TN-3000-124 [MEANWELL]
3000W True Sine Wave DC-AC Inverter with Solar Charger; 3000W纯正弦波直流 - 交流逆变器与太阳能充电器型号: | TN-3000-124 |
厂家: | MEAN WELL ENTERPRISES CO., LTD. |
描述: | 3000W True Sine Wave DC-AC Inverter with Solar Charger |
文件: | 总4页 (文件大小:1975K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN-3000 series
Features :
True sine wave output (THD<3%)
High surge power up to 6000W
U.P.S. mode and energy saving mode (selectable)
High efficiency up to 92%
Power ON-OFF switch
Standby saving mode can be selectable
Front panel indicator for operation status
Thermostatically controlled cooling fan
Protections: Bat. low alarm / Bat. low shutdown / Over voltage / Over temp.
/ Output short / Input polarity reverse / Overload / AC circuit breaker
Application : Home appliance, power tools, office and portable
equipment, vehicle and yacht ...etc.
Built-in solar / AC charger
Optional monitoring software
3 years warranty
E13
SPECIFICATION
MODEL
TN-3000-112
TN-3000-124
TN-3000-148
TN-3000-212
TN-3000-224
TN-3000-248
RATED POWER (Typ.)
3000W
3000W
3000W
3000W
3000W
3000W
MAXIMUM OUTPUT POWER 3450W for 180 sec. / 4500W for 10 sec. / surge power 6000W for 30 cycles
Factory setting set at 110VAC
Factory setting set at 230VAC
AC VOLTAGE
100 / 110 / 115 / 120VAC selectable by setting button S.W
60 0.1Hz 50/60Hz selectable by setting button S.W
True sine wave (THD<3%) at rated input voltage
3%
200 / 220 / 230 / 240VAC selectable by setting button S.W
50 0.1Hz 50/60Hz selectable by setting button S.W
FREQUENCY
OUTPUT
WAVEFORM
AC REGULATION (Typ.)
TRANSFER TIME (Typ.)
SAVING MODE (Typ.)
FRONT PANEL INDICATOR
BAT. VOLTAGE
t<10ms inverter
Load 5W will be changed to standby mode
Battery voltage level, output load level, saving mode, fault and operation status
by pass
24V
48V
24V
48V
12V
12V
VOLTAGE RANGE
Note.5 10.5 ~ 15VDC
Note.3 300A
21 ~ 30VDC
150A
42 ~ 60VDC
75A
10.5 ~ 15VDC
300A
21 ~ 30VDC
150A
42 ~ 60VDC
75A
DC CURRENT (Typ.)
10W @ standby saving mode
INPUT
NO LOAD DISSIPATION (Typ.)
OFF MODE CURRENT DRAW
1mA
EFFICIENCY (Typ.)
BATTERY TYPES
FUSE
Note.1 88%
90%
91%
89%
91%
92%
Open & sealed Lead Acid
40A*12
40A*6
22.5V
21V
20A*6
45V
40A*12
11.3V
40A*6
22.5V
21V
20A*6
45V
BATTERY
INPUT
PROTECTION
11.3V
Note.5
BAT. LOW ALARM
10.5V
42V
10.5V
42V
BAT. LOW SHUTDOWN Note.5
REVERSE POLARITY
By internal fuse open
105
5
95
5
95
5
90
5
85
5
85
5
OVER TEMPERATURE
OUTPUT SHORT
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
105 ~ 115% load for 180 sec., 115% ~ 150% load for 10 sec.
Protection type : Shut down o/p voltage, re-power on to recover
AC input: 40A, AC output receptacle:15A
OUTPUT
PROTECTION
OVER LOAD (Typ.)
CIRCUIT BREAKER
GFCI PROCTECTION
AC input: 20A, AC output receptacle: 15A
None
Optional (Only type F)
WORKING TEMP.
Note.2
0 ~ +40 @ 100% load ; 60 @ 50% load
20% ~ 90% RH non-condensing
-30 ~ +70 / -22 ~ +158oF, 10 ~ 95% RH
WORKING HUMIDITY
ENVIRONMENT
STORAGE TEMP., HUMIDITY
VIBRATION
10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
None
UL458 (only for "GFCI" receptacle-Type F )
None
SAFETY STANDARDS
EN60950-1
LVD
SAFETY &
EMC
Bat I/P - AC I/P:3.0KVAC Bat I/P - AC O/P:3.0KVAC AC O/P - FG:1.5KVAC
WITHSTAND VOLTAGE
Compliance to EN55022 class A, 72/ 245/ CEE, 95/ 54/ CE, E-Mark
Compliance to EN61000-4-2,3,4,5,6,8,11 ENV50204
EMI CONDUCTION&RADIATION Compliance to FCC class A
None
25A
EMS IMMUNITY
12A
6A
12A
6A
CHARGE CURRENT (Typ.)
25A
AC
CHARGER
28.5V
45V
57V
75V
28.5V
45V
57V
75V
CHARGE VOLTAGE
MAX OPEN CIRCUIT VOLTAGE 25V
CHARGE CURRENT (max.) 30A
Note.5 14.3V
Note.5 14.3V
14.3V
25V
SOLAR
CHARGER
28.5V
57V
28.5V
57V
CHARGE VOLTAGE
CONTROL WIRING
DIMENSION
14.3V
RJ11 -RS232 (Option)
OTHERS
NOTE
466.8*283.5*100mm (L*W*H)
12.9Kg; 1pcs/14Kg/1.98CUFT
PACKING
1.Efficiency is tested by 2100W, linear load at 13V, 26V, 52V input voltage.
2.Output derating capacity referenced by curve 1.
3.DC current is tested by 3000W, linear load at 12V, 24V, 48V input voltage.
4.All parameters not specified above are measured at rated load, 25 of ambient temperature.
5.The tolerance of each voltage value by models is:112/212 0.5V;124/224 1V;148/248
2V
File Name:TN-3000-SPEC 2010-04-09
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN-3000 series
Instructions for TN-3000 monitoring software
1. Installation of TN-3000 unit and PC
5
9
4
8
3
7
2
6
1
1
6
Phone Jack
RJ11
DB9 FEMALE
RJ11
PIN NO.
DB9
2
3
3
5
4
2
PIN NO.
Figure 1
2. Explanation of Monitoring Manu
2.1 Main Page
Inverter TN V.1.1
Setting
Statistics
R.C. Power off
Pause
Exit
1
2
3
4
Solar Charge
INVERTER
100
100
0
AC Charge
0
Battery
5
Loading
O/P Voltage 110
V
Battery Voltage 54.1 V
O/P Frequency 60.0 Hz
Internal Temperature 10.0
TN-3000-212
AC In
By pass
Utility Voltage 0.0
V
Power on
Remote off
Battery low
6
Start Date 2010/01/01 03:13:33 PM
Reset Date 2010/01/01 01:40:56 PM
Battery used up
Stand by saving mode
Abnormal Shutdown
Figure 2
1. Setting: Adjustment for output voltage, charging related voltage, frequency, and operation mode. Please refer to Figure 3 for details.
2. Statistics: Calculate for the percentage of operating period for each operation mode. Please refer to Figure 4 for details.
3. R.C. Power off: Power can be turned ON or OFF at the remote location.
4. Pause: Stop refreshing the page of monitoring software.
5. Status of unit: Indicating current operating status of TN-3000.
6. Signals that display current condition of the unit.
File Name:TN-3000-SPEC 2010-04-09
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN-3000 series
2.2 Setting Page
Inverter Setting
File Name D:\TN_110RR\20100101\REV\TN_110RR\TNF\TN_3K0_512.TNF
Model name TN-3000-212
Manufacture MeanWell
Revision REV:1.10
Series Number LOC-1234567890
Date Of Manu. 01/01/2010
I/O Type 212
Voltage 230
Equalization Volt.
Floating Volt.
Alarm Volt.
14.3
13.3
11.3
10.5
V
V
V
V
13.5 ~ 15.0V
13.0 ~ 13.5V
11.0 ~ 11.5V
10.0 ~ 11.0V
V
1
Frequency 50
Hz
Stand-by saving mode
UPS mode
Shutdown Volt.
On
On
On
Off
Energy saving mode
Bauds Rate 9600
1
Comm Ports
Read Write
Lead
4
Exit
Read OK!!
2
3
Figure 3
1. User can adjust the settings based on the characteristics of batteries been used: Equalization Voltage, Floating Voltage, Alarm Voltage,
and Shut-down Voltage. UPS Mode / Energy Saving Mode selection and AC output voltage and frequency can also be set in this page.
2. Read: Read current settings of the unit.
3. Write: Write the revised setting into the unit.
4. Load: Load in factory default settings.
2.3 Statistic Page
Inverter Setting
Start Date 2010/01/01 03:13:33 PM
Start Date 2010/01/01 01:40:56 PM
Inverter time rate
Bypass time rate
Shut Down rate
Solar time rate
91.2
0.0
%
%
%
%
%
Inverter time rate
Bypass time rate
Shut Down rate
Solar time rate
31.9
0.0
%
%
%
%
%
8.8
68.1
0.0
0.0
Loading average
24.7
Loading average
63.7
RESET
Exit
Figure 4
1. Start Date: Date that installing the monitoring software.
2. Reset Date: Date that resetting the statistics. The Start Date will not be influenced by resetting the statistics or turning off the unit.
3 .Inverter time rate: Operating period of "Inverter Mode" represents how many percent of the whole operating period.
4. Bypass time rate: Operating period of "Bypass Mode" (energy provides directly by the utility) represents how many percent of the whole
operating period.
5. Shut down rate: Percentage of time period that the unit is under the condition of shut down.
* Inverter time rate + Bypass time rate + Shut down rate = 100%
6. Solar time rate: Percentage of time period that the solar charger is functioning after turning on the TN-3000 unit.
7. Loading average: Average loading after turning on the TN-3000 unit.
File Name:TN-3000-SPEC 2010-04-09
3000W True Sine Wave DC-AC Inverter with Solar Charger
TN-3000 series
TN 3000 112 A
A :TYPE A OUTLET
B :TYPE B OUTLET
C :TYPE C OUTLET
D :TYPE D OUTLET
E :TYPE E OUTLET
F :TYPE F OUTLET
True sine wave inverter
+AC charger and solar charger
12:12VDC
Bat. Voltage: 24:24VDC
48:48VDC
1:110VAC
Output:
O/P Wattage:3000W
2:230VAC
AC Output Receptacle (optional)
Receptacle type
TYPE-A
TYPE-B
TYPE-C
AUSTRALIA
TYPE-D
TYPE-E
JAPAN
TYPE-F
GFCI
Country
USA
EUROPE
U.K
E13
E13
E13
Certificate
(Expect for 48V input)
Mechanical Specification
Derating Curve
Unit:mm
161.84
122.44
100
80
60
40
S O P
G E N
. t i n U
l l i D W
e s P r e v e R
e h T e g a
y t i r a l
m a
o
20
129.63
0
10
20
30
40
50
60
70
Air flow
direction
Air flow
direction
AMBIENT TEMPERATURE (
CURVE 1
)
AC OUTPUT
SOLAR CHARGE
AC CHARGE
ON
OFF
7.5
BATTERY
LOAD
100
100
Setting
INVERTER
On
0
0
Bat Low
AC IN
BY PASS
Saving
(For Receptacle)
(For AC Input)
Cat.No.(1GG1HS-212)
Wire Range(10-4 AWG Str
Cu Soldered Wires)
Chassis
Ground
Torque (17.7-26.5 in lb)
Remote
port
AC INTPUT
AC OUTPUT
31.29
Type-A
AC INPUT
AC OUTPUT
FG
L
N
L
N
AC OUTPUT
SOLAR CHARGE
ON
AC CHARGE
100
OFF
BATTERY
INVERTER
LOAD
100
Setting
On
0
0
Bat Low
AC IN
BY PASS
Saving
(For Receptacle)
(For AC Input)
Cat.No.(1GG1HS-212)
Wire Range(10-4 AWG Str
Cu Soldered Wires)
Chassis
Ground
Torque (17.7-26.5 in lb)
Remote
port
AC INTPUT
AC OUTPUT
31.29
Type-B
273
283.5
File Name:TN-3000-SPEC 2010-04-09