3100-30W16999 [MACOM]

Definite Purpose Contactor 3-pole, 50-60 FLA 3-pole, 50-60 FLA; 专用接触器3极, 50-60 FLA 3极, 50-60 FLA
3100-30W16999
型号: 3100-30W16999
厂家: Tyco Electronics    Tyco Electronics
描述:

Definite Purpose Contactor 3-pole, 50-60 FLA 3-pole, 50-60 FLA
专用接触器3极, 50-60 FLA 3极, 50-60 FLA

文件: 总2页 (文件大小:100K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Catalog 1308242  
Issued 3-03 (PDF Rev. 1-06)  
PRODUCTS UNLIMITED  
Model 93 - 3100 series  
Definite Purpose Contactor  
3-pole, 50-60 FLA  
AC Coil  
File E75492  
File EN60947-4-1:1991  
IEC 947-4-1  
Users should thoroughly review the technical data before selecting a product part  
number. It is recommended that users also seek out the pertinent approvals files of  
the agencies/laboratories and review them to ensure the product meets the  
requirements for a given application.  
Features  
Environmental Data  
Temperature Range: Storage and Operating: -40°C – +65°C.  
Flammability: UL 94-HB housing.  
• 3-pole contactors.  
• Convenient “universal” mounting plate.  
• Optional interlock/auxiliary switches available.  
Mechanical Data  
Contact Termination:  
Type: Box Lug with dual 0.250” (6.35 mm) quick connects.  
Wire Size: 14-2 Cu/Al AWG  
Tightening Torque: 50 in.-lbs.  
Contact Data @ 25°C  
Arrangements: 3 Form X (3PST-NO-DM).  
Maximum Ratings: See Contact Ratings Table.  
Material: Silver Cadmium Oxide.  
Coil Termination: Dual 0.250” (6.35 mm) quick connects, standard.  
A 0.250” quick connect and a #6-32 screw, optional.  
Arc Cover: Standard.  
Weight: 32 oz. (910 g) approximately  
Coil Data @ 25°C  
Voltage: 24 - 480 VAC, 50/60 Hz. See Coil Data Table below.  
Insulation Class: UL Class B (130°C).  
Duty Cycle: Continuous.  
Contact Ratings  
Full  
Load  
Amps  
Number  
of  
Poles  
Line  
Voltage  
Locked  
Rotor  
Amps  
Resistive  
Amps  
Tungsten/  
Ballast  
Amps  
Maximum Horsepower  
Voltage  
Single  
Phase  
Three  
Phase  
110/120  
200/208  
240/277  
480  
3
7.5  
10  
-
-
50  
3
240  
480  
600  
300  
250  
200  
65  
65  
65  
53  
15  
15  
25  
25  
600  
-
110/120  
200/208  
240/277  
480  
5
7.5  
10  
-
-
60  
3
240  
480  
600  
360  
300  
240  
75  
75  
75  
53  
25  
25  
30  
30  
600  
-
Coil Data  
Nominal Coil Voltage  
Maximum Pickup Volts  
Drop-Out Volts Range  
Nominal Inrush VA @ 50 Hz  
Nominal Inrush VA @ 60 Hz  
Nominal Sealed VA @ 50 Hz  
Nominal Sealed VA @ 60 Hz  
Nominal DC Resistance - Ohms  
24  
182  
6 -15  
140  
132  
20  
120  
208/240  
177  
40 - 135  
140  
132  
20  
14  
180  
277  
235  
50-180  
140  
132  
20  
480  
374  
120 - 286  
140  
132  
20  
14  
852  
93  
20 - 70  
140  
132  
20  
14  
45  
14  
14  
280  
2.4  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
834  
Catalog 1308242  
Issued 3-03 (PDF Rev. 1-06)  
PRODUCTS UNLIMITED  
Ordering Information  
B
Typical Part No.  
3100  
-
30  
I
16  
999  
1. Series:  
3100 = 3-pole, 50-60 FLA contactor  
2.Packaging:  
Y = Individual Pack  
- = Bulk Pack  
A-ZZZ = Customer specific information (assigned by factory)  
3.Pole Configuration:  
30 = 3 Form X (3PST-NO-DM)  
4.Coil Voltage (50/60 Hz.):  
I = 24VAC, molded  
J = 120VAC, molded  
K = 208/240VAC, molded  
M = 277VAC, molded  
W = 480VAC, molded  
5.Contact Ratings (Inductive):  
16 = 50 FLA  
17 = 60 FLA  
6.Customer ID Suffix:  
999 = Standard Model  
000-998 = Factory assigned customer ID  
7. Option Code:  
Leave Blank = No customer-specific options  
A - ZZ = Factory assigned customer-specific options.  
Standard part numbers listed below are more likely to be available from stock.  
None at present.  
Outline Dimensions  
Termination  
3.10  
3.563  
(90.5)  
.218 TYP.  
(5.537)  
(78.7)  
.438  
2.75  
(69.9)  
(11.12)  
2.032  
(51.61)  
.250  
(6.35)  
.253  
(6.43)  
Standard  
on 50-60 FLA  
Lug accepts 14-2  
Cu/Al AWG  
3.25  
(82.55)  
3.75  
(95.25)  
3.19  
(81.03)  
1.468  
.250  
(6.35)  
(37.29)  
2.65  
(67.3)  
2.242  
(56.95)  
Shown with Optional Auxiliary Switch  
Equipped with 0.250” (6.35) Quick Connect Terminals  
Factory Modifications Field Added Kits  
Various interlock / auxiliary switches are available for the Model 93 contactor.  
Description  
Contact Config.  
Kit Catalog  
Number  
Number of  
Kits Required  
NO  
NC  
Single unit interlock  
1
0
1
2
0
2
0
1
1
0
2
2
34300-303  
34300-331  
34300-332  
34300-303  
34300-331  
34300-332  
1
1
1
2
2
2
configurations listed.  
Maximum of two. Must  
be same polarity.  
NORMALLY OPEN  
-303 STYLE  
NORMALLY CLOSED  
-331 STYLE  
See footnote (1) for ratings.  
SPDT Circuit  
See footnote (2) for ratings.  
1
2
1
2
34300-337  
34300-337  
1
2
SPDT Dry Circuit, 0.1 amp max.  
Gold Flashed Contacts  
1
2
1
2
34300-341  
34300-340  
1
1
Equipped with #6-32 Screw Terminals & Saddle Clamps  
Factory Modifications Field Added Kits  
NORMALLY OPEN & CLOSED  
-332 STYLE  
SPDT  
-337 & -341 STYLE  
Description  
Contact Config.  
Kit Catalog  
Number  
Number of  
Kits Required  
NO  
NC  
Single unit interlock  
1
0
1
0
1
1
34300-342  
34300-343  
34300-344  
1
1
1
configurations listed.  
Maximum of two. Must  
be same polarity. (note 1)  
Footnotes: Ratings of Auxiliary Interlocks / Switches  
(1) Contact Rating Single Circuit NO or NC  
and two circuit NO/NC:  
(2) Contact Rating SPDT (337):  
10A, 1/3 HP, 125 or 250 VAC  
W/ #6-32 SCREW & SADDLE CLAMP  
-344 STYLE  
120V 240V 480V 600V  
1/2A, 125 VDC; 1/4A, 250 VDC:  
4A 120 VAC on Lamp Load  
Break  
Make  
3.0A 1.5A 0.75A 0.6A  
30A 15A 7.5A 6A  
Continuous 10A 10A 10A 10A  
Dimensions are shown for  
reference purposes only.  
Dimensions are in inches over  
(millimeters) unless otherwise  
specified.  
Specifications and availability  
subject to change.  
www.tycoelectronics.com  
Technical support:  
Refer to inside back cover.  
835  

相关型号:

3100-30W17999

Definite Purpose Contactor 3-pole, 50-60 FLA 3-pole, 50-60 FLA
MACOM

3100-30W7999

Definite Purpose Contactor 3-pole, 20-40 FLA AC Coil
TE

3100-30W8999

Definite Purpose Contactor 3-pole, 20-40 FLA AC Coil
TE

3100-30W9999

Definite Purpose Contactor 3-pole, 20-40 FLA AC Coil
TE

3100-40H10000-998

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40H10999

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40H8000-998

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40H8999

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40H9000-998

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40H9999

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40I10000-998

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE

3100-40I10999

Definite Purpose Contactor 4-pole, 25-40 FLA AC Coil
TE