V302AS32 [LITTELFUSE]
High Energy Metal-Oxide Arrester Blocks; 高能金属氧化物避雷器模块型号: | V302AS32 |
厂家: | LITTELFUSE |
描述: | High Energy Metal-Oxide Arrester Blocks |
文件: | 总4页 (文件大小:115K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
AS Series
Data Sheet
January 1998
File Number 2492.4
High Energy Metal-Oxide Arrester Blocks
Features
The AS Series of Arrester blocks is primarily designed to be
used as the surge suppression element within a lightning
arrester assembly. These arrester blocks provide the high
peak surge current and energy ratings required for the
protection of high voltage AC power utility distribution
systems. Typically, these devices are placed within a special
arrester housing provided by the customer, and stacked to
achieve the necessary continuous working voltage ratings
for the specific application. (See the CA or NA series of
Varistor discs for lower voltage and energy applications.)
• Provided in Disc Form for Unique Packaging by
Customer
• Electrode Finish Enables Pressure Contact for Stacking
Application
[ /Title
(AS
Series)
/Sub-
ject
(High
Energy
Metal-
Oxide
Arreste
r
• Available Disc Sizes: 32mm, 42mm and 60mm Diameter
• No Follow Current
• High Surge Current Capability
• Conforms to IEC 99-4 and ANSI/IEEE C62.11 Industry
Standards
• Characterized for Lightning Arrester Parameters
Applications
• Lightning Protection of Electrical AC Distribution
Transformers and Systems
Blocks
)
• Arrester Assemblies of the Porcelain Polymeric,
“Under-oil” and Metal Clad Variety
/Autho
r ()
Packaging
AS SERIES
/Key-
words
(TVS,
Tran-
sient
Sup-
pres-
sion,
Protec-
tion,
Arreste
r,
Light-
ning
Protec-
tion,
OBSOLETE
PART
1-800-999-9445 or 1-847-824-1188 | Copyright © Littelfuse, Inc. 1998
8-3
AS Series
Absolute Maximum Ratings For ratings of individual members of a series, see Device Ratings and Specifications chart
AS SERIES
UNITS
kV
Rated Voltage
AC Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.00 to 6.00
2.55 to 5.10
Steady State Applied Voltage
AC Voltage (MCOV). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transient
kV
Peak Pulse Current (I ) for 4/10 µs Current Wave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65 to 100
2.2 to 12
60
kA
kJ
TM
Energy Rating for 2ms Current Wave . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
o
Operating Ambient Temperature (T ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A
C
STORAGE AND HANDLING NOTES:
1. Arrester blocks should be stored in a moisture free environment at all times.
2. Use caution during handling to prevent damage or chipping of edges of the arrester blocks.
CAUTION: Stresses above those listed in “Absolute Maximum Ratings” may cause permanent damage to the device. This is a stress only rating and operation of the
device at these or any other conditions above those indicated in the operational sections of this specification is not implied.
o
Device Ratings and Specifications 25 C Unless Otherwise Specified
PART NUMBER
PARAMETER
V302AS32 V402AS32 V502AS32 V602AS32 V302AS42 V402AS42 V502AS42 V402AS60 UNITS
Rated Voltage (RMS)
3.0
4.0
5.0
6.0
5.1
3.0
4.0
5.0
4.0
kV
kV
Maximum Continuous
2.55
3.40
4.25
2.55
3.40
4.25
3.40
Operating Voltage (MCOV)
Reference Current, I
Minimum Reference
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
mA
REF
3.12
4.16
5.20
6.24
3.12
4.16
5.20
4.16
kV
RMS
OBSOLETE
Voltage, V
REF
Nominal Discharge
5.0
9.8
5.0
13.1
2.9
5.0
16.3
3.6
5.0
19.6
4.3
10.0
10.0
3.5
10.0
13.3
4.7
10.0
16.7
5.8
10.0
12.5
12.0
100.0
-
kA
Current, I (8/20µs)
P
Residual Voltage (Max) at
kV
kJ
I
P
o
Energy Rating at 60 C
(2ms)
2.2
PART
Peak Current, 4/10µs at
65.0
11.3
65.0
65.0
65.0
100.0
100.0
100.0
-
kA
kV
o
60 C (Note 4)
Maximum Steep Current
Residual Voltage at 5kA
(1/20µs)
15.0
18.8
22.5
-
-
Maximum Steep Current
Residual Voltage at 10kA
(1/20µs)
-
-
-
-
11.5
15.3
19.2
14.4
kV
Maximum Dissipation
Power at MCOV
0.23
75.0
0.30
75.0
0.38
75.0
0.45
75.0
0.36
0.48
0.60
0.50
W
Maximum Conduction
Current at MCOV
110.0
110.0
110.0
140.0
µA
NOTES:
3. In addition to above standard types, custom ratings and dimensions can be provided.
4. Parts should be wrapped using a secondary insulating film or encased by polymeric housing.
8-4
AS Series
Performance Curves
1.3
35
30
1.25
1.2
25
20
V602AS32
V502AS32
V402AS32
V302AS32
1.15
1.1
15
10
5
1.05
1
0
100
1000 10,000 100,000
1
10
0.001 0.01
0.1
0.1
1
10
100
1000
10000
PEAK IMPULSE CURRENT (A)
TIME (s)
FIGURE 1. TEMPORARY OVERVOLTAGE CAPABILITY (TOV)
FOR AS SERIES ARRESTERS
FIGURE 2. V-I CHARACTERISTIC AS32 SIZE
30
25
20
15
10
5
20
V502AS42
V402AS42
15
10
5
V302AS42
V402AS60
OBSOLETE
0
0
100
1000 10,000 100,000
100
1000 10,000 100,000
1
10
1
10
0.001
0.01
0.1
0.001 0.01
0.1
PEAK IMPULSE CURRENT (A)
PEAK IMPULSE CURRENT (A)
FIGURE 3. V-I CHARACTERISTIC AS42 SIZE
FIGURE 4. V-I CHARACTERISTIC AS60 SIZE
PART
8-5
AS Series
Dimensions
PASSIVATION COLLAR
TYPICAL THICKNESS = 0.07mm
ELECTRODE
OF SPRAYED
ALUMINUM
PARTICLES
FACE CAMBER
= 0.15mm MAX
ELECTRODE
= 0.10mm TYPICAL
∅ D
H
DIMENSIONS (IN MILLIMETERS)
PART NUMBER
PARAMETER
V302AS32 V402AS32 V502AS32 V602AS32 V302AS42 V402AS42 V502AS42 V402AS60 UNITS
Diameter (∅D)
Min
32.3
32.3
32.3
32.3
40.9
40.9
40.9
60.0
mm
mm
OBSOLETE
Max
33.7
33.7
33.7
33.7
42.3
42.3
42.3
62.0
Height (H)
Min
20.0
21.5
27.0
28.5
34.0
35.5
41.0
42.5
20.0
21.5
27.0
28.5
34.3
35.8
35.3
36.8
mm
mm
Max
Ordering Information PART
VXXX ASXX TYPES
AS SERIES
V
30
2
AS 60
VARISTOR
TECHNOLOGY
DIAMETER SIZE (mm)
MCOV BASE VALUE
ARRESTER SERIES
MCOV DECADE MULTIPLIER