Data Sheet  
August 2009  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Input: 100-120/200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W  
Features  
Compact 1-RU form factor providing 20 W/in3  
Constant power from 52 – 58 Vdc  
2000W from nominal 200 – 240 Vac  
1200W from nominal 100 – 120 Vac  
Output voltage programmable from 44V – 58 Vdc;  
output defaulted to 54V  
PMBus compliant dual I2C and RS485 serial bus  
communications  
Power factor correction (meets EN/IEC 61000-3-2  
and EN 60555-2 requirements)  
Applications  
48Vdc distributed power architectures  
Power over Ethernet  
Tested to IEEE802.3 Compliance, 2250 output***  
isolation to chassis/signals for POE applications.  
(see ordering info)  
Routers/Switches  
VoIP/Soft Switches  
LAN/WAN/MAN applications  
File servers  
Indoor wireless  
Telecommunications equipment  
Enterprise Networks  
SAN/NAS/iSCSI applications  
Advanced workstations  
DC Output over-voltage and over-current  
protection  
AC Input over-voltage and under-voltage protection  
Over-temperature warning and protection  
Redundant, parallel operation with active load  
sharing and redundant +5V Aux power  
Remote ON/OFF  
Hot insertion/removal (hot plug)  
Four front panel LED indicators  
UL* Recognized to UL60950-1, CAN/ CSAC22.2  
No. 60950-1, and VDE0805-1 Licensed to  
IEC60950-1  
CE mark meets 2006/95/EC directive§  
Internal variable-speed fan control  
The CP2000AC54 Front-End Power Supplies in the Compact Power Line platform are specifically  
designed to operate as an integral part of a complete distributed power system. The high-density, front-to-  
back airflow rectifier is designed for minimal space utilization and is highly expandable for future growth. It  
is provided with many features including PoE isolation, RS485 and dual-redundant I2C communications  
busses that allow it to be used in a broad range of applications. The flexible feature set makes this front-  
end power supply an excellent choice for applications requiring modular ac-to-dc bulk intermediate  
voltages, such as in distributed power.  
*
UL is a registered trademark of Underwriters Laboratories, Inc.  
§
CSA is a registered trademark of Canadian Standards Association.  
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.  
This product is intended for integration into end-user equipment. All the required procedures for CE marking of end-user  
equipment should be followed. (The CE mark is placed on selected products.)  
** ISO is a registered trademark of the International Organization of Standards.  
*** For PoE applications, order the CP2000AC54PEZ, which is 100% factory hipot-tested per IEEE802.3.  
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Specifications  
Input  
Parameter  
Min  
Typ  
Max  
Units  
Notes  
Startup Input Voltage  
1200W Operation  
2000W Operation  
The power supply automatically configures its  
operating mode based on the voltage level it  
reads on first turn ON. (This information is  
retained as long as internal bias is maintained.)  
85  
175  
Operating Voltage Range  
1200W Configuration  
2000W Configuration  
2000W Configuration  
85  
175  
150  
120/200/240  
200/240  
275  
275  
175  
If started within low input line range.  
If started within high input line range.  
Will derate to 80% of full load; will shutdown  
below 150Vac.  
Vac  
Permitted Excursions  
275  
300  
May not meet all requirements, but will  
maintain output regulation.  
Surges  
300  
47  
325  
63  
May shut down but will not get damaged.  
Input Frequency  
Hz  
A
13.3  
11.2  
11.8  
9.9  
At 100 Vac  
At 120 Vac  
At 200 Vac  
At 240 Vac  
Input Current  
Measured at 25°C for all line conditions; does  
not include X-Capacitors charging.  
Inrush Transient  
25  
35  
Apk  
mA  
Input Leakage Current  
Power Factor  
1.5  
Measured at 265Vac, 60Hz  
From 50% to 100% load.  
0.98  
85  
88  
90  
93  
At 100 Vac with Vout > 52V and Pout > 50%.  
At 230 Vac with Vout > 52V and Pout > 50%.  
Efficiency  
%
Measurement starts at zero crossing of the ac  
voltage. Alarm issued via PFW signal going LO  
5 ms prior to output voltages going out of limits.  
Measurements made at 65% full load and  
voltage allowed to decay to 49.5V.  
Holdup Time  
15  
20  
ms  
For loads below 1200W.  
Main Output  
Parameter  
Min  
Typ  
Max  
Units  
Notes  
Maximum Output Power  
1200  
2000  
At low-line input from 100-120Vac nominal.  
At high-line input from 200-240Vac nominal.  
W
Output Voltage Setpoint  
Setpoint Accuracy  
54  
Vdc  
%
Output floats with respect to frame ground.  
-1  
-2  
+1  
+2  
Overall Regulation  
Includes all variations due to specified load  
range, drift, and environmental conditions.  
%
Output Voltage Margin  
44  
42  
58  
58  
Vdc  
Vdc  
Configured by hardware setting.  
Set either by I2C or RS485  
Maximum Output Current  
Current Share  
23  
38.5  
At 1200W, 52V and 100-120Vac.  
At 2000W, 52V and 200-240Vac.  
A
Maintains tolerance to the average of all other  
rectifiers. Loads > 25%FL  
10  
%FL  
Lineage Power  
2
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Specifications (continued)  
Output (continued)  
Parameter  
Min  
Typ  
Max  
Units  
Notes  
Output Ripple  
RMS (5Hz to 20MHz)  
Peak-to-Peak (5Hz to 20MHz)  
Psophometric Noise  
250  
500  
2
mVrms  
Measured with 20MHz bandwidth under any  
mVpk-pk condition of loading. Minimum load is 1A.  
mVrms  
External Bulk Load Capacitance  
External capacitance can be increased but the  
0
5,000  
power supply will not meet its turn-ON rise time  
requirement.  
µF  
Turn-On  
Delay  
Monotonic Turn_On from 30% to 100% of Vnom  
above -5°C operation. Monotonic Turn_On from  
60% to 100% of Vnom below -5°C operation.  
5
100  
5
s
ms  
s
Rise Time1 - Standard (PMBus)  
-Telecom (RS-485)2  
Overshoot  
2
%
Load Step Response  
I  
I/t slew rate 1A/µs.  
Settling time to within regulation requirements.  
50  
%FL  
Vdc  
ms  
2.0  
2
V  
Response Time  
Overload  
Power Limit  
2000  
102  
W
%FL  
Down to -52Vdc  
Hiccup current limit. (FL = 38.5A)  
Current Limit Inception3  
108  
Over-voltage  
Delayed  
Immediate  
Latchoff  
60  
65  
Vdc  
Vdc  
200msec delayed shutdown to be implemented.  
Instantaneous shutdown above this point.  
Three restart attempts may be implemented within a one minute window prior to a latched  
shutdown  
Over-temperature  
Warning  
5
°C  
°C  
Implemented prior to commencement of an OT  
shutdown  
Below the maximum rating of the device being  
protected  
Shutdown  
20  
Auto-recoverable  
Temperature hysteresis of approximately 10°C provided between shutdown and restart.  
1. Below -5°C, the rise time is approximately 5 minutes to protect the bulk capacitors.  
2. Complies with GR947 which calls for a minimum rise time proportional to output load.  
3. Fold-down current limit is programmed as a default to permit system start-up when units are plugged in one at a time. Latch-  
off mode current limit can be activated via an I2c command.  
Auxiliary Output  
Parameter  
Min  
Typ  
Max  
Units  
Vdc  
A
Notes  
Output Voltage Setpoint  
Output Current  
5
0.005  
-5  
0.75  
+10  
100  
7
Overall Regulation  
Ripple and Noise  
Over-voltage Clamp  
Over-current Limit  
%
50  
mVpk-pk 20MHz bandwidth  
Vdc  
110  
175  
%FL  
Physical  
Length (in./mm)  
Width (in./mm)  
Height (in./mm)  
Weight (lb/kg)  
13.85 / 351.8  
4.00 / 101.6  
1.66 / 42.2  
4.6 / 2.1  
Lineage Power  
3
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Specifications (continued)  
Environmental  
Parameter  
Min  
Typ  
Max  
Units  
Notes  
Ambient Temperature  
Operating  
-51  
45  
°C  
°C  
%/°C  
%/°C  
Air inlet from sea level to 5,000 feet.  
Per 1,000 feet above 5,000 feet.  
Up to 55°C  
Ambient Derating  
1
Power Derating2  
1
2
From 55 to 75 °C  
Storage Temperature  
Humidity  
-40  
5
85  
95  
°C  
%
Relative humidity, non-condensing  
Shock and Vibration  
Operational Test  
Test Levels  
IEC 68-2  
IEC 721-3-2  
IEC 68-2-31  
Drop and Tip Over  
Per Telcordia GR-63-CORE, all floors, when  
installed in CP Shelf.  
Earthquake Rating  
Acoustic Noise  
4
Zone  
Noise is proportional to fan speed, load and  
ambient temperature.  
45  
dBA  
Harmonic Emissions  
Radiated Emissions4  
Conducted Emissions - ac  
Per EN/IEC61000-3-2  
FCC and CISPR22 (EN55022) - Class B3  
FCC and CISPR22 (EN55022) Class B  
Telcordia GR-1089-CORE - Class A  
Conducted Emissions - dc  
ESD  
Telcordia GR-1089-CORE and CISPR22 (EN55022) - Class A  
Error free per EN/IEC 61000-4-2 Level 4 (8 kV contact discharge, 15 kV air discharge).  
Error free per EN/IEC 61000-4-3 Level 3 (10 V/m).  
Radiated Immunity  
Electrical Fast Transient Burst  
Error free per EN/IEC 61000-4-4 Level 3 (2 kV, 5 kHz repetition rate)  
Lightning Surge  
Error Free  
EN/IEC61000-4-5 Level 4 (4 kV common mode, 2 kV differential mode).  
ANSI C62.41 Level A3 (6 kV common and differential mode)  
Damage Free  
Conducted Immunity  
Reliability (calculated)  
Error free per EN/IEC 61000-4-6 Level 3 (10Vrms).  
At ambient of 25°C at full load per Telcordia SR-  
400,000  
Hours  
332, Reliability Prediction for Electronic Equipment,  
Method I Case III.  
Isolation  
Input-Chassis/Signals  
Input - Output  
Output-Chassis/Signals  
1500  
3000  
2250  
Vrms  
Vrms  
Vdc  
Per EN60950-1.  
Consult factory for testing to this requirement  
Per IEEE802.3.  
Service Life  
10  
Years  
25°C ambient, full load excluding fans.  
1. Designed to start at an ambient as low as -40°C, but may not meet operational limits until above -5°C.  
2. Power derating shall consider only temperature variations at nominal line (100 – 120, 200 – 240Vrms). The unit may derate  
faster if the input line is below nominal.  
3. Class B radiated emmissions compliance requires the addition of a ferrite bead to each power line cord at the shelf-end of the  
cable. See the figure below.  
4. Radiated emissions compliance was met using a Lineage Power shelf. This shelf includes output common and differential mode  
capacitors that assist in meeting compliance.  
Lineage Power  
4
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Module Present Signal: This signal has dual  
functionality. It can be used to alert the system  
when a module is inserted. Has a 500resistor in  
series between this signal and Logic GRD. An  
external pull-up should not raise the voltage on the  
pin above 0.25Vdc. If raised the pin is raised to  
5Vdc the write_protect feature of the EEPROM is  
enabled.  
Status and Control  
The rectifier provides three means for  
monitor/control: analog, PMBus compliant I2C, or  
RS485 for interfacing to Lineage Power controllers  
or battery plants.  
Details of analog controls are provided in this data  
sheet under Signal Definitions. Lineage Power will  
provide separate application notes on PMBus  
protocol for users to interface to the CPL rectifiers.  
Contact your local Lineage Power representative  
for details.  
Protocol Select: Establishes the communications  
mode of the power supply, between analog/I2C and  
RS485 modes. For RS485, connect 750 – 3.92k  
pull-down resistor to 54_OUT(-DC).  
Hot Plug  
Enable: On/Off control when either PMBus  
When rapidly extracting and reinserting modules  
care should be taken to allow for discharging the  
internal bias supply so that a predictable restart  
could be achieved. The way to ensure that the  
circuit sufficiently discharges is to observe the  
spinning of the fans after an extraction. The unit  
should not be reinserted until the fans stop  
spinning.  
communications or analog functions are utilized as  
configured by the Protocol pin. This pin must be  
pulled low to turn ON the main output of the power  
supply. The power supply will turn OFF if either the  
Enable or the ON/OFF pin is released. The Enable  
function does not work with the RS-485 protocol.  
This signal is referenced to Logic_GRD.  
ON/OFF: This is a short pin utilized for hot-plug  
applications to ensure that the power supply turns  
OFF before the power pins are disengaged. It also  
ensures that the power supply turns ON only after  
the power pins have been engaged. Must be  
connected to 54_OUT (-DC).  
Control Definitions  
All signals are referenced to Logic GRD unless  
otherwise noted. See the Signal Definitions Table  
at the end of this document for further description  
of all the signals.  
Input Signals  
Output Signals  
Margining: Setpoint of the rectifier can be changed  
via this input pin. Programming can be either a  
voltage source or a resistance divider. The  
margining pin is connected to 3.3Vdc via a 10kΩ  
resistor inside the rectifier. See graphs below.  
Alert #: PMBus interrupt signal.  
Fault: This signal goes LO for any failure that  
requires rectifier replacement. Some of these faults  
may be due to:  
Fan failure  
Over-temperature condition  
Over-temperature shutdown  
Over-voltage shutdown  
Internal Rectifier Fault  
Power Capacity: A HI on this pin indicates rectifier  
configured for 2000W operation; a LO indicates  
rectifier configured for 1200W operation.  
An open circuit on this pin reverts the voltage level  
back to the original setting.  
Lineage Power  
5
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Alarm Table  
Monitoring Signals  
Power Supply LED State  
(Referenced to Logic_GRD)  
AC OK  
Green  
DC OK  
Green  
Service  
Amber  
Fault  
Red  
Module  
Present  
Condition  
Fault  
OTW  
PFW  
OK  
1
1
0
0
HI  
HI  
HI  
LO  
Thermal Alarm  
(5C before shutdown)  
1
1
1
0
HI  
LO  
HI  
LO  
Thermal Shutdown  
1
0
1
0
0
0
0
0
0
0
0
0
1
1
1
0
0
0
1
1
0
1
LO  
LO  
LO  
HI  
LO  
HI  
HI  
HI  
HI  
HI  
HI  
HI  
HI  
HI  
LO  
LO  
LO  
LO3  
LO  
LO  
LO  
LO  
LO  
HI  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
LO  
HI  
Defective Fan  
1
0
Blown AC Fuse in Unit  
No AC <15mS (single unit)  
AC Present but not within limits  
AC not present1  
1
0
0
1
Blinks  
0
HI  
0
1
1
1
1
0
HI  
Boost Stage Failure  
0
0
LO  
LO  
HI  
Over Voltage Latched Shutdown  
Over Current  
Blinks  
1
Non-catastrophic Internal Failure2  
1 Missing Module  
LO  
Standby (remote)  
1
1
1
0
1
1
0
Blinks  
0
0
0
HI  
HI  
HI  
HI  
HI  
HI  
LO  
HI  
LO  
LO  
LO  
Service Request (PMBus mode)  
Communications Fault (RS485 mode)  
Blinks  
HI  
1
This signal is correct if the rectifier is back biased from other rectifiers in the shelf .  
2 Any detectable fault condition that does not result in the power supply shutting down. For example, ORing FET failure, boost  
section out of regulation, etc.  
3
Signal transition from HI to LO is output load dependent  
Output Connector  
Mating Connector: AMP 1450572-1  
A1  
A6  
P1  
P7  
Signal  
Output Power  
Input Power  
P3  
6
5
4
3
2
1
P7  
P6  
P5  
P4  
P2  
P1  
SCL_0 MOD_PRES PFW  
LOGIC_GRD RS_485+ UNIT_ADDR  
A
B
C
D
SCL_1 OTW  
SDA_0 Margin  
SDA_1 Fault  
Alert#_0 Alert#_1  
Enable Reset  
5VA Power_Cap  
RS_485-  
Ishare  
8V_INT  
54_OUT 54_OUT  
(-DC) (+DC)  
EARTH LINE-2 LINE-1  
(GND) (Neutral) (Line)  
Reserved  
Protocol  
ON/OFF  
SHELF_ADDR  
Connector is viewed from the rear positioned inside the power supply.  
Signal pins columns 1 and 2 are referenced to 54_OUT (-DC).  
Signal pins columns 3 through 6 are referenced to Logic GRD.  
Last-to-make first-to-break pins.  
First-to-make last-to-break longest pin implemented in the mating connector.  
Lineage Power  
6
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Signal Definitions  
All hardware alarm signals (Fault, PFW, OTW, Power Capacity) are open drain FETs. These signals  
should be pulled HI to either 3.3V or 5V. Maximum sink current 5mA. An active LO signal (< 0.4Vdc). All  
signals are referenced to Logic GRD unless otherwise stated. Contact your Lineage Power representative  
for more details.  
Function  
Label  
Enable  
Type  
Input  
Description  
Output Enable  
If shorted to LOGIC_GRD, the rectifier output is enabled  
when using I2C mode of operation. May also be toggled to  
reset a latched OFF rectifier. Function not available in  
RS485 mode.  
Power Fail Warning  
I2C Interrupt  
PFW  
Output  
Output  
An open drain FET; normally HI, indicating output power is  
present. Changes to LO at least 5msec before the output  
voltage is lost.  
Interrupt signal via I2C lines indicating that service is  
requested from the host controller. This signal pin is pulled  
up to 3.3V via a 10kresistor and switches to active LO  
when an interrupt occurs.  
Alert#_0  
Alert#_1  
Rectifier Fault  
Module Present  
ON/OFF  
Fault  
Output  
Output  
Input  
Indicates that an internal fault exists. An open drain FET;  
normally HI, changes to LO.  
MOD_PRES  
ON/OFF  
Short pin, see Status and Control description for further  
information on this signal.  
Short pin, connects last and breaks first; used to activate  
and deactivate output during hot-insertion and extraction,  
respectively. Ref: 54_OUT (-DC)  
Protocol select  
Margining  
Protocol  
Margin  
Input  
See Status and Control description for further information  
on this signal. Ref: 54_OUT (-DC).  
Input  
Allows changing of output voltage through an analog  
voltage input or via resistor divider.  
Over-Temperature Warning OTW  
Output  
An open drain FET; normally HI, changes to LO  
approximately 5°C prior to thermal shutdown.  
Power Capacity  
POWER_CAP Output  
An open drain FET; Used to indicate rectifier operation  
mode; HI indicates 2000W operation and LO indicates  
1200W operation.  
Rectifier address  
Shelf Address  
Back bias  
Unit_addr  
Shelf_addr  
8V_INT  
Input  
Input  
_
Voltage level addressing of rectifiers within a single shelf.  
Ref: 54_OUT (-DC).  
Voltage level addressing of rectifiers within multiple  
shelves. Ref: 54_OUT (-DC).  
Diode OR’ed 8Vdc drain; used to back bias  
microprocessors and DSP of failed rectifier from operating  
rectifiers. Ref: 54_OUT (-DC).  
Mux Reset  
Reset  
5VA  
Input  
Resets the I2C lines to I2C line 0.  
Standby power  
Output  
5V at 0.75A provided for external use by either adjacent  
power supplies or the using system.  
Current Share  
Ishare  
-
A single wire interface between each of the power unit  
forces them to share the load current. Ref: 54_OUT (-DC).  
I2C Line 0  
I2C Line 1  
RS485 Line  
SCL_0, SDA_0 Input  
SCL_1, SDA_1 Input  
I2C line 0.  
I2C line 1.  
RS485 line.  
RS_485+  
RS_485-  
Input  
Lineage Power  
7
Data Sheet  
Compact Power Line  
CP2000AC54 Front-End Power Supply  
Front Panel LEDs  
Analog Mode  
I2C Mode  
ON: Input ok  
RS485 Mode  
Blinking: Input out of limits  
ON: Output ok  
Blinking: Overload  
ON: Over-temperature  
ON: Over-temperature Warning  
Blinking: Service  
ON: Over-temperature  
Warning  
Warning  
ON: Fault  
Blinking: Not communicating  
ON: Fault  
!
Dimensions  
13.85 in.  
(351.8 mm)  
Rear View  
4.00 in.  
(101.6 mm)  
1.70 in.  
(43.2 mm)  
Front View  
Top View  
Ordering Information  
Item  
Description  
Comcode  
CP2000AC54PE  
CP2000AC54PEZ  
Designed to IEEE802.3 POE compliance, RoHS 5/6  
Tested to IEEE802.3 POE compliance, RoHS 6/6  
CC109120722  
CC109139408  
Asia-Pacific Headquarters  
Tel: +65 6593 7211  
Europe, Middle-East and Africa Headquarters  
World Wide Headquarters  
Lineage Power LLC  
Tel: +49 898 780 672 80  
601 Shiloh Road, Plano, TX 75074, USA  
+1-800-526-7819  
India Headquarters  
Tel: +91 80 2841 1633  
(Outside U.S.A.: +1-972-284-2626)  
www.lineagepower.com  
e-mail: techsupport1@lineagepower.com  
Lineage Power reserves the right to make changes to the product(s) or information contained herein without notice. No liability is assumed as a result of their use or  
application. No rights under any patent accompany the sale of any such product(s) or information.  
© 2009 Lineage Power LLC, (Mesquite, Texas) All International Rights Reserved.  
Revision : GGS-August 2009  
Lineage Power  
Page 8  

相关型号:

CP2000AC54SD

Compact Power Line Input: 200-240 Vac; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
LINEAGEPOWER

CP2000AC54TEP

100-120/200-277VAC input; Default Outputs: ±54VDC @ 2000W, 5VDC @ 4W
LINEAGEPOWER

CP2000AC54TEZ

100-120/200-277VAC input; Default Outputs: ±54VDC @ 2000W, 5VDC @ 4W
LINEAGEPOWER

CP2000DC54

Compact Power Line Input: -40 to -72 Vdc; Outputs: ±54 Vdc at 2000W; 5 Vdc at 4W
LINEAGEPOWER

CP2001-7R

120...195 Watt DC-DC Converters
POWER-ONE

CP2001-7RB1

DC-DC Regulated Power Supply Module, 2 Output, 182W, Hybrid, METAL, CASE P01, MODULE
BEL

CP2001-7RB3

Analog Circuit,
BEL

CP2001-7RDG

DC-DC Regulated Power Supply Module, 2 Output, 152W, METAL, CASE P01, MODULE
BEL

CP2001-7RDGI

DC-DC Regulated Power Supply Module, 2 Output, 152W, METAL, CASE P01, MODULE
BEL

CP2001-7RDGT

DC-DC Regulated Power Supply Module, 2 Output, 152W, METAL, CASE P01, MODULE
BEL

CP2001-7RDGTI

DC-DC Regulated Power Supply Module, 2 Output, 152W, METAL, CASE P01, MODULE
BEL

CP2001-7RDGTW

DC-DC Regulated Power Supply Module, 2 Output, 152W, METAL, CASE P01, MODULE
BEL