18KYCH-AA-R/S [MSYSTEM]
Rack-mounted DCS Signal Conditioners 18K-RACK;型号: | 18KYCH-AA-R/S |
厂家: | M-SYSTEM |
描述: | Rack-mounted DCS Signal Conditioners 18K-RACK DCS 分布式控制系统 |
文件: | 总3页 (文件大小:108K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
MODEL: 18KYCH
Rack-mounted DCS Signal Conditioners 18K-RACK
GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw
terminals on the front and connector on the rear; terminal
cover provided
CONTROL OUTPUT ISOLATOR
(applicable to HART signal, opencircuit detection selectable)
Functions & Features
Connection
Input: Connector
• Takes 4 - 20 mA DC as input
Input monitor: M3.5 screw terminals (torque: 0.8 N·m)
Output: M3.5 screw terminals (torque: 0.8 N·m) and
connector
• Isolates and relays HART signals
• Opencircuit detection selectable
• Module can be retracted without removing wiring for an
insulation test
Power: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Input to output to power
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)
With power switch: Selectable from the front
(factory default: ON)
• Capable of monitoring input signals at front terminals
• Optional power switch
Opencircuit detection: Input current 0 mA when the output
loop is open.
Photo MOSFET Relay ON Resistance; 3 Ω max.
INPUT SPECIFICATIONS
■ DC Current: Input resistor incorporated
Input current: ≥ 0 mA
MODEL: 18KYCH–AA–R[1]
ORDERING INFORMATION
• Code number: 18KYCH-AA-R[1]
Specify a code from below for [1].
(e.g. 18KYCH-AA-R/S/B)
OUTPUT SPECIFICATIONS
The output goes below 0 % when the input is open.
HART COMMUNICATION
Transmission gain: Approx. -3 dB (within 1 – 3 kHz)
measured with 250 Ω at output
INPUT
Current
Loop impedance: 250 Ω ±10 %
A: 4 - 20 mA DC (Input resistance approx. 250Ω)
Communication directions: Bidirectional
OUTPUT
Current
INSTALLATION
Current consumption: Approx. 60 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18KBXx
Weight: 110 g (0.24 lb)
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
250 Ω ±10 % for HART communication
POWER INPUT
DC Power
R: 24 V DC
PERFORMANCE in percentage of span
Accuracy: ±0.1 %
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
[1] OPTIONS (multiple selections)
Power Switch
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (input to output to
power to ground )
blank: None
/S: With power switch
Opencircuit detection
blank: none
/B: Opencircuit detector
18KYCH SPECIFICATIONS
ES-0431 Rev.0 Page 1/3
http://www.m-system.co.jp/
MODEL: 18KYCH
EXTERNAL VIEW
■ WITH POWER SWITCH
7
8
5
6
2
Power Switch
Span Adj.
Zero Adj.
1
3
4
EXTERNAL DIMENSIONS unit: mm (inch)
2–M3
SCREW
8–M3.5
7 (.28)
SCREW
7 (.28)
24 (.94)
32 (1.26)
78 (3.07)
TERMINAL ASSIGNMENTS
7
8
5
6
1
2
3
4
18KYCH SPECIFICATIONS
ES-0431 Rev.0 Page 2/3
http://www.m-system.co.jp/
MODEL: 18KYCH
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
HART Isolation
Z
S
DC Isolation
*2
4 – 20mA DC
*1
Output
Driver
Opencircuit
Detector
Amplifier
+
−
5
6
3
4
7
8
1
Module Field Terminals
(Section A)
2
HHC INPUT MONITOR
250Ω
External Field Terminals
(Section A)
INPUT
(DCS Output, HHC *1)
*3
POWER
Use either of module or external field terminals.
*1. Hand-held communicator
*2. Included with option /B
*3. Included with option /S
Section A. Field Terminals
4 – 20mA DC
1
2
+
−
*1
R
L
OUTPUT
HHC
Specifications are subject to change without notice.
18KYCH SPECIFICATIONS
ES-0431 Rev.0 Page 3/3
http://www.m-system.co.jp/
相关型号:
18L-03P-044
Circular DIN Connector, 3 Contact(s), Male, Board Mount, Printed Wiring Pin Terminal, Plug
AMPHENOL
18L-03S-034
Circular DIN Connector, 3 Contact(s), Female, Board Mount, Printed Wiring Pin Terminal, Socket
AMPHENOL
©2020 ICPDF网 联系我们和版权申明