18HZ-2166-R [MSYSTEM]

Rack-mounted DCS Signal Conditioners 18-RACK;
18HZ-2166-R
型号: 18HZ-2166-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted DCS Signal Conditioners 18-RACK

DCS 分布式控制系统
文件: 总3页 (文件大小:95K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 18HZ  
Rack-mounted DCS Signal Conditioners 18-RACK  
POWER INPUT  
DC Power  
R: 24 V DC  
FREQUENCY TRANSDUCER  
Functions & Features  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
• Providing two DC output signals in proportion to deviation  
(±5 Hz) from center frequency (50 Hz or 60 Hz)  
• DC output containing little ripple is ideal for computer  
input  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
Typical Applications  
Connection  
• Centralized monitoring and control of power management  
system in manufacturing facility or building  
• Measuring frequency for UPS  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output 1: Connector  
Output 2: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Input to output 1 to output 2 to power  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
INPUT SPECIFICATIONS  
Operational range: 85 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
MODEL: 18HZ–[1][2]66–R  
Input burden: Approx. 1 VA  
ORDERING INFORMATION  
• Code number: 18HZ-[1][2]66-R  
Specify a code from below for each of [1] and [2].  
(e.g. 18HZ-1166-R)  
OUTPUT SPECIFICATIONS  
OPERATION DIAGRAM (example)  
OUT  
5V  
[1] FREQUENCY  
1: 45 – 55 Hz  
3
1
2: 55 – 65 Hz  
3: 45 – 65 Hz  
45  
55  
65 Hz  
[2] INPUT  
1: 110 V AC  
2: 220 V AC  
INSTALLATION  
Current consumption: Approx. 60 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18BXx or 18KBXx  
Weight: 150 g (0.33 lb)  
OUTPUT 1  
Voltage  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
OUTPUT 2  
Voltage  
PERFORMANCE in percentage of span  
Accuracy: ±1.0 %  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
Temp. coefficient: ±0.1 %/°C (±0.06 %/°F)  
Response time: ≤ 0.5 sec. (0 – 90 %)  
Ripple: 0.5 %p-p max. (100/120 Hz)  
Line voltage effect: ±0.1 % over voltage range  
18HZ SPECIFICATIONS  
ES-1870 Rev.6 Page 1/3  
http://www.m-system.co.jp/  
MODEL: 18HZ  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(input to output 1 or output 2 or power)  
500 V AC @ 1 minute  
(output 1 to output 2 to power)  
2000 V AC @1 minute  
(input or output or power to ground)  
CONNECTION DIAGRAM  
SOURCE  
1 2  
VT  
FUSE  
U
V
u
v
1
2
5
6
+
OUTPUT 2  
OUTPUT 1  
OUTPUT 2  
POWER  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
18HZ SPECIFICATIONS  
ES-1870 Rev.6 Page 2/3  
http://www.m-system.co.jp/  
MODEL: 18HZ  
Specifications are subject to change without notice.  
18HZ SPECIFICATIONS  
ES-1870 Rev.6 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

18HZ-2266-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18HZ-3166-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18HZ-3266-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JDL

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JDL-A066-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JDL-A166-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JDL-A266-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JDL-A366-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JDL-A466-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JF-666-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JF-666-R/1

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18JF-666-R/2

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM