PB-1000-48 [MEANWELL]
1000W Intelligent Single Output Battery Charger; 1000W智能单路输出充电器型号: | PB-1000-48 |
厂家: | MEAN WELL ENTERPRISES CO., LTD. |
描述: | 1000W Intelligent Single Output Battery Charger |
文件: | 总5页 (文件大小:490K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
1000W Intelligent Single Output Battery Charger
PB-1000 series
Features :
Controlled by microprocessor
2/8 stage charging selectable on output panel
Universal AC input / Full range
Built-in active PFC function PF>0.95
Protection: Reverse Polarity / Short circuit / Over voltage / Over temperature
Charger for lead-acid batteries
3 color LED loading indicator
Built-in remote ON-OFF control
2-Bank charger
Temperature compensation function
FAN on/off control (depends on charging current)
3 years warranty
..
SPECIFICATION
MODEL
PB-1000-12
BOOST CHARGE VOLTAGE 14.4V
FLOAT CHARGE VOLTAGE 13.8V
PB-1000-24
PB-1000-48
28.8V
27.6V
34.7A
57.6V
55.2V
17.4A
OUTPUT CURRENT
60A
RECOMMENDED BATTERY
CAPACITY(AMP HOURS)(Note 3)
BATTERY TYPE
OUTPUT
200 ~ 600Ah
120 ~ 350Ah
60 ~ 175Ah
Open & Sealed Lead Acid
<1mA
LEAKAGE CURRENT FROM
BATTERY (Typ.)
VOLTAGE RANGE
90 ~ 264VAC
47 ~ 63Hz
127 ~ 370VDC
FREQUENCY RANGE
EFFICIENCY (Typ.)
85%
88%
89%
POWER FACTOR (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
0.95/230VAC
12A/115VAC
25A/115VAC
<3.5mA / 240VAC
16 ~ 18V
0.98/115VAC at full load
INPUT
5.2A/230VAC
50A/230VAC
LEAKAGE CURRENT
32 ~ 35V
64.5 ~ 69.5V
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
80
85
5
5
(12V), 85
(12V),75
5
(24V,48V) (TSW1: detect on heatsink of power transistor)
(24V,48V) (TSW2 : detect on heatsink of o/p diode)
PROTECTION
5
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
YES, protected by internal circuit
SHORT CIRCUIT
YES, protected by internal circuit
REVERSE POLARITY
REMOTE CONTROL
BATTER BANKS
Open: Normal work
2 banks (A & B)
Short: Stop Charging
2 / 8 stage selectable
FAST CHARGE
FUNCTION
Relay contact rating(max.): 30V/1A resistive ; "Short" when the unit is working properly, "Open"when the unit is failure or the protection function is activating
Relay contact rating(max.): 30V/1A resistive ; "Short" when the battery is full, "Open" when the battery is still charging
By NTC, compensate both banks at the same time
CHARGER OK
OUTPUT OK
TEMPERATURE COMPENSATION
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
ENVIRONMENT
-40 ~ +85 , 10 ~ 95% RH
0.05%/ (0 ~ 50
)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC 25 70%RH
SAFETY &
EMC
(Note 2)
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22)
HARMONIC CURRENT
EMS IMMUNITY
MTBF
Compliance to EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
127.4Khrs min. MIL-HDBK-217F (25
300*184*70mm(L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
3.5Kg; 4pcs/15Kg/1.83CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
3. This is Mean Well's suggested range. Please consult your battery manufacturer for their suggestions about maximum charging current limitation.
File Name:PB-1000-SPEC 2008-05-12
1000W Intelligent Single Output Battery Charger
PB-1000 series
Mechanical Specification
Case No. 804B
Unit:mm
300
155
70
72.6
7
A
Air flow
direction
48
26.5
A
1
2
9
7
8
5
6
3
4
10
8 Stage
2 Stage
Charging Curve
Control Pin No. Assignment(CN100) : HRS DF11-10DP-2DS or equivalent
Pin No. Assignment Pin No. Assignment Mating Housing
Terminal
2 Stage
RY13
RY14
RY15
GND
NTC(5K
RC-
)
1,2
3,4
5,6
7
8
9
Start
Vboost
HRS DF11-10DS HRS DF11-**SC
or equivalent or equivalent
10
RC+
Charge Voltage
RY13 : Bank A OK
RY14 : Bank B OK
RY15 : Charger OK
NTC / GND : Temperature sense
RC+ / RC-: Remote ON/OFF
100%
10%
Charge Current
Constant Current Constant Voltage
stage 1
stage 2
Battery Full
Green
Orange
Color of LED
8 Stage
Recondition
Float
Pulse
Soft Start
Analysis
Maintain
Constant Current Constant Voltage
Charge Voltage
Charge Current
stage 1
stage 2
stage 3
stage 4
stage 5
stage 6
stage 7
stage 8
Orange
Green
Color of LED
File Name:PB-1000-SPEC 2008-05-12
1000W Intelligent Single Output Battery Charger
PB-1000 series
Block Diagram
PFC : 95KHz
PWM fosc : 60KHz
BANK A (+V)
BANK B (+V)
ACTIVE
INRUSH
CURRENT
LIMITING
RECTIFIER
RECTIFIER
&
FILTER
POWER
EMI
FILTER
I/P
&
PFC
SWITCHING
PFC
CONTROL
REVERSE
DETECTION
MCU
PWM
CONTROL
CURRENT
DETECTION
2/8
STAGE
SELECT
AUX
POWER
FAN
OTP
REMOTE
CONTROL
RC
Bank A OK
Bank B OK
Charger OK
RY13
RY14
RY15
Derating Curve
The Function of LEDs
Battery
Fail
Color of LED
Red
100
80
Charging
Orange
Green
Battery Full
60
40
20
-20
0
10
20
30
40
50
60
70
(HORIZONTAL)
AMBIENT TEMPERATURE (
)
Function Description of CN100
Pin No. Function
Description
1,2
3,4
RY13 Relay contact rating(max.) : 30V/1A resistive. ; "Short" when the battery A is full, "Open" when the battery A is still charging.
RY14 Relay contact rating(max.) : 30V/1A resistive. ; "Short" when the battery B is full, "Open" when the battery B is still charging.
Relay contact rating(max.) : 30V/1A resistive. ; "Short" when the unit is working properly, "Open" when the unit is failure or
5,6
RY15
the protection function is activating.
Temperature sensor comes along with the charger can be connected to the unit to allow temperature compensation of the
charging voltage.
7,8
GND / RTH
If the temperature sensor is not used, the charger still works normally.
Turn the output on and off by electrical or dry contact between pin 10 (RC+) and pin 9(RC-), "Open" : Normal work ,
"Short" : Stop charging
9,10 RC- / RC+
File Name:PB-1000-SPEC 2008-05-12
1000W Intelligent Single Output Battery Charger
PB-1000 series
Function Manual
1.Remote Control
The charger can be turned ON/OFF by using the
"Remote Control" function.
CN100
2
1
RY13 RY13
RY14 RY14
RY15 RY15
GND RTH
RC- RC+
Between RC+(pin10) and RC-(pin9)
Charger
A
B
SW Open
SW Short
ON
B
A
OFF
8 Stage
2 Stage
1
3
5
7
9
2
4
6
8
10
10
9
SW
+
-
+
-
Battery B
Battery A
2.Two Battery Banks
The charger may be hooked up two battery banks (A and/or B). Connect the battery bank(s) as below. If you are connecting 2 battery banks in the
same time, keep in mind that they must share a common ground.
A
B
A
B
B
A
B
A
8 Stage
2 Stage
8 Stage
2 Stage
1
3
5
7
9
2
4
1
3
5
7
9
2
4
6
6
8
10
8
10
+
-
+
-
Battery A
Battery B
A
B
B
A
8 Stage
2 Stage
1
3
5
7
9
2
4
6
8
10
+
-
+
-
Battery B
Battery A
File Name:PB-1000-SPEC 2008-05-12
1000W Intelligent Single Output Battery Charger
PB-1000 series
3. 2 or 8 stage Charging Select
The charger features user selectable 2 or 8 stage charging.
The charging profile is selected by moving the slide switch
on the back panel.
CN100
2
1
RY13 RY13
RY14 RY14
RY15 RY15
GND RTH
RC- RC+
Switch
Charging mode
2 stage charging
8 stage charging
A
B
Turn right
Turn left
B
A
8 Stage
2 Stage
1
3
5
7
9
2
4
6
8
10
10
9
8 Stage
2 Stage
+
-
+
-
Battery B
Battery A
4.Charger OK Relay(RY15)
CN100
Charger
Between pin5 and pin6(RY15)
ON (Short)
2
1
RY13 RY13
A
B
Normal work
B
A
RY14 RY14
RY15 RY15
GND RTH
RC- RC+
Failure or the protection
function is activating
OFF (Open)
8 Stage
2 Stage
1
3
5
7
9
2
4
6
8
10
10
9
RY15
+
-
+
-
Battery B
Battery A
5.Output OK Relay(RY13 & RY14)
CN100
1.Bank A OK (RY13)
2
1
Bank A
Between pin1 and pin2(RY13) Color of LED A
RY13 RY13
A
B
Battery A Full
Charging
ON (Short)
Green
B
A
RY14 RY14
RY15 RY15
GND RTH
RC- RC+
OFF (Open)
Orange
8 Stage
2 Stage
1
3
5
7
9
2
4
2.Bank B OK (RY14)
6
8
10
Bank B
Between pin3 and pin4(RY14) Color of LED B
10
9
Battery B Full
Charging
ON (Short)
Green
OFF (Open)
Orange
RY14
RY13
+
-
+
-
Battery B
Battery A
6.Temperature Compensation
CN100
Temperature sensor comes along with the charger can
2
1
RY13 RY13
A
B
be connected to the unit to allow temperature compensation
of the charging voltage.
B
A
RY14 RY14
RY15 RY15
GND RTH
RC- RC+
If the temperature sensor is not used, the charger still
works normally.
8 Stage
2 Stage
1
3
5
7
9
2
4
6
8
10
10
9
+
-
+
-
Battery B
Battery A
NTC
The temperature sensor can either be attached to the
battery or placed in its surrounding environment.
File Name:PB-1000-SPEC 2008-05-12
相关型号:
©2020 ICPDF网 联系我们和版权申明