable
Temperature hysteresis of approximately 10°C provided between shutdown and restart.
1. Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors.
2. Complies with GR947 which calls for a minimum rise time proportional to output load.
3. Fold-down current limit is programmed as a default to permit system start-up when units are plugged in one at a time. Latch-
off mode current limit can be activated via an I2c command.
Auxiliary Output
Parameter
Min
Typ
Max
Units
Vdc
A
Notes
Output Voltage Setpoint
Output Current
5
0.005
-5
0.75
+10
100
7
Overall Regulation
Ripple and Noise
Over-voltage Clamp
Over-current Limit
%
50
mVpk-pk 20MHz bandwidth
Vdc
110
175
%FL
Physical
Length (in./mm)
Width (in./mm)
Height (in./mm)
Weight (lb/kg)
13.85 / 351.8
4.00 / 101.6
1.66 / 42.2
4.6 / 2.1
Lineage Power
3
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Specifications (continued)
Environmental
Parameter
Min
Typ
Max
Units
Notes
Ambient Temperature
Operating
-51
45
°C
°C
%/°C
%/°C
Air inlet from sea level to 5,000 feet.
Per 1,000 feet above 5,000 feet.
Up to 55°C
Ambient Derating
1
Power Derating2
1
2
From 55 to 75 °C
Storage Temperature
Humidity
-40
5
85
95
°C
%
Relative humidity, non-condensing
Shock and Vibration
Operational Test
Test Levels
IEC 68-2
IEC 721-3-2
IEC 68-2-31
Drop and Tip Over
Per Telcordia GR-63-CORE, all floors, when
installed in CP Shelf.
Earthquake Rating
Acoustic Noise
4
Zone
Noise is proportional to fan speed, load and
ambient temperature.
45
dBA
Harmonic Emissions
Radiated Emissions4
Conducted Emissions - ac
Per EN/IEC61000-3-2
FCC and CISPR22 (EN55022) - Class B3
FCC and CISPR22 (EN55022) Class B
Telcordia GR-1089-CORE - Class A
Conducted Emissions - dc
ESD
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A
Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge).
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).
Radiated Immunity
Electrical Fast Transient Burst
Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate)
Lightning Surge
Error Free
EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode).
ANSI C62.41 Level A3 (6 kV common and differential mode)
Damage Free
Conducted Immunity
Reliability (calculated)
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).
At ambient of 25°C at full load per Telcordia SR-
400,000
Hours
332, Reliability Prediction for Electronic Equipment,
Method I Case III.
Isolation
Input-Chassis/Signals
Input - Output
Output-Chassis/Signals
1500
3000
2250
Vrms
Vrms
Vdc
Per EN60950-1.
Consult factory for testing to this requirement
Per IEEE802.3.
Service Life
10
Years
25°C ambient, full load excluding fans.
1. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C.
2. Power derating shall consider only temperature variations at nominal line (100 – 120, 200 – 240Vrms). The unit may derate
faster if the input line is below nominal.
3. Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the
cable. See the figure below.
4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode
capacitors that assist in meeting compliance.
Lineage Power
4
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Module Present Signal: This signal has dual
functionality. It can be used to alert the system
when a module is inserted. Has a 500Ω resistor in
series between this signal and Logic GRD. An
external pull-up should not raise the voltage on the
pin above 0.25Vdc. If raised the pin is raised to
5Vdc the write_protect feature of the EEPROM is
enabled.
Status and Control
The rectifier provides three means for
monitor/control: analog, PMBus compliant I2C, or
RS485 for interfacing to Lineage Power controllers
or battery plants.
Details of analog controls are provided in this data
sheet under Signal Definitions. Lineage Power will
provide separate application notes on PMBus
protocol for users to interface to the CPL rectifiers.
Contact your local Lineage Power representative
for details.
Protocol Select: Establishes the communications
mode of the power supply, between analog/I2C and
RS485 modes. For RS485, connect 750 – 3.92kΩ
pull-down resistor to 54_OUT(-DC).
Hot Plug
Enable: On/Off control when either PMBus
When rapidly extracting and reinserting modules
care should be taken to allow for discharging the
internal bias supply so that a predictable restart
could be achieved. The way to ensure that the
circuit sufficiently discharges is to observe the
spinning of the fans after an extraction. The unit
should not be reinserted until the fans stop
spinning.
communications or analog functions are utilized as
configured by the Protocol pin. This pin must be
pulled low to turn ON the main output of the power
supply. The power supply will turn OFF if either the
Enable or the ON/OFF pin is released. The Enable
function does not work with the RS-485 protocol.
This signal is referenced to Logic_GRD.
ON/OFF: This is a short pin utilized for hot-plug
applications to ensure that the power supply turns
OFF before the power pins are disengaged. It also
ensures that the power supply turns ON only after
the power pins have been engaged. Must be
connected to 54_OUT (-DC).
Control Definitions
All signals are referenced to Logic GRD unless
otherwise noted. See the Signal Definitions Table
at the end of this document for further description
of all the signals.
Input Signals
Output Signals
Margining: Setpoint of the rectifier can be changed
via this input pin. Programming can be either a
voltage source or a resistance divider. The
margining pin is connected to 3.3Vdc via a 10kΩ
resistor inside the rectifier. See graphs below.
Alert #: PMBus interrupt signal.
Fault: This signal goes LO for any failure that
requires rectifier replacement. Some of these faults
may be due to:
• Fan failure
• Over-temperature condition
• Over-temperature shutdown
• Over-voltage shutdown
• Internal Rectifier Fault
Power Capacity: A HI on this pin indicates rectifier
configured for 2000W operation; a LO indicates
rectifier configured for 1200W operation.
An open circuit on this pin reverts the voltage level
back to the original setting.
Lineage Power
5
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Alarm Table
Monitoring Signals
Power Supply LED State
(Referenced to Logic_GRD)
AC OK
Green
DC OK
Green
Service
Amber
Fault
Red
Module
Present
Condition
Fault
OTW
PFW
OK
1
1
0
0
HI
HI
HI
LO
Thermal Alarm
(5C before shutdown)
1
1
1
0
HI
LO
HI
LO
Thermal Shutdown
1
0
1
0
0
0
0
0
0
0
0
0
1
1
1
0
0
0
1
1
0
1
LO
LO
LO
HI
LO
HI
HI
HI
HI
HI
HI
HI
HI
HI
LO
LO
LO
LO3
LO
LO
LO
LO
LO
HI
LO
LO
LO
LO
LO
LO
LO
LO
LO
LO
HI
Defective Fan
1
0
Blown AC Fuse in Unit
No AC <15mS (single unit)
AC Present but not within limits
AC not present1
1
0
0
1
Blinks
0
HI
0
1
1
1
1
0
HI
Boost Stage Failure
0
0
LO
LO
HI
Over Voltage Latched Shutdown
Over Current
Blinks
1
Non-catastrophic Internal Failure2
1 Missing Module
LO
Standby (remote)
1
1
1
0
1
1
0
Blinks
0
0
0
HI
HI
HI
HI
HI
HI
LO
HI
LO
LO
LO
Service Request (PMBus mode)
Communications Fault (RS485 mode)
Blinks
HI
1
This signal is correct if the rectifier is back biased from other rectifiers in the shelf .
2 Any detectable fault condition that does not result in the power supply shutting down. For example, ORing FET failure, boost
section out of regulation, etc.
3
Signal transition from HI to LO is output load dependent
Output Connector
Mating Connector: AMP 1450572-1
A1
A6
P1
P7
Signal
Output Power
Input Power
P3
6
5
4
3
2
1
P7
P6
P5
P4
P2
P1
SCL_0 MOD_PRES PFW
LOGIC_GRD RS_485+ UNIT_ADDR
A
B
C
D
SCL_1 OTW
SDA_0 Margin
SDA_1 Fault
Alert#_0 Alert#_1
Enable Reset
5VA Power_Cap
RS_485-
Ishare
8V_INT
54_OUT 54_OUT
(-DC) (+DC)
EARTH LINE-2 LINE-1
(GND) (Neutral) (Line)
Reserved
Protocol
ON/OFF
SHELF_ADDR
Connector is viewed from the rear positioned inside the power supply.
Signal pins columns 1 and 2 are referenced to 54_OUT (-DC).
Signal pins columns 3 through 6 are referenced to Logic GRD.
Last-to-make first-to-break pins.
First-to-make last-to-break longest pin implemented in the mating connector.
Lineage Power
6
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Signal Definitions
All hardware alarm signals (Fault, PFW, OTW, Power Capacity) are open drain FETs. These signals
should be pulled HI to either 3.3V or 5V. Maximum sink current 5mA. An active LO signal (< 0.4Vdc). All
signals are referenced to Logic GRD unless otherwise stated. Contact your Lineage Power representative
for more details.
Function
Label
Enable
Type
Input
Description
Output Enable
If shorted to LOGIC_GRD, the rectifier output is enabled
when using I2C mode of operation. May also be toggled to
reset a latched OFF rectifier. Function not available in
RS485 mode.
Power Fail Warning
I2C Interrupt
PFW
Output
Output
An open drain FET; normally HI, indicating output power is
present. Changes to LO at least 5msec before the output
voltage is lost.
Interrupt signal via I2C lines indicating that service is
requested from the host controller. This signal pin is pulled
up to 3.3V via a 10kΩ resistor and switches to active LO
when an interrupt occurs.
Alert#_0
Alert#_1
Rectifier Fault
Module Present
ON/OFF
Fault
Output
Output
Input
Indicates that an internal fault exists. An open drain FET;
normally HI, changes to LO.
MOD_PRES
ON/OFF
Short pin, see Status and Control description for further
information on this signal.
Short pin, connects last and breaks first; used to activate
and deactivate output during hot-insertion and extraction,
respectively. Ref: 54_OUT (-DC)
Protocol select
Margining
Protocol
Margin
Input
See Status and Control description for further information
on this signal. Ref: 54_OUT (-DC).
Input
Allows changing of output voltage through an analog
voltage input or via resistor divider.
Over-Temperature Warning OTW
Output
An open drain FET; normally HI, changes to LO
approximately 5°C prior to thermal shutdown.
Power Capacity
POWER_CAP Output
An open drain FET; Used to indicate rectifier operation
mode; HI indicates 2000W operation and LO indicates
1200W operation.
Rectifier address
Shelf Address
Back bias
Unit_addr
Shelf_addr
8V_INT
Input
Input
_
Voltage level addressing of rectifiers within a single shelf.
Ref: 54_OUT (-DC).
Voltage level addressing of rectifiers within multiple
shelves. Ref: 54_OUT (-DC).
Diode OR’ed 8Vdc drain; used to back bias
microprocessors and DSP of failed rectifier from operating
rectifiers. Ref: 54_OUT (-DC).
Mux Reset
Reset
5VA
Input
Resets the I2C lines to I2C line 0.
Standby power
Output
5V at 0.75A provided for external use by either adjacent
power supplies or the using system.
Current Share
Ishare
-
A single wire interface between each of the power unit
forces them to share the load current. Ref: 54_OUT (-DC).
I2C Line 0
I2C Line 1
RS485 Line
SCL_0, SDA_0 Input
SCL_1, SDA_1 Input
I2C line 0.
I2C line 1.
RS485 line.
RS_485+
RS_485-
Input
Lineage Power
7
Data Sheet
Compact Power Line
CP2000AC54 Front-End Power Supply
Front Panel LEDs
Analog Mode
I2C Mode
ON: Input ok
RS485 Mode
Blinking: Input out of limits
ON: Output ok
Blinking: Overload
ON: Over-temperature
ON: Over-temperature Warning
Blinking: Service
ON: Over-temperature
Warning
Warning
ON: Fault
Blinking: Not communicating
ON: Fault
!
Dimensions
13.85 in.
(351.8 mm)
Rear View
4.00 in.
(101.6 mm)
1.70 in.
(43.2 mm)
Front View
Top View
Ordering Information
Item
Description
Comcode
CP2000AC54PE
CP2000AC54PEZ
Designed to IEEE802.3 POE compliance, RoHS 5/6
Tested to IEEE802.3 POE compliance, RoHS 6/6
CC109120722
CC109139408
Asia-Pacific Headquarters
Tel: +65 6593 7211
Europe, Middle-East and Africa Headquarters
World Wide Headquarters
Lineage Power LLC
Tel: +49 898 780 672 80
601 Shiloh Road, Plano, TX 75074, USA
+1-800-526-7819
India Headquarters
Tel: +91 80 2841 1633
(Outside U.S.A.: +1-972-284-2626)
www.lineagepower.com
e-mail: techsupport1@lineagepower.com
Lineage Power reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or
application. No rights under any patent accompany the sale of any such product(s) or information.
© 2009 Lineage Power LLC, (Mesquite, Texas) All International Rights Reserved.
Revision : GGS-August 2009
Lineage Power
Page 8
相关型号:
CP2000AC54SD
Compact Power Line Input: 200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
LINEAGEPOWER
CP2000DC54
Compact Power Line Input: -40 to -72 Vdc; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
LINEAGEPOWER
CP2001-7RB1
DC-DC Regulated Power Supply Module, 2 Output, 182W, Hybrid, METAL, CASE P01, MODULE
BEL