MODEL: 10DU
High-density Signal Conditioners 10-RACK
[1] OPTIONS
blank: none
/Q: With options (specify the specification)
CURRENT LOOP SUPPLY
(10 – 50 mA loop)
Functions & Features
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
• Powering a 10 – 50 mA DC current loop
• Isolation
• Shortcircuit protection
• Applicable to smart transmitters
/C02: Polyurethane coating
/C03: Rubber coating
Typical Applications
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals at the front and via card-edge connector at the
rear; terminal cover provided
• Various 2-wire transmitters
Connection
Input: M3.5 screw terminals (torque 0.8 N·m)
Output: Card-edge connector and M3.5 screw terminals
(torque 0.8 N·m)
Power input: Supplied from card-edge connector
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
MODEL: 10DU–H60-R[1]
SUPPLY OUTPUT
Output voltage: 24 – 28 V DC with no load
ORDERING INFORMATION
• Code number: 10DU-H60-R[1]
Specify a code from below for [1].
(e.g. 10D-H60-R/Q)
Current rating: ≤ 55mA DC
• Shortcircuit Protection
Current limited: Approx. 65 mA
Protected time duration: No limit
• Specify the specification for option code /Q
(e.g. /C01)
INPUT SPECIFICATIONS
Equivalent input impedance: Approx. 100 Ω at 50 mA
INPUT
Current
6.0
approx. 6.0
H: 10 – 50 mA DC
5.0
approx.
4.8
OUTPUT 1
Voltage
4.0
6: 1 – 5 V DC (Load resistance 50 kΩ min.)
10
30
50
INPUT CURRENT [mA]
OUTPUT 2
0: None
OUTPUT SPECIFICATIONS
The output goes below 0 % when the input is open.
POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
http://www.m-system.co.jp/
10DU SPECIFICATIONS
ES-0828 Rev.7 Page 1/3
MODEL: 10DU
INSTALLATION
Current consumption: Approx. 100 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 10BXx
Weight: 200 g (0.44 lb)
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
Supply output: ±3 % over voltage range
Output signal: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(input to output to power)
1500 V AC @ 1 minute (input or output or power to ground)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)
7–M3.5 SCREW
8 (.31)
2–4.3 (.17) dia.
MTG HOLE
TERMINAL COVER
1
5
2
6
3
7
8
3 (.12)
25 (.98)
51 (2.01)
130 (5.12)
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Z
S
2-WIRE
TRANSMITTER
Current
Limiter
+
+
–
1
2
3
8
7
–
+
OUTPUT
–
Isolation
+
mA
–
MONITOR
5
6
(10 – 50mA DC)
OUTPUT
POWER
http://www.m-system.co.jp/
10DU SPECIFICATIONS
ES-0828 Rev.7 Page 2/3
MODEL: 10DU
Specifications are subject to change without notice.
http://www.m-system.co.jp/
10DU SPECIFICATIONS
ES-0828 Rev.7 Page 3/3
相关型号:
©2020 ICPDF网 联系我们和版权申明