17RP-11P6-R [MSYSTEM]

Rack-mounted Power Transducers 17-RACK;
17RP-11P6-R
型号: 17RP-11P6-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted Power Transducers 17-RACK

文件: 总3页 (文件大小:107K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 17RP  
Rack-mounted Power Transducers 17-RACK  
OUTPUT  
Voltage  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
VAR TRANSDUCER  
Functions & Features  
• Providing a DC output signal in proportion to AC reactive  
AUXILIARY POWER SUPPLY  
power  
DC Power  
• DC output containing little ripple is ideal for computer  
R: 24 V DC  
input  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
• "Time division multiplication" method accepts distorted  
waveforms  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
Typical Applications  
• Centralized monitoring and control of power management  
system in a manufacturing facility or building  
Connection  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output: Connector  
Auxiliary power: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Voltage input to current input to output to  
auxiliary power  
Computation: Time division multiplication  
Overrange output: Approx. -10 to +120 %  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
MODEL: 17RP–1[1][2]6–R  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
ORDERING INFORMATION  
• Code number: 17RP-1[1][2]6-R  
• Voltage Input  
Operational range: 0 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
Specify a code from below for each [1] and [2].  
(e.g. 17RP-11P6-R)  
• Var range (e.g. LAG 1000 – LEAD 1000 var)  
• Current Input  
Operational range: 0 – 120 % of rating  
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10  
sec., 120% continuous  
CONFIGURATION  
1: 3-phase / 3-wire  
How To Determine Var Range  
Calibration Range [var] = (Measuring Range) ÷  
((VT Ratio) × (CT Ratio))  
[1] INPUT (unbalanced load)  
(Voltage must be balanced.)  
1: 110 V / 5 A AC  
Check that the required calibration range is within the  
available range in the table.  
2: 110 V / 1 A AC  
[example]  
3: 220 V / 1 A AC  
3-phase / 3-wire, measuring range 75 kvar,  
VT 220 / 110 V, CT 250 / 5 A  
4: 220 V / 5 A AC  
(75 × 10 [var])÷((220 / 110) × (250 / 5))= 750 [var]  
3
I INPUT RANGE  
3-phase / 3-wire  
[2] OUTPUT SIGNAL POLARITY  
P: Negative in lag, positive in lead  
BURDEN (VA)  
VOLT. CURR.  
INPUT  
AVAILABLE  
RANGE  
M: Negative in lead, positive in lag  
STD.RANGE  
110V/1A  
110V/5A  
220V/1A  
220V/5A  
200 var  
0.2  
0.1/ph  
0.5/ph  
0.1/ph  
0.5/ph  
100  
500  
240 var  
1200 var  
480 var  
/phase  
1000 var  
4
00 var  
200  
0.4  
/phase  
2000 var  
1000  
2400 var  
http://www.m-system.co.jp/  
17RP SPECIFICATIONS  
ES-2967 Rev.0 Page 1/3  
MODEL: 17RP  
OUTPUT SPECIFICATIONS  
OPERATION DIAGRAM (example)  
• Negative in lag, positive in lead  
OUT  
5V  
3
1
1000  
(Lag)  
0
1000Var  
(Lead)  
• Negative in lead, positive in lag  
OUT  
5V  
3
1
1000  
(Lag)  
0
1000Var  
(Lead)  
INSTALLATION  
Auxiliary power supply  
Current consumption: Approx. 40 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 40 to 85 % RH (non-condensing)  
Mounting: Standard Rack 17BXE  
Weight: 200 g (0.44 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±0.5 % (at 23°C ±10°C or 73.4°F ±18°F,  
45 – 65 Hz)  
Response time: ≤ 2 sec. (0 – 100 % ±1 %)  
Ripple: 1 %p-p max.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 500 V AC @ 1 minute (output to  
auxiliary power)  
2000 V AC @ 1 minute (voltage input to current input to  
output or auxiliary power)  
1500 V AC @1 minute (voltage input or current input or  
output or auxiliary power to ground)  
http://www.m-system.co.jp/  
17RP SPECIFICATIONS  
ES-2967 Rev.0 Page 2/3  
MODEL: 17RP  
CONNECTION DIAGRAM  
3-PHASE/3-WIRE  
SOURCE  
1
2 3  
VT  
FUSE  
FUSE  
FUSE  
U
u
P1  
P2  
P3  
5
6
7
V
V
v
v
U
u
K
K
k
1S  
1L  
3S  
3L  
1
2
3
4
OUTPUT  
k
CT  
l
l
AUXLIARY  
POWER  
L
L
LOAD  
DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
Specifications are subject to change without notice.  
http://www.m-system.co.jp/  
17RP SPECIFICATIONS  
ES-2967 Rev.0 Page 3/3  

相关型号:

17RP-12M6-R

Rack-mounted Power Transducers 17-RACK
MSYSTEM

17RP-12P6-R

Rack-mounted Power Transducers 17-RACK
MSYSTEM

17RP-13M6-R

Rack-mounted Power Transducers 17-RACK
MSYSTEM

17RP-13P6-R

Rack-mounted Power Transducers 17-RACK
MSYSTEM

17RP-14M6-R

Rack-mounted Power Transducers 17-RACK
MSYSTEM

17RP-14P6-R

Rack-mounted Power Transducers 17-RACK
MSYSTEM

17RR-D1-M-04-2K

Wire Terminal
AMPHENOL

17RR-D1-M-06-100

Wire Terminal
AMPHENOL

17RR-D1-M-06-2K

Wire Terminal
AMPHENOL

17RR-D1-M-11-2K

Wire Terminal
AMPHENOL

17RR-D2-F-01-2K

Wire Terminal
AMPHENOL

17RR-D2-M-02-10R

Wire Terminal
AMPHENOL