UHP-1000-24 [MEANWELL]

1000W Slim Type with PFC Switching Supply;
UHP-1000-24
型号: UHP-1000-24
厂家: MEAN WELL ENTERPRISES CO., LTD.    MEAN WELL ENTERPRISES CO., LTD.
描述:

1000W Slim Type with PFC Switching Supply

功率因数校正
文件: 总8页 (文件大小:333K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
Bauart gepruft  
Sicherheit  
egelma ge  
o s  
od  
be wac  
g
www.tuv.com  
ID 2000000000  
EN62368-1  
UL62368-1  
IEC62368-1  
Features  
Slim and Low profile (41mm)  
Certificates  
Safety: UL/EN62368-1  
EMC: EN 55032 / 55024  
Fanless and conduction-cooled design  
Withstand 300VAC surge input for 5 seconds  
Built-in active PFC function  
Applications  
-30~+70working temperature  
Output voltage and constant current level programmable  
Protections: Short circuit / Overload / Over voltage /  
Over temperature  
Industrial automation machinery  
Industrial control system  
Mechanical and electrical equipment  
Electronic instruments, equipment  
or apparatus  
Built-in remote ON-OFF control  
DC OK active signal  
Test and measurement instrument  
Laser rlated machine  
Operating altitude up to 5000 meter (Note.5)  
LED indicator for power on  
Charging related equipment  
Household appliances  
3 years warranty  
Description  
UHP-1000 series is a 1000W single-output slim type power supply with 41mm of low profile design.  
Adopting the full range 90~264VAC input, the entire series provides an output voltage line of 12V,24V,36V  
and 48V. In addition to the high efficiency up to 96%, that the whole series operates from -30~ 70under  
air convection without fan. UHP-1000 has the complete protection functions and 5G anti-vibration  
capability; It is complied with the international safety regulations such as TUV EN62368-1, UL62368-1,  
and the design refers to EN61558-1 and EN60335-1. UHP-1000 series serves as a high performance  
power supply solution for various industrial applications.  
Model Encoding  
UHP - 1000 - 12  
Output voltage(12V/24V/36V/48V)  
Rated wattage  
Series name  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
SPECIFICATION  
MODEL  
UHP-1000-12  
UHP-1000-24  
UHP-1000-36  
UHP-1000-48  
36V  
48V  
DC VOLTAGE  
12V  
24V  
RATED CURRENT  
80A  
42A  
28A  
21A  
RATED POWER(convection)  
RIPPLE & NOISE (max.) Note.2  
960W  
1008W  
240mVp-p  
1008W  
240mVp-p  
1008W  
300mVp-p  
150mVp-p  
By built-in potentiometer, SVR  
VOLTAGE ADJ. RANGE  
OUTPUT  
24~28.8V  
36~43.2V  
1.0%  
48~57.6V  
1.0%  
12~14.4V  
1.0%  
1.0%  
VOLTAGE TOLERANCE Note.3  
LINE REGULATION  
0.5%  
0.5%  
0.5%  
0.5%  
0.5%  
0.5%  
0.5%  
0.5%  
LOAD REGULATION  
SETUP, RISE TIME  
1000ms, 50ms/230VAC  
1000ms,50ms/115VAC at full load  
HOLD UP TIME (Typ.)  
12ms/230VAC  
12ms/115VAC  
250 ~ 370VDC  
VOLTAGE RANGE  
Note.4 90 ~ 264VAC  
FREQUENCY RANGE  
POWER FACTOR (Typ.)  
EFFICIENCY (Typ.)  
47 ~ 63Hz  
PF0.95/230VAC PF0.99/115VAC at full load  
INPUT  
94%  
95%  
95.5%  
96%  
10.1A/115VAC  
5.3A/230VAC  
AC CURRENT (Typ.)  
INRUSH CURRENT (Typ.)  
LEAKAGE CURRENT  
Cold start 20A/115VAC  
<0.75mA / 240VAC  
40A/230VAC  
105~120% rated output power  
OVERLOAD  
Protection type: Constant current limiting with delay shutdown after 3 seconds, re-power on to recover  
Protection type: Constant current limiting with delay shutdown after 3 seconds, re-power on to recover  
SHORT CIRCUIT  
PROTECTION  
14.5 ~ 16V  
29 ~ 33V  
43.5 ~ 49V  
59 ~ 66V  
OVER VOLTAGE  
Protection type: Shut down O/P voltage, re-power on to recover  
OVER TEMPERATURE  
Protection type: Shut down O/P voltage, recovers automatically after temperature goes down  
Adjustment of output voltage is allowable to 50 ~ 120% of nominal output voltage  
Please refer to the Function Manual.  
OUTPUT VOLTAGE  
PROGRAMMABLE(PV) Note 5  
Adjustment of constant current level is allowable to 20 ~ 100% of rated current.  
Please refer to the Function Manual.  
OUTPUT CURRENT  
PROGRAMMABLE(PC) Note 5  
FUNCTION  
Power ON: "Low" <0 ~ 0.5V or Short circuit  
12V@0.5A tolerance 10%, ripple 150mVp-p  
Power OFF: "Hi" >2 ~ 5V or Open circuit  
REMOTE ON/OFF CONTROL  
AUXILIARY POWER  
DC-OK SIGNAL  
The TTL signal out, PSU turn on = 4.5 ~ 5.5V; PSU turn off = -0.1 ~ 0.5V. Please refer to the Function Manual.  
-30 ~ +70(Refer to “Derating Curve")  
WORKING TEMP.  
20 ~ 90% RH non-condensing  
WORKING HUMIDITY  
STORAGE TEMP., HUMIDITY  
TEMP. COEFFICIENT  
VIBRATION  
ENVIRONMENT  
-40 ~ +85, 10 ~ 95% RH non-condensing  
0.03%/(0 ~ 50℃)  
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes  
UL62368-1, TUV EN62368-1, EAC TP TC 004 approved; Design refer to EN61558-1, EN60335-1  
I/P-O/P: 3.75KVAC I/P-FG: 2KVAC O/P-FG: 1.25KVAC  
I/P-O/P, I/P-FG,O/P-FG: 100M Ohms/500VDC/25/ 70%RH  
SAFETY STANDARDS  
WITHSTAND VOLTAGE  
ISOLATION RESISTANCE  
Parameter  
Conducted  
Standard  
Test Level / Note  
Class B  
EN55032 (CISPR32)  
EN55032 (CISPR32)  
EN61000-3-2  
Radiated  
Class B  
EMC EMISSION  
Harmonic Current  
Voltage Flicker  
EN55024 , EN61000-6-2  
Parameter  
ESD  
Class A  
SAFETY &  
EN61000-3-3  
-----  
EMC  
(Note.6)  
Standard  
Test Level / Note  
EN61000-4-2  
EN61000-4-3  
EN61000-4-4  
EN61000-6-2  
EN61000-4-6  
EN61000-4-8  
Level 3, 8KV air ; Level 2, 4KV contact  
Radiated  
Level 3  
EFT / Burst  
Surge  
Level 3  
EMC IMMUNITY  
2KV/Line-Line 4KV/Line-Earth  
Conducted  
Level 3  
Level 4  
Magnetic Field  
>95% dip 0.5 periods, 30% dip 25 periods,  
>95% interruptions 250 periods  
Voltage Dips and Interruptions  
EN61000-4-11  
MTBF  
218.86K hrs min. Telcordia SR-332 (Bellcore) ; 69.81K hrs min. MIL-HDBK-217F (25)  
240*115*41mm (L*W*H)  
OTHERS  
NOTE  
DIMENSION  
PACKING  
1.74kg ; 8pcs/14.9kg/0.74CUFT  
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25of ambient temperature.  
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.  
3. Tolerance: includes set up tolerance, line regulation and load regulation.  
4. Derating may be needed under low input voltages. Please check the derating curve for more details.  
5. PV/PC functions when users do not use SVR.  
6. The power supply is considered a component which will be installed into a final equipment. All the EMC tests are been executed by mounting the unit on  
a 360mm*360mm metal plate with 1mm of thickness. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to  
perform these EMC tests, please refer to “EMI testing of component power supplies. ” (as available on http://www.meanwell.com)  
7. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than 2000m(6500ft).  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
BLOCK DIAGRAM  
PWM fosc : 55KHz  
PFC fosc : 70KHz  
POWER  
SWITCH-  
ING  
EMI FILTER  
&
RECTIFIER  
RECTIFIERS  
&
FILTER  
+V  
-V  
PFC  
CIRCUIT  
I/P  
FG  
O.L.P.  
DETECTION  
CIRCUIT  
PV/PC  
O.L.P.  
PWM  
CONTROL  
SHUT DOWN  
O.V.P.  
O.T.P.  
PFC  
CONTROL  
REMOTE ON-OFF  
CONTROL  
REMOTE  
ON-OFF  
DC OK FUNCTION  
STATIC CHARACTERISTIC  
EFFICIENCY VS LOAD (48V MODEL)  
100  
95  
90  
85  
80  
75  
70  
65  
60  
100  
90  
80  
70  
60  
50  
40  
115VAC  
230VAC  
10% 20% 30% 40% 50% 60% 70% 80% 90% 100%  
110  
120  
140 160 180  
220  
240 264  
90 100  
200  
LOAD  
INPUT VOLTAGE (V) 60Hz  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
DERATING CURVE  
230VAC for 12V  
230VAC for other  
230VAC for 12V  
230VAC for other  
100  
80  
100  
80  
60  
50  
60  
50  
110VAC  
110VAC  
20  
20  
-30  
0
10  
20  
30  
40 45 50  
60  
70  
-30  
0
10  
20  
30  
40 45 50  
60  
70  
(HORIZONTAL)  
(HORIZONTAL)  
AMBIENT TEMPERATURE WITH CONDUCTION COOLING()  
AMBIENT TEMPERATURE WITH FORCED AIR COOLING()  
110VAC  
for other  
100  
80  
80  
70  
60  
230VAC  
for other  
230VAC  
for 12V  
60  
40  
40  
35  
30  
110VAC  
for 12V  
20  
20  
(HORIZONTAL)  
90  
-40  
-25  
0
20  
45  
55  
65  
75  
-30  
0
10  
20  
30  
40 45 50  
60  
70  
(HORIZONTAL)  
AMBIENT TEMPERATURE WITH CONVECTION COOLING()  
Tcase ()  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
FUNCTION MANUAL  
1.Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim)  
In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed by applying EXTERNAL VOLTAGE.  
CN80  
2
1
1413  
EXTERNAL  
VOLTAGE (DC)  
PIN4 -GND-signal  
PIN3 PV  
12V  
24V  
36V  
48V  
14.4 28.8 43.2 57.6  
12 24 36 48  
100  
Non-Linear  
83.3  
80  
60  
40  
6
12 18 24  
20  
V
V
50  
90  
100  
110  
120  
5
6
0
0
0
0
2.5  
EXTERNAL VOLTAGE (DC)  
OUTPUT VOLTAGE (%)  
Caution: By factory default, the Output Voltage Programming is not activated, and PV (pin1) and PV-DIS(pin2) are shorted by connector. Whenever this  
function is not needed to activate, as assumed in other sections’ diagrams, please keep PV (pin1) and PV-DIS(pin2) shorted ; otherwise  
the power supply will have no output.  
2.Output Current Programming (or, PC / remote current programming / dynamic current trim)  
The output current can be trimmed to 20~100% of the rated current by applying EXTERNAL VOLTAGE.  
Iout  
CN80  
Non-linear  
Operating Area  
100  
2
1
1413  
83.3  
For 50~100% Vo  
EXTERNAL  
VOLTAGE (DC)  
For 120% Vo  
PIN12 -GND-signal  
PIN11 PC  
20  
V
1
1.83  
5
EXTERNAL VOLTAGE(VDC)  
Caution: By factory default, the Output Current Programming is not activated, and VCCS(pin13) and PC-DIS(pin14) are shorted by connector. Whenever  
this function is not needed to activate, as assumed in other sections’ diagrams, please keep VCCS(pin13) and PC-DIS(pin14) shorted ;  
otherwise, the power supply will have no output.  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
3.Remote ON-OFF Control  
The power supply can be turned ON/OFF individually or along with other units in parallel by using the "Remote ON-OFF" function.  
CN80  
CN80  
2
1
2
1
1413  
1413  
EXTERNAL  
VOLTAGE (DC)  
switch  
PIN8 -GND-signal  
PIN8-GND-signal  
PIN7 Remote ON-OFF  
PIN7 Remote ON-OFF  
Remote ON-OFF  
Power Supply Status  
“Low” <0~0.5V or Short circuit  
“Hi” >2~5V or Open circuit  
ON  
OFF  
4.DC-OK Signal  
DC-OK signal is a TTL level signal. The maximum sink current is 10mA and the maximum external voltage is 5.6V.  
CN80  
2
1
1413  
PIN9 DC-OK  
Application  
Circuit  
PIN10 -GND-signal  
DC-OK signal  
Power Supply Status  
“Hi” >4.5~5.5V  
ON  
“Low” <-0.1~0.5V  
OFF  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
MECHANICAL SPECIFICATION  
Case No.:272A  
Unit:mm  
240  
232  
3
TB2  
1
2
3
TB1  
3
2
1
TB3  
4
5
6
1
2
13  
14  
SVR  
CN80  
44.2 L=6  
120  
tc  
tc : Max. Case Temperature  
AC Input Terminal(TB1) Pin NO. Assignment  
DC Output Terminal (TB2,TB3) Pin NO. Assignment  
Pin No. Assignment  
Max mounting torque  
Terminal  
Pin No. Assignment  
Terminal  
Max mounting torque  
1
2
3
AC/L  
AC/N  
1,2,3  
4,5,6  
+V  
-V  
(MW)  
NEL-400  
DECA  
T42-BS11-03  
5Kgf-cm  
13.5Kgf-cm  
Control Pin No. Assignment(CN80): HRS DF11-14DP-2DS or equivalent  
2
1
Mating Housing  
Terminal  
HRS DF11-14DS or equivalent  
HRS DF11-**SC or equivalent  
14  
13  
Pin No.  
Function  
PV  
Description  
Connection for output voltage programming.  
Short connecting between PV (pin1) and PV-DIS (pin2) if output voltage programming function is not activated.  
1,3  
2
PV-DIS  
4,8,10,12 GND (Signal) Negative output voltage signal.  
Auxiliary voltage output, 10.8~13.2V, referenced to GND-AUX (pin6).  
The maximum load current is 0.5A. This output is not controlled by “Remote ON-OFF”.  
Auxiliary voltage output GND.  
5
6
7
+12V-AUX  
GND-AUX  
The signal return is isolated from the output terminals (+V & -V).  
The unit can turn the output ON/OFF by electrical signal or dry contact between Remote ON/OFF.  
Short (0 ~ 0.5V): Power ON; Open (2 ~ 5V): Power OFF ; The maximum input voltage is 5.5V.  
Low (-0.1 ~ 0.5V): When the Vout80% 5%.  
Remote  
ON-OFF  
9
DC-OK  
High (4.5 ~ 5.5V): When Vout80% 5%.  
The maximum sink current is 10mA and only for output.  
11  
13  
14  
PC  
Connection for constant current level programming.  
Vccs  
Positive output voltage signal.  
PC-DIS  
Short connecting between Vccs (pin13) and PC-DIS (pin14) if output current programming function is not activated.  
File Name:UHP-1000-SPEC 2019-02-01  
1000W Slim Type with PFC Switching Supply  
UHP-1000 series  
Operate with additional aluminum plate and fan  
In order to meet the “Derating Curve” and the “Static Characteristics” , UHP-1000 series can be installed onto an aluminum plate(or the cabinet of the same size)  
on the bottom or apply forced air cooled solution. The size of the suggested aluminum plate and configuration of fan are shown as below. And for optimizing  
thermal performance, the aluminum plate must have an even and smooth surface (or coated with thermal grease), and UHP-1000 series must be firmly mounted  
at the center of the aluminum plate.  
unit:mm  
M3*4  
450  
450  
23.5CFM  
FAN  
Air flow  
direction  
TB2  
1
2
TB1  
3
3
2
TB3  
1
4
5
6
SVR  
INSTALLATION MANUAL  
Please refer to : http://www.meanwell.com/manual.html  
File Name:UHP-1000-SPEC 2019-02-01  

相关型号:

UHP-1000-36

1000W Slim Type with PFC Switching Supply
MEANWELL

UHP-1000-48

1000W Slim Type with PFC Switching Supply
MEANWELL

UHP-12/21-D48N

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid
MURATA

UHP-12/21-D48NB

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid
MURATA

UHP-12/21-D48NB-C

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid, ROHS COMPLIANT PACKAGE-9
MURATA

UHP-12/21-D48NBL2

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid
MURATA

UHP-12/21-D48NL2-C

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid, ROHS COMPLIANT PACKAGE-9
MURATA

UHP-12/21-D48P

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid
MURATA

UHP-12/21-D48PB-C

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid, ROHS COMPLIANT PACKAGE-9
MURATA

UHP-12/21-D48PBL1

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid
MURATA

UHP-12/21-D48PBL2-C

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid, ROHS COMPLIANT PACKAGE-9
MURATA

UHP-12/21-D48PL1-C

DC-DC Regulated Power Supply Module, 1 Output, 255W, Hybrid, ROHS COMPLIANT PACKAGE-9
MURATA