PSP-600-12 [MEANWELL]
600W with PFC and Parallel Function; 600W带PFC和并联功能型号: | PSP-600-12 |
厂家: | MEAN WELL ENTERPRISES CO., LTD. |
描述: | 600W with PFC and Parallel Function |
文件: | 总3页 (文件大小:393K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
600W with PFC and Parallel Function
PSP-600 series
Features :
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan
With DC OK Signal output
Current sharing up to 2400W(3+1)
Built-in remote ON-OFF control
Built-in remote sense function
Fixed switching frequency at PFC:88KHz PWM:100KHz
3 years warranty
SPECIFICATION
MODEL
PSP-600-5
PSP-600-12
PSP-600-13.5
PSP-600-15
PSP-600-24
PSP-600-27
PSP-600-48
DC VOLTAGE
5V
12V
13.5V
15V
24V
27V
48V
RATED CURRENT
CURRENT RANGE
RATED POWER
80A
50A
44.5A
40A
25A
22.2A
12.5A
0 ~ 80A
400W
0 ~ 50A
600W
0 ~ 44.5A
600W
0 ~ 40A
600W
0 ~ 25A
600W
0 ~ 22.2A
600W
0 ~ 12.5A
600W
RIPPLE & NOISE (max.) Note.2 180mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 2.0%
240mVp-p
10 ~ 13.2V
1.0%
240mVp-p
12 ~ 15V
1.0%
240mVp-p
13.5 ~ 18V
1.0%
240mVp-p
20 ~ 26.4V
1.0%
240mVp-p
24 ~ 30V
1.0%
300mVp-p
41 ~ 56V
1.0%
OUTPUT
4.75 ~ 5.5V
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
0.5%
1.0%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
0.5%
1500ms, 50ms at full load
20ms at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
Note.5 88 ~ 264VAC
124 ~ 370VDC
FREQUENCY RANGE
POWER FACTOR (Typ.)
EFFICIENCY(Typ.)
47 ~ 63Hz
0.95/230VAC
79%
0.99/115VAC at full load
INPUT
84%
85%
85%
86%
86%
87%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
6.8A/115VAC
20A/115VAC
<1.3mA/240VAC
3.4A/230VAC
40A/230VAC
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
5.75 ~ 6.75V 13.8 ~ 16.2V 15.5 ~ 18.2V 18 ~ 21V 27.6 ~ 32.4V 31 ~ 36.5V
Protection type : Shut down o/p voltage, re-power on to recover
+5V: 95 (TSW1) detect on heatsink of power transistor; 95 (TSW51) detect on heatsink of power diode
OVERLOAD
57.6 ~ 67.2V
OVER VOLTAGE
PROTECTION
+12V ~ +48V: 85 (TSW1) detect on heatsink of power transistor; 80 (TSW51) detect on heatsink of power diode
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE
RC+/RC-: Short = power on ; Open = power off
REMOTE CONTROL
POK SIGNAL
FUNCTION
PSU turn on: 3.3V ~ 5.6V
PSU turn off: 0V ~ 1V
-20 ~ +60 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
0.03%/ (0 ~ 50
)
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
SAFETY &
EMC
(Note 4)
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, light industry level, criteria A
116.4K hrs min. MIL-HDBK-217F (25
170*120*93mm (L*W*H)
)
OTHERS
NOTE
DIMENSION
PACKING
1.9Kg; 8pcs/15.5Kg/1.06CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:PSP-600-SPEC 2008-07-29
600W with PFC and Parallel Function
PSP-600 series
Mechanical Specification
Case No.910A Unit:mm
RS Connector(CN5) : JST B-XH or equivalent
Pin No. Assignment
Mating Housing
Terminal
1
2
RS+
RS-
JST SXH-001T
or equivalent
JST XHP
or equivalent
Terminal Pin No. Assignment
2-M3 L=4mm max.
Pin No.
Assignment
AC/L
2-M3 L=4mm max.
1
2
AC/N
3
FG
4
P(Current Share)
POK
5
6
R.C. G
150
7
R.C.
8~11
DC OUTPUT +V
185
170
150
12~15 DC OUTPUT -V
120
8
11.5
1
2
3
4
5
6
7
2-M3 L=4mm max.
2-M3 L=4mm max.
14 max.
1 2
CN5
8
9
10 11 12 13 14 15
9.5
11.5
Block Diagram
PFC fosc : 88KHz
PWM fosc : 100KHz
FAN
SIGNAL
CONTROL
POK
CURRENT
SHARING
CIRCUIT
P
ACTIVE
INRUSH
CURRENT
RECTIFIERS
&
P.F.C.
POWER
SWITCH-
ING
RECTIFIERS
&
FILTER
+V
-V
EMI
FILTER
I/P
FG
LIMITING
RC.G.
RC
O.C.P.
DETECTION
CIRCUIT
PWM
CONTROL
O.L.P.
O.V.P.
O.T.P.
Derating Curve
Output Derating VS Input Voltage
Ta=25
100
90
100
80
Others
80
70
60
50
12V
60
40
50
40
20
-20
0
10
20
30 40 45
50
60 (HORIZONTAL)
88 100 115
135
155
230 264
AMBIENT TEMPERATURE (
)
INPUT VOLTAGE (V) 60Hz
File Name:PSP-600-SPEC 2008-07-29
600W with PFC and Parallel Function
PSP-600 series
Control Terminal Instruction Manual
POK(+) RCG(-)
RCG RC
L
N
FG
P
POK RCG RC
L
N
FG
P
POK RCG RC
L
N
FG
P POK RCG RC
+V +V +V +V -V -V -V -V
+V +V +V +V -V -V -V -V
+V +V +V +V -V -V -V -V
RS+ RS-
RS+ RS-
RS+ RS-
+
-
+
-
+
-
LOAD
LOAD
LOAD
Remote Sensing
POK Signal
Remote Control
Power ON: RCG and RC for short
Power OFF: RCG and RC for open
POK Signal is the voltage difference between
"RCG" and "POK" pin output POK Signal for TTL level signal
PSU turn on: 3.3V ~ 5.6V
PSU turn off: 0V ~ 1V
Parallel Operation with Remote Sensing
(1)Parallel operation is available by connecting the units shown as below (+S,-S and P are connected mutually in parallel) :
(2)The voltage difference among each output should be minimized that less than 2% is required.
(3)The total output current must not exceed the value determined by the following equation (Output current at parallel operation)
=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 4 units is the maximum, please consult the manufacture for other applications.
(5) When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.
(6) When in parallel operation, the minimum output load should be greater than 3% of total output load.
(Min. load > 3% rated current per unit x number of unit)
LOAD
+V
+S
-V
-S
+
-
P
RC- RS+ RS-
+
-
P
RC- RS+ RS-
+
-
P
RC- RS+ RS-
+
- P RC- RS+ RS-
PSU
PSU
PSU
PSU
File Name:PSP-600-SPEC 2008-07-29