2000~6000W Front End Power System
RKP-1U Rack System
Features :
Universal AC input / Full range
Holds up to 3 power modules
Active current sharing up to 6000W(3 unit) in one 19rack, 3 rack max.
can be operated in parallel (up to 9 units)
PMBus serial interface
IEC320-C20 or terminal block input
Front-end & rectifier applications
Stackable for system expansion
Low profile: 1U height, 19 rack mount
Hot swappable modules
Output voltage trimming function
3 years warranty
Description :
RCP-2000 rack power system is an advanced 19 rack-mounted power system containing up to 3 hot-swappable RCP-2000 rectifiers and
can deliver up to 6000W in the single rack. Up to 3 racks can be stacked to provide expanded total system capability up to 18,000W that
are especially suitable for the application of servers, information technology equipment, networking, telecommunications, and wide
range of industrial applications using distributed power architecture. Equipped with PMBus communication protocol, RCP-2000 rack
system can be controlled or monitored by external device such as monitoring unit (RCP-CMU-1) or PC.
SELECTION GUIDE
I
C 12
-
Output voltage
Rack: RKP-1U I
C
Whole System: RKP-6K1U
C: With RCP-CMU-1
: Without RCP-CMU-1
C: With RCP-CMU-1
: Without RCP-CMU-1
I: AC Inlet (IEC320-C20)
T: Terminal block
I: AC Inlet
T: Terminal
SPECIFICATION - Rack System
MODEL
RKP-6K1U -12
RKP-6K1U -24
RKP-6K1U -48
MODULE
RACK
RCP-2000-12
RKP-1UI or RKP-1UT
12V
RCP-2000-24
RCP-2000-48
OUTPUT VOLTAGE
24V
48V
OUTPUT
INPUT
MAX. OUTPUT CURRENT
300A
240A
5760W
126A
6048W
MAX. OUTPUT POWER Note.6 3600W
VOLTAGE RANGE
Note.5 90 ~ 264VAC
127 ~ 370VDC
7A/230VAC
FREQUENCY RANGE
AC CURRENT (Typ.)FOR EACH UNIT
LEAKAGE CURRENT
AUXILIARY POWER
47 ~ 63Hz
13A/115VAC
<3.5mA / 230VAC
16A/115VAC
11A/230VAC
16A/115VAC
11A/230VAC
5V @ 0.3A, 12V @ 0.8A
By electrical signal or dry contact ON:short OFF:open
REMOTE ON/OFF CONTROL
Compensate voltage drop on the load wiring up to 0.5V. "Local Sense"should be connected in order to get the correct output voltage if the "Remote Sense"is not used
The isolated TTL signal out, refer to function manual
REMOTE SENSE
DC OK SIGNAL
FUNCTION
The isolated TTL signal out, refer to function manual
AC FAIL SIGNAL
Adjustment of output voltage, possible between 90 ~ 110% of rated output
Logic " High" for over temperature warning, refer to function manual, isolated signal
The isolated TTL signal out, refer to function manual
OUTPUT VOLTAGE TRIM
OVER TEMP WARNING
FAN FAIL SIGNAL
WORKING TEMP.
-40 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
-40 ~ +85 , 10 ~ 95% RH
ENVIRONMENT
TEMP. COEFFICIENT
VIBRATION
0.03%/ (0 ~ 50
)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.7KVDC
SAFETY &
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMC
(Note 4)
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
DIMENSION
Rack 483.6*350.8*44(L*W*H)
11.5Kg; 1pcs/11.5Kg/2.67CUFT
OTHERS
NOTE
PACKING
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. Output of all the RCP-2000 modules are connected in parallel in the rack.
7. Under parallel operation of more than one rack connecting together, ripple of the output voltage may be higher than the SPEC at light load condition.
It will go back to normal ripple level once the output load is more than 10%.
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
Mechanical Specification (Rack System)
Case No. 959A
Unit:mm
Fig1
14
1
25
13
ADDRESS
SWITCH
ADDRESS
SWITCH
ADDRESS
SWITCH
-
+
JK1
CN500
C
B
A
Fig2
RKP-1UT
FG
N
L
FG
N
L
FG
N
L
8.2
8.2
8.2
10
10
8
10
8
1
1
8
ADDRESS
SWITCH
ADDRESS
SWITCH
ADDRESS
SWITCH
-
+
JK1
CN500
C
B
A
RKP-1UI
Mounting Bracket
IEC320-C20
IEC320-C20
IEC320-C20
440
SVR1
SVR1
SVR1
22
22
46
Air flow
direction
Module C
Module B
Module A
10.2
DC OK
DC OK
466.1
DC OK
483.6
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
CN500 Pin No. Assignment
Connector Pin No. Assignment(CN500) : D-Type Right Angle 25 positions
Pin No. Assignment Pin No.
Assignment
FAN FAIL-A
ON/OFF-B
AC-OK-B
DC-OK-B
PV-B
Pin No.
Assignment
T-ALARM-B
FAN FAIL-B
+5V-AUX
Pin No.
16
Assignment
ON/OFF-C
AC-OK-C
DC-OK-C
PV-C
Pin No.
21
Assignment
ON/OFF-A
AC-OK-A
DC-OK-A
PV-A
FAN FAIL-C
1
2
6
7
11
12
13
14
15
+S
-S
17
22
8
3
4
5
18
23
9
+12V-AUX
GND-AUX
+V
-V
19
24
T-ALARM-A
10
T-ALARM-C
20
25
JK1 Pin No. Assignment
Connector Pin No. Assignment(CN ) : RJ45 8 positions
Pin No. Assignment Pin No. Assignment Pin No.
Assignment
DA
DB
-V
CONTROL
NC
7
8
SCL
1
2
4
5
GND-AUX
SDA
3
6
CN500 IN/OUT Connector pins function description
Pin No. Function
Description
Each unit can separately turn the output on and off by electrical signal or dry contact between ON/OFF A,B,C(pin 1,7,16) and
+5V-AUX(pin 15). Short: ON, Open:OFF. (Note.2)
1,7,16
ON/OFF
Low : When the input voltage is 87Vrms. High : when the input voltage in 75Vrms. (Note.2)
High : When the Vout 80 5%. Low : When Vout 80 5%. (Note.2)
2,8,17
3,9,18
AC-OK
DC-OK
PV
Connection for output voltage trimming. The voltage can be trimmed within its defined range. (Note.1)
4,10,19
High : When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm.
Low : When the internal temperature (TSW1 or TSW2 short) under the limit temperature. (Note.2)
5,11,20
6,12,21
13
T-ALARM
FAN FAIL
+5V-AUX
High : When the internal fan fail. Low : When the internal fan is normal. (Note.2)
Auxiliary voltage output, 4.5 ~ 5.5V, referenced to GND-AUX (pin 15). The maximum load current is 0.3A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
Auxiliary voltage output, 10.8 ~ 13.2V, referenced to GND-AUX (pin 15). The maximum load current is 0.8A. This output has the
built-in "Oring diodes" and is not controlled by the remote ON/OFF control.
14
+12V-AUX
Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
15
22
GND-AUX
+S
Positive sensing. The +S signal should be connected to the positive terminal of the load. The +S and -S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
Negative sensing. The -S signal should be connected to the negative terminal of the load. The -S and +S leads should be twisted
in pair to minimize noise pick-up effect. The maximum line drop compensation is 0.5V.
23
-S
Positive output voltage. For local sense use only, can't be connected directly to the load.
Negative output voltage. For local sense use only, can't be connected directly to the load.
24
25
+V
-V
JK1 IN/OUT Connector pins function description
Pin No.
Function
DA,DB
-V
Description
1,2
3
Differential digital signal for parallel control. (Note.1)
Negative output voltage. For parallel control, can't be connected directly to the load.
4
CONTROL Remote ON/OFF control pin used in the PMBus interface. (Note.2)
5
NC
Not use.
6
SDA
SCL
Serial Data used in the PMBus interface. (Note.2)
Serial Clock used in the PMBus interface. (Note.2)
7
8
GND-AUX Auxiliary voltage output GND. The signal return is isolated from the output terminals (+V & -V).
Note.1: Non-isolated signal, referenced to the output terminals (-V).
Note.2: Isolated signal, referenced to GND-AUX.
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
Function Manual
1. Remote ON/OFF Control
The PSU can be turned ON/OFF together or separately by using the "Remote ON/OFF" function.
1
7
16
1
7
16
ON/OFF A
ON/OFF B
ON/OFF C
ON/OFF A
ON/OFF B
ON/OFF C
Between ON/OFF and +5V-AUX Output
RKP-1U
RKP-1U
SW Open
SW Short
OFF
ON
13
13
+5V-AUX
+5V-AUX
2. Voltage Drop Compensation
2.1 Remote Sense
The remote sense compensates voltage drop on the load wiring up to 0.5V.
+V
+S
+V
22
23
RKP-1U
LOAD
-S
-V
-V
Sense lines should be twisted in pairs
2.2 Local Sense
Notice : The +S,-S have to be connected to the +V,-V terminals locally in order to get the correct output voltage if the remote sensing is not used.
24
+V
22
+S
RKP-1U
25
23
-V
-S
3. Output Voltage TRIM
(1)Connecting an external DC source between PV(4,10,19) and -V(25) on CN500 that is shown in Fig. 3.1.
(2)Adjustment of output voltage is possible between 90~110%(Typ.) of the rated output which is shown in Fig. 3.2. Reducing output current is required when the
output voltage is trimmed up.
Vout
100
110
90
100
4,10,19
PV
-V
80
70
60
90
80
70
60
0~5V
25
Fig. 3.1 Add on 0~5V external voltage
V
V
0
0.5
1.5
3
4.5
5
70
80
90
100
110
EXTERNAL VOLTAGE(DC)
OUTPUT VOLTAGE (%)
Fig. 3.2 Output voltage trimming
4. Front Panel Indicators & Corresponding Signal at Function Pins
*
Function
LED
Signal
PSU Output
Description
AC-OK GREEN
0 ~ 0.5V
4.5 ~ 5.5V
0 ~ 0.5V
ON
When input voltage 87V
When input voltage 75V
AC-NG
RED
OFF
ON
DC-OK GREEN
When output voltage 80% 5% of Vo rated.
DC-NG
T-OK
RED
4.5 ~ 5.5V
0 ~ 0.5V
When output voltage 80% 5% of Vo rated.
ON
GREEN
When the internal temperature (TSW1 & TSW2 short) is within safe limit
ON
T-ALARM RED
4.5 ~ 5.5V
When the internal temperature (TSW1 or TSW2 open) exceeds the limit of temperature alarm
OFF
*Signal between function pin and "GND-AUX".
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
5.PMBus communication interface
5.1 Interface specification
RCP-2000 support PMBus Rev.1.1 with maximum 100kHz bus speed.
5.2 Device Address (A0~A4)
MSB
1
LSB
0
A4 A3 A2 A1 A0
The device address can be defined by using DIP switch and shows below. The DIP switch down position is logic "1" and up position is logic "0".
1 2 3 4 5
ON
DIP switch position
DIP switch position
Module
No.
Module
No.
1
2
3
4
5
1
2
3
4
5
0
1
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
ON
ON
ON
ON
OFF
ON
ON
ON
ON
2
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
ON
3
OFF
ON
ON
ON
OFF
ON
ON
ON
4
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
5
OFF
ON
ON
ON
OFF
ON
ON
ON
6
OFF
OFF
ON
ON
OFF
OFF
ON
ON
7
OFF
ON
ON
OFF
ON
ON
8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
9
OFF
ON
ON
ON
OFF
ON
ON
ON
10
11
12
13
14
15
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
5.3 Command Summary (ref. to PMBus Rev.1.1)
Command
Code
Command
Name
Transaction
Type
# of data
Bytes
Description
01h
02h
19h
OPERATION
R/W Byte
Read Byte
Read Byte
1
1
1
Remote ON/OFF control
ON/OFF function configuration
Capabilities of a PMBus device
ON_OFF_CONFIG
CAPABILITY
Define data format for output voltage
(format: Linear, N= -9)
20h
21h
VOUT_MODE
R Byte
1
2
Output voltage setting value
(format: Linear, N= -9)
VOUT_COMMAND
R Word
Output voltage trimming value
(format: Linear, N= -9)
22h
46h
47h
VOUT_TRIM
R/W Word
R/W Word
R Byte
2
2
1
Output overcurrent setting value
IOUT_OC_FAULT_LIMIT
IOUT_OC_FAULT_RESPONSE
Define protection and response when an
output overcurrent fault occurred
79h
7Ah
7Bh
7Ch
7Dh
STATUS_WORD
STATUS_VOUT
STATUS_IOUT
R Word
R Byte
R Byte
R Byte
R Byte
2
1
1
1
1
Summary status reporting
Output voltage status reporting
Output current status reporting
AC inpit voltage statusreporting
Temperature status reporting
STATUS_INPUT
STATUS_TEMPERATURE
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
2000~6000W Front End Power System
RKP-1U Rack System
Command
Code
Command
Name
Transaction
Type
# of data
Description
Bytes
80h
81h
STATUS_MFR_SPECIFIC
STATUS_FANS_1_2
R Byte
R Byte
1
1
Manufacture specific status reporting
Fan1 and 2 status reporting
AC input voltage reading value
(format: Linear, N=-1)
88h
8Bh
8Ch
8Dh
90h
91h
98h
READ_VIN
R Word
R Word
R Word
R Word
R Word
R Word
R Byte
2
2
2
2
2
2
1
Output voltage reading value
(format: Linear, N= -9)
READ_VOUT
Output current reading value
(format: Linear, N= -3)
READ_IOUT
Temperature 1 reading value
(format: Linear, N= -3)
READ_TEMPERATURE_1
READ_FAN_SPEED_1
READ_FAN_SPEED_2
PMBUS_REVISION
Fan speed 1 reading value
(format: Linear, N= 4)
Fan speed 2 reading value
(format: Linear, N= 4)
The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
99h
9Ah
9Bh
9Ch
9Dh
9Eh
MFR_ID
Block Read
Block Read
Block Read
Block R/W
Block R/W
Block R/W
12
12
6
Manufacturer's name
MFR_MODEL
MFR_REVISION
MFR_LOCATION
MFR_DATE
Manufacturer's model name
Firmware revision
3
Manufacturer's factory location
Manufacture date. (format: YYMMDD)
Product serial number
6
MFR_SERIAL
12
File Name:RKP-1U RACK SYSTEM-SPEC 2011-05-09
相关型号: