MPO-500S-48T [MPD]

Single Output, 500W Power Factor Corrected, AC/DC Power Supplies;
MPO-500S-48T
型号: MPO-500S-48T
厂家: MICROPOWER DIRECT, LLC    MICROPOWER DIRECT, LLC
描述:

Single Output, 500W Power Factor Corrected, AC/DC Power Supplies

文件: 总4页 (文件大小:1490K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Series  
MPO-500S  
Single Output, 500W  
Power Factor Corrected,  
AC/DC Power Supplies  
Electrical Specifications  
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.  
Key Features:  
Input  
Parameter  
Conditions  
Min.  
90  
120  
47  
Typ.  
Max.  
264  
370  
63  
Units  
VAC  
VDC  
Hz  
500W Power W/30 CFM  
Universal 90-264 AC Input  
>0.95 Active PFC  
Universal  
Input Voltage Range  
Input Frequency  
Input Current  
See Model Selection Guide  
Cold Start, 115 VAC  
Cold Start, 230 VAC  
EN 60950 Approved  
Standby 5V Output  
ThreeSingleOutputModels  
Meets EN 55022 B  
>160 kHour MTBF  
35.0  
70.0  
0.50  
Inrush Current  
A Pk  
mA  
Safety Ground Leakage Current  
Power Factor Correction, See Note 1  
Output  
Parameter  
Max Output Power  
0.95  
Conditions  
Min.  
Typ.  
Max.  
Units  
500W (with 30 CFM), 240W (230 VAC), 230W (115 VAC)  
Only 5.0” x 3.0” x 1.4”  
Output Voltage Accuracy  
Line Regulation  
2.0  
1.0  
1.2  
%
%
VIN = 115 to 264 VAC  
12 VOUT  
Load Regulation, See Note 2  
%
24 and 48 VOUT  
12 VDC Output  
24 VDC Output  
48 VDC Output  
115 VAC, 90% VOUT  
0°C - 50°C  
1.0  
150  
240  
480  
Ripple & Noise (20 MHz), See Note 3  
mV P - P  
Hold-Up Time  
8
mSec  
%/°C  
°C  
0.03  
0.06  
120  
Temperature Coefficient  
-30°C - 0°C  
Over Temperature Protection  
Over Voltage Protection  
Overload Protection  
Short Circuit Protection, See Note 4  
General  
Autorecovery  
See Model Selection Guide  
120  
170  
%
Continuous (Autorecovery)  
Parameter  
Conditions  
Input to Output  
Min.  
3,000  
4,242  
Typ.  
Max.  
Units  
VAC  
VDC  
Isolation Voltage  
Input to Ground 1,500  
Output to Ground  
VAC  
kHz  
500  
58  
Switching Frequency  
EMI Characteristics  
Parameter  
75  
Standard  
Criteria  
Level  
Radiated Emissions  
Conducted Emissions  
Noise Immunity (EMS)  
Surge  
Environmental  
Parameter  
Operating Temperature Range  
Storage Temperature Range  
Cooling  
Humidity  
Physical  
EN 55022  
EN 55022  
EN 55024  
A
B
EN 61000-4-4  
1 kV (L-N), 2 kV (L-G)  
MicroPower Direct  
292 Page Street  
Suite D  
Stoughton, MA 02072  
USA  
Conditions  
Min.  
-30  
-30  
Typ.  
+25  
Max.  
+70  
+85  
Units  
°C  
°C  
Ambient  
Free Air Convection (See Derating Curve)/30 CFM  
RH, Non-condensing 95  
%
T: (781) 344-8226  
F: (781) 344-8481  
E: sales@micropowerdirect.com  
W: www.micropowerdirect.com  
Size  
Weight  
See Mechanical Drawing (Page 4)  
16.22 Oz (0.460 kg)  
Reliability Specifications  
Parameter  
MTBF  
Conditions  
MIL HDBK 217F, 25°C, Gnd Benign  
Min.  
160  
Typ.  
Max.  
Units  
kHours  
Safety Standards  
Vibration  
UL 1950, EN 60950  
10~500 Hz, 2G 10 min/1 Cycle. Period of 60 min each along X, Y &Z Axis  
www.micropowerdirect.com  
Model Selection Guide  
www.micropowerdirect.com  
Output  
Voltage  
Adjust  
Range  
(VDC)  
Input  
Output Current (A)  
Over  
Output  
Voltage  
(VDC)  
Minimum Capacitive  
Model  
Number  
Voltage  
Efficiency  
Load  
(%)  
Load  
Current (A)  
Free Air  
Protection (%, Typ, 230 VAC)  
(VDC Typ)  
(µF Max)  
W/30 CFM  
115 VAC 230 VAC  
115 VAC 230 VAC  
MPO-500S-12T  
MPO-500S-24T  
MPO-500S-48T  
Notes:  
1. PFC meets EN61000-3-2.  
2. Load regulation is given for a load  
change of 10% to 100%.  
6.0  
6.0  
6.0  
3.0  
3.0  
3.0  
12.0  
24.0  
48.0  
11.52 - 12.48  
23.04 - 24.96  
46.08 - 49.44  
41.50  
20.80  
10.41  
19.16  
9.58  
4.80  
20.00  
10.00  
5.00  
3.0  
3.0  
3.0  
10,000  
5,000  
2,500  
16.0  
31.0  
57.0  
88  
90  
92  
Block Diagram  
3. Ripple & noise is measured at 20  
MHz bandwidth using a ceramic  
0.1 µF and a low resistance electro-  
lytic 47 µF capacitor connected in  
parallel. The capacitors should be  
mounted as close to the power supply  
terminals as possible.  
4. Output short circuit protection is pro-  
vided by a “Hiccup” mode circuit.  
5. The standby output voltage is 4.4 to  
5.5 VDC at 0.4A max. It is accessible  
at pins 1 & 2 on the CN3 connector.  
6. Positive and negative sensing is avaii-  
ableattheconnectorCN3. Ifused, the  
positive (+S at pin 8) sense should be  
connectedtothepositiveterminalofthe  
load, and the negative (-S at pin  
7) should be connected to the negative terminal of  
the load. The positive and negative leads should be  
twisted together to minimize the effects of noise pick-  
up. The maximum line drop compensation is 0.3V.  
7. The Green LED (just above CN3 on the logic board)  
indicates the DC output is present when it is lit. If the  
LED is off when the unit is supposed to be operating,  
it would indicate a fault condition.  
8. These units will operate at no load without damage,  
but they may not meet specifications. The recom-  
mended minimum load is given in the model selection  
chart above.  
9. Each unit includes an input fuse. Since this fuse is not  
field replaceable, it is recommended that an external  
fuse be used on the input of the power supply for  
protection. For these units, a 8-9A/250V slow blow  
fuse is recommended.  
CN3 Connections  
Function  
Description  
No.  
1
2
-5 SB Return for stand by voltage output. Connected to -VOUT.  
+5 SB  
Standby voltage output. See note 5 above.  
Connected to -VOUT. Return for DC OK & RC.  
3
GND  
A small DC output, referenced to pin 3 (see diagram at left).  
4
DC OK  
Return for the remote control. Connected to -VOUT.  
5
-RC  
Turns the output On/Off. See diagram below.  
6
+RC  
-Sense connection. See note 6 above  
7
-S  
+Sense connection. See note 6 above  
8
+S  
Remote On/Off  
Operation of the unit can be controlled remotely through the use of a  
switch or TTL signal. Contact the factory for more information.  
Output LED & Trim  
Output LED: An LED lamp next to the output connec-  
tor. The LED is on (Green)during normal operation. If  
the LED is not lit, it indicates a problem with the supply.  
Between: +RC - -RC  
SW1 Closed  
Output Status  
Off  
On  
Output Adjust: The output voltage can be adjusted  
over the range given in the table below by using the  
trim pot located to the side (and just behind) of the  
output connector. Great care should be taken not to  
use excessive force when making any adjustment. To  
much force may damage the wiper arm of the pot,  
rendering the power supply inoperable.  
SW1 Open  
DC Okay Signal  
Between: DC OK - GND  
3.7 VDC - 6.0 VDC  
0.0 VDC - 1.0 VDC  
Output Status  
On  
Off  
Model  
Adjustment Range  
11.52 - 12.48 VDC  
23.04 - 24.98 VDC  
46.08 - 49.44 VDC  
When the unit is operating, a small, stable DC voltage is available  
at pin 3 on CN3 (referenced to -VOUT). This voltage may be used for  
remote monitoring to insure the unit is operating. Contact the factory  
for more information.  
MPO-500S-12T  
MPO-500S-24T  
MPO-500S-48T  
MicroPower Direct  
292 Page Street Ste D Stoughton, MA 02072 TEL: (781) 344-8226 FAX: (781) 344-8481 E-Mail: sales@micropowerdirect.com  
www.micropowerdirect.com  
Derating Curve, Output Power vs Temperature  
Derating Curve, Output Power vs Input Voltage  
Efficiency vs Input Voltage MPO-500S -12  
Efficiency vs Input Voltage MPO-500S -24  
Efficiency vs Input Voltage MPO-500S -48  
Efficiency vs Output Load MPO-500S -12  
Efficiency vs Output Load MPO-500S -24  
Efficiency vs Output Load MPO-500S -48  
MicroPower Direct  
292 Page Street Ste D Stoughton, MA 02072 TEL: (781) 344-8226 FAX: (781) 344-8481 E-Mail: sales@micropowerdirect.com  
Air Flow  
www.micropowerdirect.com  
To operate the unit with a load over  
240W, air flow must be provided.  
The diagram at left shows the  
approximate area where the airflow  
should be directed.  
Mechanical Dimensions  
Output Connector (CN2):  
Terminal Block:  
Dinkle DT-2C-B07W-06: M3 Screws  
6 terminals, 7.62 mm Centers  
Suitable Wire = 22 - 14 AWG  
Logic Signal Connector (CN3):  
Mating Part No:  
PHD-H20-2X04 or equivalent  
(Cherg Weei Technology Corp)  
Fan Driver Connector (CN4):  
Mating Part No:  
CX-H250-02 or equivalent  
(Cherg Weei Technology Corp)  
Connections  
Input Connector (CN1):  
Terminal Block:  
Dinkle DT-2C-B07W-03: M3 Screws  
3 terminals, 7.62 mm Centers  
Suitable Wire = 22 - 14 AWG  
Pin Function  
Pin Function  
Pin  
Function  
-5 SB  
+5 SB  
GND  
DC OK  
-RC  
+RC  
-S  
+S  
1
2
3
4
5
6
7
8
1
2
+12V  
GND  
Pin  
Function  
1
2
3
4
5
6
+VOUT  
+VOUT  
+VOUT  
-VOUT  
-VOUT  
-VOUT  
1
2
3
Field Ground  
AC-Neutral  
AC-Line  
See page 2 for more information  
on the signals available from CN3  
MicroPower Direct  
We Power Your Success - For Less!  
292 Page Street Ste D Stoughton, MA 02072  
TEL: (781) 344-8226  
FAX: (781) 344-8481  
E-Mail: sales@micropowerdirect.com  

相关型号:

MPO-65S

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-05

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-12

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-13.5

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-15

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-24

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-27

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-3.3

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-48

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO-65S-7.5

Single Output, 65W Compact, Open Frame AC/DC Power Supplies
MPD

MPO100S12

MPO-100S Series
MPD

MPO100S15

MPO-100S Series
MPD