10AS-61 [MSYSTEM]
High-density Signal Conditioners 10-RACK;型号: | 10AS-61 |
厂家: | M-SYSTEM |
描述: | High-density Signal Conditioners 10-RACK |
文件: | 总4页 (文件大小:145K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 10AS
High-density Signal Conditioners 10-RACK
[2] ALARM OUTPUT
1: Single (SPDT); Hi in power failure
2: Single (SPDT); Lo in power failure
DC ALARM
3: Dual (2 points SPDT); Hi in power failure
4: Dual (2 points SPDT); Lo in power failure
5: Hi/Lo (2 points SPDT); ON at alarm; OFF in power failure
7: Hi/Lo (2 points SPDT); ON at alarm and in power failure
8: Hi/Lo (2 points SPDT); OFF at alarm and in power failure
0: Specify
Functions & Features
• Providing relay contact closures at preset DC input levels
• Single or dual (Hi/Lo) trip
• Multi-turn screwdriver setpoint adjustments
Typical Applications
• Annunciator
• Various alarm applications
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank: none
/Q: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
MODEL: 10AS–[1][2]–R[3]
/C03: Rubber coating
ORDERING INFORMATION
• Code number: 10AS-[1][2]-R[3]
Specify a code from below for each [1] through [3].
(e.g. 10AS-62-R/Q)
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals at the front and via card-edge connector at the
rear; terminal cover provided
Use Ordering Information Sheet (No. ESU-1033) to specify
output code 0 specifications.
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
Output: M3.5 screw terminals (torque 0.8 N·m)
Power input: Supplied from card-edge connector
Screw terminal: Nickel-plated steel
• Special input range (For code 0)
• Specify the specification for option code /Q
(e.g. /C01)
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
[1] INPUT
Current
Setpoint adjustments: Multi-turn screwdriver adjustments
(front); -5 – +105 % independently
A: 4 – 20 mA DC (Input resistance 250 Ω)
D: 0 – 20 mA DC (Input resistance 50 Ω)
G: 0 – 1 mA DC (Input resistance 1000 Ω)
H: 10 – 50 mA DC (Input resistance 100 Ω)
Voltage
Hysteresis (deadband): Approx. 1 %
Front LEDs: Red light turns on when the coil is energized.
Power ON timer: Relays de-energized for approx. 2 seconds
after power is turned on.
3: 0 – 1 V DC (Input resistance 1 MΩ min.)
4: 0 – 10 V DC (Input resistance 1 MΩ min.)
5: 0 – 5 V DC (Input resistance 1 MΩ min.)
6: 1 – 5 V DC (Input resistance 1 MΩ min.)
0: Specify voltage (See INPUT SPECIFICATIONS)
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
■ DC Voltage: 0 – 300 V DC
Minimum span: 1 V
Offset: Max. 1.5 times span
Input resistance: ≥ 1 MΩ
http://www.m-system.co.jp/
10AS SPECIFICATIONS
ES-0881 Rev.13 Page 1/4
MODEL: 10AS
OUTPUT SPECIFICATIONS
■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
INSTALLATION
Current consumption: Approx. 80 mA with dual alarm
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 10BXx
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage: 380 V AC or 125 V DC
Maximum switching power: 120 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Weight: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Trip point repeatability: ±0.1 %
Mechanical life: 5 x 10 cycles
7
For maximum relay life with inductive loads, external
protection is recommended.
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: Approx. 0.5 sec. (0 – 100 % at 90 %
setpoint)
Alarm Trip Operation Terminal No. in parentheses
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to output to power)
•Output Code : 1, 2
(3–8)ON
Output
(5–8)ON
Input
(%)
1500 V AC @ 1 minute (input or output or power to ground)
0
50
50
50
50
▲
100
100
100
100
Setpoint
•Output Code : 3, 4
(3–8)ON
Output 1
(5–8)ON
(6–8)ON
Output 2
(7–8)ON
Input
(%)
0
▲
▲
Setpoint 2
Setpoint 1
•Output Code : 5, 7
(3–8)ON
Hi Output
(5–8)ON
(7–8)ON
Lo Output
(6–8)ON
Input
(%)
0
▲
▲
Lo Setpoint
Hi Setpoint
•Output Code : 8
(3–8)ON
Hi Output
(5–8)ON
(7–8)ON
Lo Output
(6–8)ON
Input
(%)
0
▲
▲
Lo Setpoint
Hi Setpoint
Trip Operation in Power Failure
•Output code 1: Terminals 3 – 8 turn ON
•Output code 2: Terminals 5 – 8 turn ON
•Output code 3
•Output code 4
•Output code 5, 8
•Output code 7
http://www.m-system.co.jp/
10AS SPECIFICATIONS
ES-0881 Rev.13 Page 2/4
MODEL: 10AS
EXTERNAL VIEW
1
5
2
6
Single or Dual Output 1
or High Alarm LED
3
Single or Dual Output 1
or High Setpoint Adj.
Dual Output 2
or Low Setpoint Adj.
Dual Output 2
or Low Alarm LED
7
8
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7–M3.5 SCREW
8 (.31)
2–4.3 (.17) dia.
MTG HOLE
TERMINAL COVER
1
5
2
6
3
7
8
3 (.12)
25 (.98)
51 (2.01)
130 (5.12)
http://www.m-system.co.jp/
10AS SPECIFICATIONS
ES-0881 Rev.13 Page 3/4
MODEL: 10AS
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■ SINGLE ALARM
■ Relay Protection
•AC Powered
Inductive
Load (Coil)
3
5
6
7
8
1H
1L
SETPOINT ADJ.
Comparator
Varistor or Spark
Quenching Circuit
LOAD
Low Drift
Amplifier
+
–
1
2
Ry
*
OUTPUT
INPUT
•DC Powered
Inductive
Load (Coil)
COM
Diode, Varistor or
CR Circuit
LOAD
POWER
■ DUAL ALARM
3
5
6
7
8
Hi ADJ. Lo ADJ.
Comparator
**
HI OUTPUT
Hi
Ry
Ry
Low Drift
Amplifier
+
–
1
2
*
INPUT
**
LO OUTPUT
Lo
COM
POWER
Relay actions are determined by output codes.
* Input shunt resistor incorporated for current input.
**With code 3, 4 (dual alarm), Output 1 is assigned to Hi,
while Output 2 is assigned to Lo terminals.
The diagram illustrates relay actions for the output code 5 or 8.
Specifications are subject to change without notice.
http://www.m-system.co.jp/
10AS SPECIFICATIONS
ES-0881 Rev.13 Page 4/4
相关型号:
©2020 ICPDF网 联系我们和版权申明