RSP-2400 [MEANWELL]

2400W Single Output Power Supply; 2400W单路输出电源
RSP-2400
型号: RSP-2400
厂家: MEAN WELL ENTERPRISES CO., LTD.    MEAN WELL ENTERPRISES CO., LTD.
描述:

2400W Single Output Power Supply
2400W单路输出电源

文件: 总6页 (文件大小:433K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
2400W Single Output Power Supply  
RSP-2400 series  
Features :  
AC input 180 ~ 264VAC  
AC input active surge current limiting  
High efficiency up to 91%  
Built-in active PFC function,PF>0.95  
Protections: Short circuit / Overload / Over voltage / Over temperature  
/ Fan alarm  
Forced air cooling by built-in DC with fan speed control function  
Output voltage can be trimmed between 20~110% of the rated output voltage  
High power density 12.5W/inch3  
Current sharing up to 3 units  
Alarm signal output (relay contact and TTL signal)  
Built-in 12V/0.1A auxiliary output for remote control  
Built-in remote ON-OFF control  
Built-in remote sense function  
3 years warranty  
SPECIFICATION  
MODEL  
RSP-2400-12  
RSP-2400-24  
RSP-2400-48  
DC VOLTAGE  
RATED CURRENT  
12V  
24V  
48V  
166.7A  
0 ~ 166.7A  
2000.4W  
100A  
50A  
CURRENT RANGE  
RATED POWER  
0 ~ 100A  
2400W  
150mVp-p  
22 ~ 28V  
1.0%  
0 ~ 50A  
2400W  
200mVp-p  
43 ~ 56V  
1.0%  
RIPPLE & NOISE (max.) Note.2 150mVp-p  
VOLTAGE ADJ. RANGE  
VOLTAGE TOLERANCE Note.3 1.0%  
OUTPUT  
10.8 ~ 13.2V  
LINE REGULATION  
LOAD REGULATION  
SETUP, RISE TIME  
HOLD UP TIME (Typ.)  
0.5%  
0.5%  
0.5%  
0.5%  
0.5%  
0.5%  
1000ms, 80ms at full load  
12ms at full load  
VOLTAGE RANGE  
180 ~ 264VAC  
47 ~ 63Hz  
254 ~ 370VDC  
FREQUENCY RANGE  
POWER FACTOR (Typ.)  
EFFICIENCY (Typ.)  
0.95/230VAC at full load  
87%  
INPUT  
90%  
91.5%  
15.5A/180VAC  
12A/230VAC  
AC CURRENT (Typ.)  
INRUSH CURRENT (Typ.)  
60A/230VAC  
LEAKAGE CURRENT  
<2.0mA / 240VAC  
100 ~ 112% rated output power  
OVERLOAD  
User adjustable continuous constant current limiting or constant current limiting with delay shutdown after 5 seconds, re-power on to recover  
13.8 ~ 16.8V 28.8 ~ 33.6V 57.6 ~ 67.2V  
Protection type : Shut down o/p voltage, re-power on to recover  
PROTECTION OVER VOLTAGE  
95  
95  
5
5
(12V), 100  
(12V), 85  
5
(24V,48V) (TSW1: detect on heatsink of power transistor)  
(24V), 80 (48V) (TSW2 : detect on heatsink of o/p diode)  
5
5
OVER TEMPERATURE  
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down  
12V@0.1A(Only for Remote ON/OFF control)  
AUXILIARY POWER(AUX)  
REMOTE ON/OFF CONTROL  
ALARM SIGNAL OUTPUT  
Please see the Function Manual  
Please see the Function Manual  
FUNCTION  
2.4 ~ 13.2V  
4.8 ~ 28V  
9.6 ~ 56V  
OUTPUT VOLTAGE TRIM  
CURRENT SHARING  
Please see the Function Manual  
-20 ~ +70 (Refer to output load derating curve)  
20~90% RH non-condensing  
WORKING TEMP.  
WORKING HUMIDITY  
STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH  
ENVIRONMENT  
TEMP. COEFFICIENT  
VIBRATION  
0.05%/ (0 ~ 50  
)
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes  
UL60950-1, TUV EN60950-1 approved  
SAFETY STANDARDS  
WITHSTAND VOLTAGE  
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC  
SAFETY &  
ISOLATION RESISTANCE  
EMI CONDUCTION & RADIATION  
HARMONIC CURRENT  
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH  
Compliance to EN55022 (CISPR22)  
EMC  
(Note 4)  
Compliance to EN61000-3-2,-3  
EMS IMMUNITY  
MTBF  
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A  
106.7K hrs min. MIL-HDBK-217F (25  
278*177.8*63.5mm (L*W*H)  
)
OTHERS  
NOTE  
DIMENSION  
PACKING  
3.3Kg; 4pcs/14.2Kg/1.89CUFT  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.  
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.  
3. Tolerance : includes set up tolerance, line regulation and load regulation.  
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets  
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”  
(as available on http://www.meanwell.com)  
File Name:RSP-2400-SPEC 2010-10-18  
2400W Single Output Power Supply  
RSP-2400 series  
Mechanical Specification  
Case No.982B  
Unit:mm  
278  
236.3  
27  
40  
CN1 CN2 CN3  
8 6 4 2 8 6 4 2 10 8 6 4 2  
7 5 3 1 7 5 3 1 9 7 5 3 1  
8-M4(Both Sides) L=5mm  
236.3  
27  
OUTPUT  
4-M4 L=5mm  
+V  
-V  
CN1 CN2 CN3  
8
7
6 4  
5 3  
2
1
8
7
6
5
4
3
2
1
10 8  
9 7  
6
5
4
3
2
1
Air flow  
direction  
INPUT  
16max.  
AC Input Terminal Pin No. Assignment  
Pin No. Assignment  
Control Pin No. Assignment(CN1,CN2) : HRS DF11-8DP-2DS or equivalent  
Pin No. Assignment Pin No. Assignment Mating Housing  
Terminal  
1
2
3
AC/L  
AC/N  
FG  
RCG  
RC  
-S  
CS(Current Share)  
+S  
1
2
5,7  
6
HRS DF11-8DS HRS DF11-**SC  
or equivalent or equivalent  
PV  
8
3
4
PS  
RCG: Remote ON/OFF Ground  
RC : Remote ON/OFF  
-S : -Remote Sensing  
CS: Load Share  
PV :Output Voltage External Control  
PS : Reference Voltage Terminal  
+S: +Remote Sensing  
Control Pin No. Assignment(CN3) : HRS DF11-10DP-2DS or equivalent  
Pin No. Assignment Pin No. Assignment Pin No. Assignment Pin No. Assignment  
Mating Housing  
Terminal  
P OK GND  
P OK  
P OK2  
RCG  
RC  
AUXG  
AUX  
OL-SD  
1
2
3
4
5
6
7
8
9
10  
HRS DF11-10DS HRS DF11-**SC  
or equivalent or equivalent  
P OK GND2  
OLP  
P OK GND: Power OK Ground  
RCG: Remote ON/OFF Ground  
RC: Remote ON/OFF  
AUX: Auxiliary Output  
OLP: OLP mode select  
P OK: Power OK Signal (Relay Contact)  
P OK2: Power OK Signal (TTL Signal)  
AUXG: Auxiliary Ground  
OL-SD: OLP mode select  
PFC fosc : 88KHz  
Block Diagram  
PWM fosc : 100KHz  
+S  
ACTIVE  
RECTIFIERS  
&
FILTER  
RECTIFIERS  
POWER  
SWITCHING  
+V  
-V  
EMI  
FILTER  
INRUSH  
CURRENT  
LIMITING  
I/P  
&
PFC  
-S  
PFC  
CONTROL  
O.V.P.  
O.L.P.  
PWM  
CONTROL  
DETECTION  
CIRCUIT  
O.T.P.  
P OK  
RC  
REMOTE  
CONTROL  
LOAD  
SHARING  
CS  
FAN  
AUX  
POWER  
RECTIFIERS  
&
FILTER  
AUX POWER  
(12V/0.1A)  
File Name:RSP-2400-SPEC 2010-10-18  
2400W Single Output Power Supply  
RSP-2400 series  
Derating Curve  
Static Characteristics  
Ta=25  
100  
80  
100  
90  
60  
50  
40  
80  
70  
20  
60  
-20  
0
10  
20  
30  
40  
50  
60  
70 (HORIZONTAL)  
180 185 190 195 200 210 220 230 240 250 264  
AMBIENT TEMPERATURE (  
)
INPUT VOLTAGE (V) 60Hz  
Function Manual  
1.Remote ON/OFF  
(1)Remote ON/OFF control becomes available by applying voltage in CN1 & CN2 & CN3.  
(2)Table 1.1 shows the specification of Remote ON/OFF function.  
(3)Fig.1.2 shows the example to connect Remote ON/OFF control function.  
Table 1.1 Specification of Remote ON/OFF  
Connection Method  
Output on  
Fig. 1.2(A)  
SW Open  
SW Close  
Fig. 1.2(B)  
SW Open  
SW Close  
Fig. 1.2(C)  
SW Close  
SW Open  
SW Logic  
Output off  
Fig.1.2 Examples of connecting remote ON/OFF  
(A)Using external voltage source  
(B)Using internal 12V auxiliary output  
AUX  
AUX  
12V  
1K  
1K  
RC  
RC  
12V typ.  
12V typ.  
SW  
RCG  
RCG  
SW  
AUXG  
AUXG  
(C)Using internal 12V auxiliary output  
AUX  
RC  
1K  
1K  
12V typ.  
SW  
RCG  
AUXG  
File Name:RSP-2400-SPEC 2010-10-18  
2400W Single Output Power Supply  
RSP-2400 series  
2.Alarm Signal Output  
(1)Alarm signal is sent out through "P OK" & "P OK GND" and P OK2 & P OK GND2 pins.  
(2)An external voltage source is required for this function.  
(3)Table 2.1 explains the alarm function built-in the power supply.  
Function  
Description  
Output of alarm(P OK, Relay Contact) Output of alarm(P OK2, TTL Signal)  
The signal is "Low" when the power supply is above  
80% of the rated output voltage-Power OK  
Low (0.5V max at 500mA)  
Low (0.5V max at 10mA)  
P OK  
The signal turns to be "High" when the power supply High or open High or open  
is under 80% of the rated output voltage-Power Fail (External applied voltage, 500mA max.) (External applied voltage, 10mA max.)  
Table 2.1 Explanation of alarm  
P OK  
P OK2  
R
R
0.1uF  
V
V
P OK GND  
External voltage and R  
P OK GND2  
External voltage and R  
(The max. sink is 500mA and 20V)  
(The max. sink is 10mA and 30V)  
Fig. 2.2 Internal circuit of P OK (Relay, total is 10W)  
Fig. 2.3 Internal circuit of P OK2 (Open collector method)  
3.Output Voltage TRIM  
(1)Connecting an external DC source between PV and-S on CN1 or CN2 that is shown in Fig. 3.1.  
(2)Adjustment of output voltage is possible between 20~110%(Typ.) of the rated output which is shown in Fig. 3.2. Reducing output current is required when the  
output voltage is trimmed up.  
Vout  
OVP >120%  
120  
100  
80  
100  
80  
Non-Linear  
PV  
-S  
60  
40  
60  
40  
1~6V  
20  
20  
Fig. 3.1 Add on 1~6V external voltage  
V
V
1
2
3
4
5
6
20 40  
60  
80  
100  
120  
EXTERNAL VOLTAGE (DC)  
OUTPUT VOLTAGE (%)  
Fig. 3.2 Output voltage trimming  
File Name:RSP-2400-SPEC 2010-10-18  
2400W Single Output Power Supply  
RSP-2400 series  
4.Current Sharing  
(1)Parallel operation is available by connecting the units shown as below  
(+S,-S and CS are connected mutually in parallel):  
(2)The voltage difference among each output should be minimized that less than 2% is required.  
(3)The total output current must not exceed the value determined by the following equation.  
(Output current at parallel operation)=(The rated current per unit) x (Number of unit) x 0.9  
(4) In parallel operation 3 units is the maximum, please consult the manufacturer for other applications.  
(5) When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit.  
(6) Wires of remote sensing should be kept at least 10 cm from input wires.  
No.1(Master)  
+V  
CN1  
+S  
-S  
CS  
-V  
+S  
-S  
CS  
CN2  
AC/L AC/N  
+S  
+V  
Load  
-V  
No.2(Slave)  
-S  
+V  
CN1  
+S  
-S  
CS  
-V  
+S  
-S  
CS  
CN2  
AC/L AC/N  
No.3(Slave)  
+V  
CN1  
+S  
-S  
CS  
-V  
+S  
-S  
CS  
CN2  
AC/L AC/N  
(7) Under parallel operation, the "output voltage trim" function is not available.  
(8) When in parallel operation, the minimum output load should be greater than 2% of total output load (Min. Load >2% rated current per unit number of unit)  
5.Select O.L.P mode  
(1)Remove the shorting connector on CN3 that is shown in Fig 5.1, the O.L.P. mode will be "continuous constant current limiting".  
(2)Insert the shorting connector on CN3 that is shown in Fig 5.2, the O.L.P. mode will be "constant current limiting with delay shutdown after 5 seconds,  
re-power on to recover".  
OL-SD  
OLP  
OL-SD  
OLP  
Fig. 5.1 Remove the CN3  
Fig. 5.2 Insert the CN3  
OLP Mode : constant current limiting  
OLP Mode : constant current limiting with delay shutdown after 5 seconds  
File Name:RSP-2400-SPEC 2010-10-18  
2400W Single Output Power Supply  
RSP-2400 series  
6.Three Phase Connect  
FIG. A: 3 3W 220VAC SYSTEM (STANDARD MODEL FOR STOCK)  
R
R
S
T
L1  
FG1  
N1  
L2  
FG2  
N2  
L3  
FG3  
N3  
S
T
(NC)  
N
FG  
FIG. B: 3 4W 220/380VAC SYSTEM  
R
R
S
L1  
FG1  
N1  
L2  
FG2  
N2  
T
L3  
FG3  
N3  
N
S
N
FG  
T
FIG. C: 3 4W 190/110VAC SYSTEM  
R
R
S
T
L1  
FG1  
N1  
L2  
FG2  
N2  
N
(N.C.)  
L3  
FG3  
N3  
S
T
(NC)  
N
FG  
File Name:RSP-2400-SPEC 2010-10-18  

相关型号:

RSP-2400-12

2400W Single Output Power Supply
MEANWELL

RSP-2400-24

2400W Single Output Power Supply
MEANWELL

RSP-2400-48

2400W Single Output Power Supply
MEANWELL

RSP-2400_10

2400W Single Output Power Supply
MEANWELL

RSP-2400_1112

2400W Single Output Power Supply
MEANWELL

RSP-3000

3000W Single Output Power Supply
MEANWELL

RSP-3000-12

3000W Single Output Power Supply
MEANWELL

RSP-3000-24

3000W Single Output Power Supply
MEANWELL

RSP-3000-48

3000W Single Output Power Supply
MEANWELL

RSP-3000_10

3000W Single Output Power Supply
MEANWELL

RSP-3000_12

3000W Single Output Power Supply
MEANWELL

RSP-320

320W Single Output with PFC Function
MEANWELL