RKP-6K1U-12 [MEANWELL]

2000~6000W Front End Power System; 2000 〜 6000W前端电源系统
RKP-6K1U-12
型号: RKP-6K1U-12
厂家: MEAN WELL ENTERPRISES CO., LTD.    MEAN WELL ENTERPRISES CO., LTD.
描述:

2000~6000W Front End Power System
2000 〜 6000W前端电源系统

文件: 总6页 (文件大小:925K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
2000~6000W Front End Power System  
RKP-1U Rack System  
Features :  
Universal AC input / Full range  
Holds up to 3 power modules  
Active current sharing up to 6000W(3 unit) in one 19”rack, 3 rack max.  
can be operated in parallel (up to 9 units)  
PMBus serial interface  
IEC320-C20 or terminal block input  
Front-end & rectifier applications  
Stackable for system expansion  
Low profile: 1U height, 19” rack mount  
Hot swappable modules  
Output voltage trimming function  
3 years warranty  
Description :  
RCP-2000 rack power system is an advanced 19” rack-mounted power system containing up to 3 hot-swappable RCP-2000 rectifiers and  
can deliver up to 6000W in the single rack. Up to 3 racks can be stacked to provide expanded total system capability up to 18,000W that  
are especially suitable for the application of servers, information technology equipment, networking, telecommunications, and wide  
range of industrial applications using distributed power architecture. Equipped with PMBus communication protocol, RCP-2000 rack  
system can be controlled or monitored by external device such as monitoring unit (RCP-CMU-1) or PC.  
SELECTION GUIDE  
I
C 12  
-
Output voltage  
Rack: RKP-1U I  
C
Whole System: RKP-6K1U  
C: With RCP-CMU-1  
: Without RCP-CMU-1  
C: With RCP-CMU-1  
: Without RCP-CMU-1  
I: AC Inlet (IEC320-C20)  
T: Terminal block  
I: AC Inlet  
T: Terminal  
SPECIFICATION - Rack System  
MODEL  
RKP-6K1U -12  
RKP-6K1U -24  
RKP-6K1U -48  
MODULE  
RACK  
RCP-2000-12  
RKP-1UI or RKP-1UT  
12V  
RCP-2000-24  
RCP-2000-48  
OUTPUT VOLTAGE  
24V  
48V  
OUTPUT  
INPUT  
MAX. OUTPUT CURRENT  
300A  
240A  
5760W  
126A  
6048W  
MAX. OUTPUT POWER Note.6 3600W  
VOLTAGE RANGE  
Note.5 90 ~ 264VAC  
127 ~ 370VDC  
7A/230VAC  
FREQUENCY RANGE  
AC CURRENT (Typ.)FOR EACH UNIT  
LEAKAGE CURRENT  
AUXILIARY POWER  
47 ~ 63Hz  
13A/115VAC  
<3.5mA / 230VAC  
16A/115VAC  
11A/230VAC  
16A/115VAC  
11A/230VAC  
5V @ 0.3A, 12V @ 0.8A  
By electrical signal or dry contact ON:short OFF:open  
REMOTE ON/OFF CONTROL  
Compensate voltage drop on the load wiring up to 0.5V. "Local Sense"should be connected in order to get the correct output voltage if the "Remote Sense"is not used  
The isolated TTL signal out, refer to function manual  
REMOTE SENSE  
DC OK SIGNAL  
FUNCTION  
The isolated TTL signal out, refer to function manual  
AC FAIL SIGNAL  
Adjustment of output voltage, possible between 90 ~ 110% of rated output  
Logic " High" for over temperature warning, refer to function manual, isolated signal  
The isolated TTL signal out, refer to function manual  
OUTPUT VOLTAGE TRIM  
OVER TEMP WARNING  
FAN FAIL SIGNAL  
WORKING TEMP.  
-40 ~ +70 (Refer to "Derating Curve")  
20 ~ 90% RH non-condensing  
WORKING HUMIDITY  
STORAGE TEMP., HUMIDITY  
-40 ~ +85 , 10 ~ 95% RH  
ENVIRONMENT  
TEMP. COEFFICIENT  
VIBRATION  
0.03%/ (0 ~ 50  
)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
UL60950-1, TUV EN60950-1 approved  
SAFETY STANDARDS  
WITHSTAND VOLTAGE  
ISOLATION RESISTANCE  
EMC EMISSION  
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC  
SAFETY &  
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH  
EMC  
(Note 4)  
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3  
EMC IMMUNITY  
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A  
DIMENSION  
Rack 483.6*350.8*44(L*W*H)  
11.5Kg; 1pcs/11.5Kg/2.67CUFT  
OTHERS  
NOTE  
PACKING  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.  
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.  
3. Tolerance : includes set up tolerance, line regulation and load regulation.  
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets  
EMC directives.  
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.  
6. Output of all the RCP-2000 modules are connected in parallel in the rack.  
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.  
It will go back to normal ripple level once the output load is more than 10%.  
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09  
2000~6000W Front End Power System  
RKP-1U Rack System  
Mechanical Specification (Rack System)  
Case No. 959A  
Unit:mm  
Fig1  
14  
1
25  
13  
ADDRESS  
SWITCH  
ADDRESS  
SWITCH  
ADDRESS  
SWITCH  
-
+
JK1  
CN500  
C
B
A
Fig2  
RKP-1UT  
FG  
N
L
FG  
N
L
FG  
N
L
8.2  
8.2  
8.2  
10  
10  
8
10  
8
1
1
8
ADDRESS  
SWITCH  
ADDRESS  
SWITCH  
ADDRESS  
SWITCH  
-
+
JK1  
CN500  
C
B
A
RKP-1UI  
Mounting Bracket  
IEC320-C20  
IEC320-C20  
IEC320-C20  
440  
SVR1  
SVR1  
SVR1  
22  
22  
46  
Air flow  
direction  
Module C  
Module B  
Module A  
10.2  
DC OK  
DC OK  
466.1  
DC OK  
483.6  
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09  
2000~6000W Front End Power System  
RKP-1U Rack System  
CN500 Pin No. Assignment  
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions  
Pin No. Assignment Pin No.  
Assignment  
FAN FAIL-A  
ON/OFF-B  
AC-OK-B  
DC-OK-B  
PV-B  
Pin No.  
Assignment  
T-ALARM-B  
FAN FAIL-B  
+5V-AUX  
Pin No.  
16  
Assignment  
ON/OFF-C  
AC-OK-C  
DC-OK-C  
PV-C  
Pin No.  
21  
Assignment  
ON/OFF-A  
AC-OK-A  
DC-OK-A  
PV-A  
FAN FAIL-C  
1
2
6
7
11  
12  
13  
14  
15  
+S  
-S  
17  
22  
8
3
4
5
18  
23  
9
+12V-AUX  
GND-AUX  
+V  
-V  
19  
24  
T-ALARM-A  
10  
T-ALARM-C  
20  
25  
JK1 Pin No. Assignment  
Connector Pin No. Assignment(CN ) : RJ45 8 positions  
Pin No. Assignment Pin No. Assignment Pin No.  
Assignment  
DA  
DB  
-V  
CONTROL  
NC  
7
8
SCL  
1
2
4
5
GND-AUX  
SDA  
3
6
CN500 IN/OUT Connector pins function description  
Pin No. Function  
Description  
Each unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B,C(pin 1,7,16) and  
+5V-AUX(pin 15). Short: ON, Open:OFF. (Note.2)  
1,7,16  
ON/OFF  
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms. (Note.2)  
High : When the Vout 80 5%. Low : When Vout 80 5%. (Note.2)  
2,8,17  
3,9,18  
AC-OK  
DC-OK  
PV  
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)  
4,10,19  
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.  
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)  
5,11,20  
6,12,21  
13  
T-ALARM  
FAN FAIL  
+5V-AUX  
High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)  
Auxiliary voltage output, 4.5 ~ 5.5V, referenced to GND-AUX (pin 15). The maximum load current is 0.3A. This output has the  
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.  
Auxiliary voltage output, 10.8 ~ 13.2V, referenced to GND-AUX (pin 15). The maximum load current is 0.8A. This output has the  
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.  
14  
+12V-AUX  
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).  
15  
22  
GND-AUX  
+S  
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted  
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.  
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted  
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.  
23  
-S  
Positive output voltage. For local sense use only, can't be connected directly to the load.  
Negative output voltage. For local sense use only, can't be connected directly to the load.  
24  
25  
+V  
-V  
JK1 IN/OUT Connector pins function description  
Pin No.  
Function  
DA,DB  
-V  
Description  
1,2  
3
Differential digital signal for parallel control. (Note.1)  
Negative output voltage. For parallel control, can't be connected directly to the load.  
4
CONTROL Remote ON/OFF control pin used in the PMBus interface. (Note.2)  
5
NC  
Not use.  
6
SDA  
SCL  
Serial Data used in the PMBus interface. (Note.2)  
Serial Clock used in the PMBus interface. (Note.2)  
7
8
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).  
Note.1: Non-isolated signal, referenced to the output terminals (-V).  
Note.2: Isolated signal, referenced to GND-AUX.  
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09  
2000~6000W Front End Power System  
RKP-1U Rack System  
Function Manual  
1. Remote ON/OFF Control  
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.  
1
7
16  
1
7
16  
ON/OFF A  
ON/OFF B  
ON/OFF C  
ON/OFF A  
ON/OFF B  
ON/OFF C  
Between ON/OFF and +5V-AUX Output  
RKP-1U  
RKP-1U  
SW Open  
SW Short  
OFF  
ON  
13  
13  
+5V-AUX  
+5V-AUX  
2. Voltage Drop Compensation  
2.1 Remote Sense  
The remote sense compensates voltage drop on the load wiring up to 0.5V.  
+V  
+S  
+V  
22  
23  
RKP-1U  
LOAD  
-S  
-V  
-V  
Sense lines should be twisted in pairs  
2.2 Local Sense  
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.  
24  
+V  
22  
+S  
RKP-1U  
25  
23  
-V  
-S  
3. Output Voltage TRIM  
(1)Connecting an external DC source between PV(4,10,19) and -V(25) on CN500 that is shown in Fig. 3.1.  
(2)Adjustment of output voltage is possible between 90~110%(Typ.) of the rated output which is shown in Fig. 3.2. Reducing output current is required when the  
output voltage is trimmed up.  
Vout  
100  
110  
90  
100  
4,10,19  
PV  
-V  
80  
70  
60  
90  
80  
70  
60  
0~5V  
25  
Fig. 3.1 Add on 0~5V external voltage  
V
V
0
0.5  
1.5  
3
4.5  
5
70  
80  
90  
100  
110  
EXTERNAL VOLTAGE(DC)  
OUTPUT VOLTAGE (%)  
Fig. 3.2 Output voltage trimming  
4. Front Panel Indicators & Corresponding Signal at Function Pins  
*
Function  
LED  
Signal  
PSU Output  
Description  
AC-OK GREEN  
0 ~ 0.5V  
4.5 ~ 5.5V  
0 ~ 0.5V  
ON  
When input voltage 87V  
When input voltage 75V  
AC-NG  
RED  
OFF  
ON  
DC-OK GREEN  
When output voltage 80% 5% of Vo rated.  
DC-NG  
T-OK  
RED  
4.5 ~ 5.5V  
0 ~ 0.5V  
When output voltage 80% 5% of Vo rated.  
ON  
GREEN  
When the internal temperature (TSW1 & TSW2 short) is within safe limit  
ON  
T-ALARM RED  
4.5 ~ 5.5V  
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm  
OFF  
*Signal between function pin and "GND-AUX".  
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09  
2000~6000W Front End Power System  
RKP-1U Rack System  
5.PMBus communication interface  
5.1 Interface specification  
RCP-2000 support PMBus Rev.1.1 with maximum 100kHz bus speed.  
5.2 Device Address (A0~A4)  
MSB  
1
LSB  
0
A4 A3 A2 A1 A0  
The device address can be defined by using DIP switch and shows below. The DIP switch down position is logic "1" and up position is logic "0".  
1 2 3 4 5  
ON  
DIP switch position  
DIP switch position  
Module  
No.  
Module  
No.  
1
2
3
4
5
1
2
3
4
5
0
1
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
ON  
2
OFF  
OFF  
ON  
ON  
ON  
OFF  
OFF  
ON  
ON  
ON  
3
OFF  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
4
OFF  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
5
OFF  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
6
OFF  
OFF  
ON  
ON  
OFF  
OFF  
ON  
ON  
7
OFF  
ON  
ON  
OFF  
ON  
ON  
8
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
9
OFF  
ON  
ON  
ON  
OFF  
ON  
ON  
ON  
10  
11  
12  
13  
14  
15  
OFF  
OFF  
ON  
ON  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
5.3 Command Summary (ref. to PMBus Rev.1.1)  
Command  
Code  
Command  
Name  
Transaction  
Type  
# of data  
Bytes  
Description  
01h  
02h  
19h  
OPERATION  
R/W Byte  
Read Byte  
Read Byte  
1
1
1
Remote ON/OFF control  
ON/OFF function configuration  
Capabilities of a PMBus device  
ON_OFF_CONFIG  
CAPABILITY  
Define data format for output voltage  
(format: Linear, N= -9)  
20h  
21h  
VOUT_MODE  
R Byte  
1
2
Output voltage setting value  
(format: Linear, N= -9)  
VOUT_COMMAND  
R Word  
Output voltage trimming value  
(format: Linear, N= -9)  
22h  
46h  
47h  
VOUT_TRIM  
R/W Word  
R/W Word  
R Byte  
2
2
1
Output overcurrent setting value  
IOUT_OC_FAULT_LIMIT  
IOUT_OC_FAULT_RESPONSE  
Define protection and response when an  
output overcurrent fault occurred  
79h  
7Ah  
7Bh  
7Ch  
7Dh  
STATUS_WORD  
STATUS_VOUT  
STATUS_IOUT  
R Word  
R Byte  
R Byte  
R Byte  
R Byte  
2
1
1
1
1
Summary status reporting  
Output voltage status reporting  
Output current status reporting  
AC inpit voltage statusreporting  
Temperature status reporting  
STATUS_INPUT  
STATUS_TEMPERATURE  
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09  
2000~6000W Front End Power System  
RKP-1U Rack System  
Command  
Code  
Command  
Name  
Transaction  
Type  
# of data  
Description  
Bytes  
80h  
81h  
STATUS_MFR_SPECIFIC  
STATUS_FANS_1_2  
R Byte  
R Byte  
1
1
Manufacture specific status reporting  
Fan1 and 2 status reporting  
AC input voltage reading value  
(format: Linear, N=-1)  
88h  
8Bh  
8Ch  
8Dh  
90h  
91h  
98h  
READ_VIN  
R Word  
R Word  
R Word  
R Word  
R Word  
R Word  
R Byte  
2
2
2
2
2
2
1
Output voltage reading value  
(format: Linear, N= -9)  
READ_VOUT  
Output current reading value  
(format: Linear, N= -3)  
READ_IOUT  
Temperature 1 reading value  
(format: Linear, N= -3)  
READ_TEMPERATURE_1  
READ_FAN_SPEED_1  
READ_FAN_SPEED_2  
PMBUS_REVISION  
Fan speed 1 reading value  
(format: Linear, N= 4)  
Fan speed 2 reading value  
(format: Linear, N= 4)  
The compliant revision of the PMBus  
(default: 11h for Rev. 1.1)  
99h  
9Ah  
9Bh  
9Ch  
9Dh  
9Eh  
MFR_ID  
Block Read  
Block Read  
Block Read  
Block R/W  
Block R/W  
Block R/W  
12  
12  
6
Manufacturer's name  
MFR_MODEL  
MFR_REVISION  
MFR_LOCATION  
MFR_DATE  
Manufacturer's model name  
Firmware revision  
3
Manufacturer's factory location  
Manufacture date. (format: YYMMDD)  
Product serial number  
6
MFR_SERIAL  
12  
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09  

相关型号:

RKP-6K1U-24

2000~6000W Front End Power System
MEANWELL

RKP-6K1U-48

2000~6000W Front End Power System
MEANWELL

RKP-CMU1

1U Rack Control and Monitoring Unit
MEANWELL

RKP-CMU1_12

1U Rack Control and Monitoring Unit
MEANWELL

RKP200KN

Silicon Epitaxial Planar Pin Diode for Antenna Switching
RENESAS

RKP200KP

Silicon Epitaxial Planar Pin Diode for Antenna Switching
RENESAS

RKP201KK

Silicon Epitaxial Trench Pin Diode for Antenna Switching
RENESAS

RKP201KL

Silicon Epitaxial Trench Pin Diode for Antenna Switching
RENESAS

RKP201KM

Silicon Epitaxial Trench Pin Diode for Antenna Switching
RENESAS

RKP201KN

Silicon Epitaxial Trench Pin Diode for Antenna Switching
RENESAS

RKP202KN

Silicon Epitaxial Trench Pin Diode for Antenna Switching
RENESAS

RKP203KN

Silicon Epitaxial Trench Pin Diode for Antenna Switching
RENESAS