AC/DC Converter
LH40-13Bxx series
40W, AC/DC converter
FEATURES
Input voltage range: 85 - 305VAC/100 - 430VDC
AC and DC dual-use(input from the same terminal)
High efficiency up to 84%
Isolation voltage: 3K VAC
Operating temperature range: -40℃ to +85℃
Output short circuit, over-current, over-voltage protection
RoHS
LH40-13Bxx series are 40W efficient environmental-protection AC-DC module power supply, which have advantages such as universal input
voltage, accept either AC or DC input, high efficiency, high reliability, low power consumption and high safety isolation. They offer good
EMC performance, meet IEC/EN61000-4, CISPR32/EN55032, UL62368 and EN62368 standards. The series products are widely used in
industries such as industrial control, electricity, office.
Note: Please refer to Design Reference when module being used in a bad EMC environment.
Selection Guide
Nominal Output Voltage and
Current(Vo/Io)
Efficiency
(277VAC, %/Typ.)
Max. Capacitive
Load(µF)
Part No.
Output Power
40W
LH40-13B12
LH40-13B24
12VDC/3333mA
24VDC/1667mA
84
84
9000
2000
Input Specifications
Item
Operating Conditions
AC input
Min.
85
100
47
--
Typ.
--
Max.
305
430
63
Unit
VAC
VDC
Hz
Input Voltage Range
Input frequency
Input current
--
DC input
--
115VAC
277VAC
115VAC
277VAC
--
1.0
0.5
--
--
--
A
--
30
70
Inrush current
Hot Plug
--
--
Unavailable
Output Specifications
Item
Operating Conditions
Min.
--
Typ.
±2
Max.
--
Unit
%
Output Voltage Accuracy
Line Regulation
Full load
--
±0.5
±1
--
%
Load Regulation
0% - 100% load
--
--
Ripple & Noise*
--
50
100
--
mV
20MHz bandwidth (peak-peak value)
--
±0.02
--
%/
℃
Temperature Coefficient
Stand-by Power Consumption
Short Circuit Protection
--
0.8
W
Continuous, self-recovery
≥110%Io self-recovery
≤16VDC
Over-current Protection
12V
24V
Over-voltage Protection
≤35VDC
Min. Load
Trim
0
--
--
--
--
--
--
±10
--
%
15
60
115VAC input
277VAC input
Hold-up Time
ms
--
Note: * Ripple and noise are measured by “parallel cable” method, please see AC-DC Converter Application Notes for specific operation.
2018.06.30-A/0
Page 1 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter
LH40-13Bxx series
General Specifications
Item
Operating Conditions
Min.
3000
-40
-40
--
Typ.
--
Max.
--
Unit
Test time: 1min (leakage current<5mA)
Isolation Voltage
Input-output
VAC
--
+85
+85
95
Operating Temperature
Storage Temperature
Storage Humidity
℃
--
--
%RH
Wave-soldering
Manual-welding
260 ± 5℃; time: 5 - 10s
360 ± 10℃; time: 3 - 5s
Welding Temperature
Switching Frequency
--
65
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
kHz
-40℃ to -30℃(LH40-13B12)
+55℃ to +70℃(LH40-13B12)
+70℃ to +85℃(LH40-13B12)
-40℃ to -30℃(LH40-13B24)
+55℃ to +70℃(LH40-13B24)
+70℃ to +85℃(LH40-13B24)
85-100VAC
3.0
3.67
1.67
2.0
%/℃
Power Derating
Safety Standard
2.7
2.33
1.33
0.72
%/VAC
277-305VAC
IEC62368/EN62368/UL62368
CLASS II
Safety Class
MTBF
MIL-HDBK-217F@25℃>300,000 h
Physical Specifications
Casing Material
Dimensions
Black flame-retardant and heat-resistant plastic (UL94V-0)
89.00*63.50*25.00 mm
225g (Typ.)
Weight
Cooling Method
Free air convection
EMC Specifications
CE
CISPR32/EN55032 CLASS B
EMI
RE
CISPR32/EN55032 CLASS B
IEC/EN61000-4-2 Contact ±6KV/Air ±8KV
IEC/EN61000-4-3 10V/m
Perf. Criteria B
perf. Criteria A
perf. Criteria B
perf. Criteria B
perf. Criteria B
ESD
RS
IEC/EN61000-4-4 ±2KV
EFT
IEC/EN61000-4-4 ±4KV (See Fig. 2 for recommended circuit)
IEC/EN61000-4-5 line to line ±1KV
EMS
Surge
CS
IEC/EN61000-4-5 line to line±2KV/ line to ground ±4KV
(See Fig. 2 for recommended circuit)
perf. Criteria B
perf. Criteria A
IEC/EN61000-4-6 10Vr.m.s
Product Characteristic Curve
Note:
①Input voltage should be derated based on temperature derating when it is 85-100VAC/277-305VAC/100-120VDC/400-430VDC;
②This product is suitable for use in natural air cooling environments, if in a closed environment, please contact our company’s FAE.
2018.06.30-A/0
Page 2 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter
LH40-13Bxx series
Design Reference
1. Typical application circuit
NTC
FUSE
MOV
RL
C1 C2 TVS1
AC(L)
+Vo
AC(L)
AC-DC
AC(N)
AC(N)
-Vo
Fig. 1
Model
FUSE
MOV
S10K350
NTC
C1(µF)
1
C2(µF)
220
TVS1
LH40-13B12
LH40-13B24
SMBJ20A
SMBJ30A
3.15A/300VAC, slow
fusing, necessary
5D-9
120
Note: Output filtering capacitor C2 is electrolytic capacitors, it is recommended to apply electrolytic capacitor with high frequency and low resistance. For
capacitance and current of capacitor please refer to manufacture’s datasheet. Capacitor voltage reduced to at least 80%. C1 is ceramic capacitors, which is
used to filter high-frequency noise. TVS is a recommended component to protect post-circuits if converter fails.
2. EMC solution-recommended circuit
NTC
MOV2
MOV3
FUSE
C1
C2
TVS
RL
AC(L)
AC(L)
+Vo
CY1
CY2
R1
+
CX
AC/DC
LCM
MOV1
-Vo
AC(N)
AC(N)
Fig.2 (Output external circuit refer to the typical application circuit)
Element model
Recommended value
S14K350
MOV1
MOV2, MOV3
CX
S07K350
0.15µF/300VAC
2.2nF/400VAC
2.2nF /400VAC
1MΩ/2W
CY1
CY2
R1
LCM
NTC
2.2mH, recommended to use MORNSUN’s FL2D-10-222;
5D-14
FUSE
3.15A/300V, slow fusing, necessary
2018.06.30-A/0
Page 3 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter
LH40-13Bxx series
3. Application of Trim and calculation of Trim resistance
+Vot
+Vot
R1
RT
R1
R3
Vref
Trim
R3
Vref
R2
Trim
R2
RT
0V
Trim down
0V
Trim up
Applied circuits of Trim (Part in broken line is the interior of models)
Calculation formula of Trim resistance:
aR2
R2-a
Vref
Vot-Vref
-R3
up:
RT=
a=
R1
RT is Trim resistance, a is a self-defined
parameter, with no real meaning.
aR1
R1-a
Vot-Vref
Vref
down:
-R3
RT=
a=
R2
Vout
12V
R1(KΩ)
R2(KΩ)
R3(KΩ)
Vref(V)
Vot(V)
3.83
1
1
2.5
Output voltage
after regulation,
variation ≤ ±10%
24V
8.66
1
1
2.5
4. For more information, Please find the application note on www.mornsun-power.com
Dimensions and Recommended Layout
2018.06.30-A/0
Page 4 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
AC/DC Converter
LH40-13Bxx series
Notes:
1. Packing information please refer to Product Packing Information which can be downloaded from www.mornsun-power.com. Packing
bag number: 58220021;
2. Unless otherwise specified, parameters in this datasheet were measured under the conditions of Ta=25℃, humidity<75% with nominal
input voltage and rated output load;
3. All index testing methods in this datasheet are based on our Company’s corporate standards;
4. We can provide product customization service, please contact our technicians directly for specific information;
5. Products are related to laws and regulations: see "Features" and "EMC";
6. Our products shall be classified according to ISO14001 and related environmental laws and regulations, and shall be handled by
qualified units.
Mornsun Guangzhou Science & Technology Co., Ltd.
Address: No. 5, Kehui St. 1, Kehui Development Center, Science Ave., Guangzhou Science City, Luogang District, Guangzhou, P. R. China
Tel: 86-20-38601850-8801
Fax: 86-20-38601272
E-mail: info@mornsun.cn
2018.06.30-A/0
Page 5 of 5
MORNSUN Guangzhou Science & Technology Co., Ltd. reserves the copyright and right of final interpretation
相关型号:
©2020 ICPDF网 联系我们和版权申明