WDR-60 [MEANWELL]
60W Ultra Wide Input Industrial DIN Rail Power Supply;型号: | WDR-60 |
厂家: | MEAN WELL ENTERPRISES CO., LTD. |
描述: | 60W Ultra Wide Input Industrial DIN Rail Power Supply |
文件: | 总4页 (文件大小:182K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
60W Ultra Wide Input Industrial DIN Rail Power Supply
WDR-60 series
Bauart gepruft
Sicherheit
egelma ge
o s
od
be wac
g
www. tuv.com
ID 2000000000
EN61558
UL61010
TPTC004
■ Features
■ Applications
ꢀ180 ~ 550Vac ultra wide input for 1-phase or 2-phase
ꢀ32mm slim width
ꢀIndustrial control system
ꢀSemiconductor fabrication equipment
ꢀFactory automation
ꢀ4.7KVac I/O high isolation(Reinforced isolation)
ꢀProtections: Short circuit / Overload / Over voltage / Over temperature
ꢀCooling by free air convection
ꢀElectro-mechanical apparatus
ꢀCan be installed on DIN rail TS-35/7.5 or 15
ꢀ-30~+85°C ultra-wide operating temperature ( >+60°C derating)
ꢀOver voltage category Ⅲ
ꢀDC OK relay contact
ꢀDC output voltage adjustable(+20%)
ꢀ3 years warranty
■ Description
WDR-60 series is a 60W DIN rail power supply with ultra-wide AC input range. It is suitable to be mounted
on TS-35/7.5 or TS-35/15 rails. Main features are as following: it can accept 180~550Vac ultra-wide input
voltage range for single phase or 2-phase system, easy to install DIN rail type, narrow width (32mm) in slim
design, -30~+85°C wide range operating temp, 4.7KVAC high isolation voltage, operation at 2000m altitude,
adjustable output voltage (+20% max.), high efficiency, low ripple & noise, complete protections and so on.
WDR-60 is compliant with EN-61000-6-2 standard regarding immunity for industrial environments. It suitable
for industrial automation, surveillance, telecommunication and more applications.
■ Model Encoding
WDR- 60 - 24
Output voltage
Rated wattage
Series name
File Name:WDR-60-SPEC 2019-10-12
60W Ultra Wide Input Industrial DIN Rail Power Supply
WDR-60 series
SPECIFICATION
MODEL
WDR-60-24
WDR-60-5
WDR-60-12
WDR-60-48
48V
24V
DC VOLTAGE
5V
12V
1.25A
2.5A
RATED CURRENT
CURRENT RANGE
RATED POWER
10A
5A
0 ~ 1.25A
60W
0 ~ 2.5A
60W
0 ~ 10A
50W
0 ~ 5A
60W
200mVp-p
48 ~ 57V
1.0%
150mVp-p
24 ~ 29V
1.0%
RIPPLE & NOISE (max.) Note.2 100mVp-p
VOLTAGE ADJ. RANGE
VOLTAGE TOLERANCE Note.3 2%
120mVp-p
12 ~ 15V
1.5%
OUTPUT
5 ~ 6V
0.5%
0.5%
LINE REGULATION
0.5%
0.5%
0.5%
0.5%
LOAD REGULATION
1.5%
0.5%
SETUP, RISE, HOLD UP TIME
1000ms, 70ms, 20ms/400Vac
2000ms, 70ms, 10ms/230Vac at full load
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
Note.4 180 ~ 550Vac or 254 ~ 780Vdc
47 ~ 63Hz
86.5% / 400Vac
89% / 400Vac
83.5% / 400Vac
0.4A/400Vac
90.5% / 400Vac
INPUT
0.7A/230Vac
AC CURRENT
INRUSH CURRENT (max.)
COLD START 50A /400Vac 30A/230Vac
<2mA / 530Vac
LEAKAGE CURRENT
105 ~ 135% rated output power
OVERLOAD
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed
Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed
6.2 ~ 7.2V
16 ~ 18V
31 ~ 37V
58 ~ 60.5V
PROTECTION
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
Protection type : Shut down o/p voltage, re-power on to recover
Relay contact rating(max.) : 30V / 1A resistive
-30 ~ +85℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
OVER TEMPERATURE
DC OK SIGNAL
FUNCTION
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP.
TEMP. COEFFICIENT
VIBRATION
-40 ~ +85℃
ENVIRONMENT
0.03%/℃ (0 ~ 60℃)
Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6
2000 meters
OPERATING ALTITUDE Note.5
OVER VOLTAGE CATEGORY
SAFETY STANDARDS
Ⅲ; According to EN61558, EN50178, EN60664-1, EN62477-1, EN60204-1; altitude up to 2000 meters
UL61010, EN61558-2-16, EAC TP TC 004 approved; design refer to GL and EN60204-1(By request)
I/P-O/P:4.7KVAC I/P-FG:2.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
Parameter
Standard
Test Level / Note
Conducted
EN55032(CISPR32)
EN55032(CISPR32)
EN61000-3-2
Class B
EMC EMISSION
Class B
Class A
-------
Radiated
Harmonic Current
Voltage Flicker
EN61000-3-3
SAFETY &
EN55024, EN55035, EN61000-6-2, EN61204-3
EMC
(Note 7)
Test Level /Note
Parameter
Standard
ESD
Level 3, 8KV air; Level 2, 4KV contact, criteria A
EN61000-4-2
EN61000-4-3
EN61000-4-4
Radiated Susceptibility
EFT Bursts
Surge
Level 3, 10V/m, criteria A
Level 3, 2KV/5KHz, criteria A
Level 4, 2KV/Line-Line, 4KV/Line-Earth, criteria A
Level 3, 10V, criteria A
EMC IMMUNITY
EN61000-4-5
EN61000-4-6
EN61000-4-8
Conducted
Level 4, 30A/m, criteria A
Magnetic Field
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
Voltage Dips and interruptions
EN61000-4-11
MTBF
313.68K hrs min. MIL-HDBK-217F (25℃)
32*125.2*102mm (W*H*D)
OTHERS
DIMENSION
PACKING
0.45Kg; 28pcs/13.6Kg/1.24CUFT
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Derating may be needed under low input voltage. Please check the derating curve for more details.
5. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than
2000m(6500ft).
NOTE
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with
full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
File Name:WDR-60-SPEC 2019-10-12
60W Ultra Wide Input Industrial DIN Rail Power Supply
WDR-60 series
Block Diagram
fosc : 40-70KHz
DC OK
RECTIFIERS
RECTIFIERS
+V
-V
POWER
EMI
I/P
&
&
SWITCHING
FILTER
FILTER
FILTER
O.C.P.
O.V.P.
FG
CONTROL
O.L.P.
DETECTION
CIRCUIT
Derating Curve
100
50
30
-30
0
10
20
30
40
50
60
70
85
(VERTICAL)
AMBIENT TEMPERATURE (℃)
Static Characteristics
100
90
80
70
60
50
40
(Vac)
210
180
230 240 270 310 360 380 440 480 520 550
INPUT VOLTAGE (VAC) 60Hz
DC OK Relay Contact
Contact Close
PSU turns ON / DC OK.
PSU turns OFF / DC Fail.
30V/1A resistive load.
Contact Open
Contact Ratings (max.)
File Name:WDR-60-SPEC 2019-10-12
60W Ultra Wide Input Industrial DIN Rail Power Supply
WDR-60 series
Mechanical Specification
Case No.221E
Unit:mm
Terminal Pin No. Assignment (TB2)
Pin No. Assignment
1
2
DC output -V
DC output +V
Relay Contact
3,4
32
102
TB2
2 3 4
1
DC OK
TB1
FG L2 L1
1 2
3
Terminal Pin No. Assignment (TB1)
Pin No. Assignment
1
2
3
FG
L2
L1
Installation Instruction
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
Back View
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
File Name:WDR-60-SPEC 2019-10-12
相关型号:
WDR-60-12
60W Ultra Wide Input Industrial DIN Rail Power SupplyWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL
WDR-60-24
60W Ultra Wide Input Industrial DIN Rail Power SupplyWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL
WDR-60-48
60W Ultra Wide Input Industrial DIN Rail Power SupplyWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL
WDR-60-5
60W Ultra Wide Input Industrial DIN Rail Power SupplyWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL
WDRR
Din-Rail ReceiverWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A00A0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A00B0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A01A0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A01B0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A02A0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A02B0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
WDRR1A03A0A
Limitless⢠Single Switch AdapterWarning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL
©2020 ICPDF网 联系我们和版权申明