WDR-60 [MEANWELL]

60W Ultra Wide Input Industrial DIN Rail Power Supply;
WDR-60
型号: WDR-60
厂家: MEAN WELL ENTERPRISES CO., LTD.    MEAN WELL ENTERPRISES CO., LTD.
描述:

60W Ultra Wide Input Industrial DIN Rail Power Supply

文件: 总4页 (文件大小:182K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
60W Ultra Wide Input Industrial DIN Rail Power Supply  
WDR-60 series  
Bauart gepruft  
Sicherheit  
egelma ge  
o s  
od  
be wac  
g
www. tuv.com  
ID 2000000000  
EN61558  
UL61010  
TPTC004  
Features  
Applications  
180 ~ 550Vac ultra wide input for 1-phase or 2-phase  
32mm slim width  
Industrial control system  
Semiconductor fabrication equipment  
Factory automation  
4.7KVac I/O high isolation(Reinforced isolation)  
Protections: Short circuit / Overload / Over voltage / Over temperature  
Cooling by free air convection  
Electro-mechanical apparatus  
Can be installed on DIN rail TS-35/7.5 or 15  
-30~+85°C ultra-wide operating temperature ( >+60°C derating)  
Over voltage category  
DC OK relay contact  
DC output voltage adjustable(+20%)  
3 years warranty  
Description  
WDR-60 series is a 60W DIN rail power supply with ultra-wide AC input range. It is suitable to be mounted  
on TS-35/7.5 or TS-35/15 rails. Main features are as following: it can accept 180~550Vac ultra-wide input  
voltage range for single phase or 2-phase system, easy to install DIN rail type, narrow width (32mm) in slim  
design, -30~+85°C wide range operating temp, 4.7KVAC high isolation voltage, operation at 2000m altitude,  
adjustable output voltage (+20% max.), high efficiency, low ripple & noise, complete protections and so on.  
WDR-60 is compliant with EN-61000-6-2 standard regarding immunity for industrial environments. It suitable  
for industrial automation, surveillance, telecommunication and more applications.  
Model Encoding  
WDR- 60 - 24  
Output voltage  
Rated wattage  
Series name  
File Name:WDR-60-SPEC 2019-10-12  
60W Ultra Wide Input Industrial DIN Rail Power Supply  
WDR-60 series  
SPECIFICATION  
MODEL  
WDR-60-24  
WDR-60-5  
WDR-60-12  
WDR-60-48  
48V  
24V  
DC VOLTAGE  
5V  
12V  
1.25A  
2.5A  
RATED CURRENT  
CURRENT RANGE  
RATED POWER  
10A  
5A  
0 ~ 1.25A  
60W  
0 ~ 2.5A  
60W  
0 ~ 10A  
50W  
0 ~ 5A  
60W  
200mVp-p  
48 ~ 57V  
1.0%  
150mVp-p  
24 ~ 29V  
1.0%  
RIPPLE & NOISE (max.) Note.2 100mVp-p  
VOLTAGE ADJ. RANGE  
VOLTAGE TOLERANCE Note.3 2%  
120mVp-p  
12 ~ 15V  
1.5%  
OUTPUT  
5 ~ 6V  
0.5%  
0.5%  
LINE REGULATION  
0.5%  
0.5%  
0.5%  
0.5%  
LOAD REGULATION  
1.5%  
0.5%  
SETUP, RISE, HOLD UP TIME  
1000ms, 70ms, 20ms/400Vac  
2000ms, 70ms, 10ms/230Vac at full load  
VOLTAGE RANGE  
FREQUENCY RANGE  
EFFICIENCY (Typ.)  
Note.4 180 ~ 550Vac or 254 ~ 780Vdc  
47 ~ 63Hz  
86.5% / 400Vac  
89% / 400Vac  
83.5% / 400Vac  
0.4A/400Vac  
90.5% / 400Vac  
INPUT  
0.7A/230Vac  
AC CURRENT  
INRUSH CURRENT (max.)  
COLD START 50A /400Vac 30A/230Vac  
<2mA / 530Vac  
LEAKAGE CURRENT  
105 ~ 135% rated output power  
OVERLOAD  
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed  
Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed  
6.2 ~ 7.2V  
16 ~ 18V  
31 ~ 37V  
58 ~ 60.5V  
PROTECTION  
OVER VOLTAGE  
Protection type : Shut down o/p voltage, re-power on to recover  
Protection type : Shut down o/p voltage, re-power on to recover  
Relay contact rating(max.) : 30V / 1A resistive  
-30 ~ +85(Refer to "Derating Curve")  
20 ~ 90% RH non-condensing  
OVER TEMPERATURE  
DC OK SIGNAL  
FUNCTION  
WORKING TEMP.  
WORKING HUMIDITY  
STORAGE TEMP.  
TEMP. COEFFICIENT  
VIBRATION  
-40 ~ +85℃  
ENVIRONMENT  
0.03%/(0 ~ 60)  
Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting clip: Compliance to IEC60068-2-6  
2000 meters  
OPERATING ALTITUDE Note.5  
OVER VOLTAGE CATEGORY  
SAFETY STANDARDS  
; According to EN61558, EN50178, EN60664-1, EN62477-1, EN60204-1; altitude up to 2000 meters  
UL61010, EN61558-2-16, EAC TP TC 004 approved; design refer to GL and EN60204-1(By request)  
I/P-O/P:4.7KVAC I/P-FG:2.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC  
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH  
WITHSTAND VOLTAGE  
ISOLATION RESISTANCE  
Parameter  
Standard  
Test Level / Note  
Conducted  
EN55032(CISPR32)  
EN55032(CISPR32)  
EN61000-3-2  
Class B  
EMC EMISSION  
Class B  
Class A  
-------  
Radiated  
Harmonic Current  
Voltage Flicker  
EN61000-3-3  
SAFETY &  
EN55024, EN55035, EN61000-6-2, EN61204-3  
EMC  
(Note 7)  
Test Level /Note  
Parameter  
Standard  
ESD  
Level 3, 8KV air; Level 2, 4KV contact, criteria A  
EN61000-4-2  
EN61000-4-3  
EN61000-4-4  
Radiated Susceptibility  
EFT Bursts  
Surge  
Level 3, 10V/m, criteria A  
Level 3, 2KV/5KHz, criteria A  
Level 4, 2KV/Line-Line, 4KV/Line-Earth, criteria A  
Level 3, 10V, criteria A  
EMC IMMUNITY  
EN61000-4-5  
EN61000-4-6  
EN61000-4-8  
Conducted  
Level 4, 30A/m, criteria A  
Magnetic Field  
95% dip 0.5 periods, 30% dip 25 periods,  
95% interruptions 250 periods  
Voltage Dips and interruptions  
EN61000-4-11  
MTBF  
313.68K hrs min. MIL-HDBK-217F (25)  
32*125.2*102mm (W*H*D)  
OTHERS  
DIMENSION  
PACKING  
0.45Kg; 28pcs/13.6Kg/1.24CUFT  
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25of ambient temperature.  
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor.  
3. Tolerance : includes set up tolerance, line regulation and load regulation.  
4. Derating may be needed under low input voltage. Please check the derating curve for more details.  
5. The ambient temperature derating of 3.5/1000m with fanless models and of 5/1000m with fan models for operating altitude higher than  
2000m(6500ft).  
NOTE  
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with  
full power. In case the adjacent device is a heat source, 15mm clearance is recommended.  
7. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets  
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”  
(as available on http://www.meanwell.com)  
File Name:WDR-60-SPEC 2019-10-12  
60W Ultra Wide Input Industrial DIN Rail Power Supply  
WDR-60 series  
Block Diagram  
fosc : 40-70KHz  
DC OK  
RECTIFIERS  
RECTIFIERS  
+V  
-V  
POWER  
EMI  
I/P  
&
&
SWITCHING  
FILTER  
FILTER  
FILTER  
O.C.P.  
O.V.P.  
FG  
CONTROL  
O.L.P.  
DETECTION  
CIRCUIT  
Derating Curve  
100  
50  
30  
-30  
0
10  
20  
30  
40  
50  
60  
70  
85  
(VERTICAL)  
AMBIENT TEMPERATURE ()  
Static Characteristics  
100  
90  
80  
70  
60  
50  
40  
(Vac)  
210  
180  
230 240 270 310 360 380 440 480 520 550  
INPUT VOLTAGE (VAC) 60Hz  
DC OK Relay Contact  
Contact Close  
PSU turns ON / DC OK.  
PSU turns OFF / DC Fail.  
30V/1A resistive load.  
Contact Open  
Contact Ratings (max.)  
File Name:WDR-60-SPEC 2019-10-12  
60W Ultra Wide Input Industrial DIN Rail Power Supply  
WDR-60 series  
Mechanical Specification  
Case No.221E  
Unit:mm  
Terminal Pin No. Assignment (TB2)  
Pin No. Assignment  
1
2
DC output -V  
DC output +V  
Relay Contact  
3,4  
32  
102  
TB2  
2 3 4  
1
DC OK  
TB1  
FG L2 L1  
1 2  
3
Terminal Pin No. Assignment (TB1)  
Pin No. Assignment  
1
2
3
FG  
L2  
L1  
Installation Instruction  
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15  
(For reference only. Not included with unit.)  
Back View  
Installation Manual  
Please refer to : http://www.meanwell.com/manual.html  
File Name:WDR-60-SPEC 2019-10-12  

相关型号:

WDR-60-12

60W Ultra Wide Input Industrial DIN Rail Power Supply

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL

WDR-60-24

60W Ultra Wide Input Industrial DIN Rail Power Supply

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL

WDR-60-48

60W Ultra Wide Input Industrial DIN Rail Power Supply

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL

WDR-60-5

60W Ultra Wide Input Industrial DIN Rail Power Supply

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
MEANWELL

WDRR

Din-Rail Receiver

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A00A0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A00B0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A01A0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A01B0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A02A0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A02B0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL

WDRR1A03A0A

Limitless™ Single Switch Adapter

Warning: Undefined variable $rtag in /www/wwwroot/website_ic37/www.icpdf.com/pdf/pdf/index.php on line 217
-
HONEYWELL