18PR-21-R [MSYSTEM]

Rack-mounted DCS Signal Conditioners 18-RACK;
18PR-21-R
型号: 18PR-21-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted DCS Signal Conditioners 18-RACK

DCS 分布式控制系统
文件: 总4页 (文件大小:117K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 18PR  
Rack-mounted DCS Signal Conditioners 18-RACK  
CAUTION  
1) This unit's output waveform is not uniform due to its  
scaling method. The user must be aware that it may be  
inconvenient for certain types of application.  
2) This unit is designed to accept at the maximum of 100  
kHz, which may cause errors due to chattering in the input  
pulses.  
PULSE SCALER  
Functions & Features  
• Converting pulse rate into convenient engineering unit for  
display on a totalizing counter or meter  
Use input relays which do not cause chattering (e.g.  
mercury relays). Other relays could be used only with a CR  
filter, for 10 Hz at maximum.  
Typical Applications  
• Positive displacement flowmeters and turbine flowmeters  
• Magnetic tachometers  
3) Use M-System’s Model M2PRU instead of this unit in  
conjunction with the pulse output from M-System’s power  
transducers.  
R
C = 1 µF  
R = 10kΩ  
PULSE  
SCALER  
Relay  
C
MODEL: 18PR–[1][2]–R  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
ORDERING INFORMATION  
• Code number: 18PR-[1][2]-R  
Connection  
Specify a code from below for each of [1] and [2].  
(e.g. 18PR-11-R)  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output: M3.5 screw terminals (torque 0.8 N·m)  
and connector  
• Input frequency range (e.g. 0 – 356.7 Hz)  
• Output frequency range (e.g. 0 – 1.00 Hz)  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
[1] INPUT  
Isolation: Input to output to power  
1: Dry contact (max. 100 kHz)  
Input pulse sensing: Capacitor coupled; detecting pulse rise  
Sensitivity adjustment: Single-turn screwdriver adjustment  
(front); 25 mVp-p – 5 Vp-p  
2: Voltage pulse (max. 100 kHz)  
Scaling factor adjustment: 10-position rotary switch; 0.9999  
[2] OUTPUT  
× 10 – 0.0001 × 10–6  
0
1: Open collector (max. frequency 20 kHz)  
2: 5 V pulse (max. frequency 20 kHz)  
3: Relay contact (max. frequency 2 Hz)  
4: 24 V pulse (max. frequency 20 Hz)  
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
18PR SPECIFICATIONS  
ES-1860 Rev.11 Page 1/4  
http://www.m-system.co.jp/  
MODEL: 18PR  
INPUT SPECIFICATIONS  
Dry Contact: Mechanical contact or open collector  
Max. frequency: 100 kHz  
OUTPUT SPECIFICATIONS  
■ Open Collector: 50 V DC @ 50 mA (resistive load)  
Frequency range: 0 – 20 kHz  
Pulse width time requirement: 5 μsec. min. (20 msec. min.  
for frequencies ≤ 10 Hz)  
ON pulse width: Approx. 30 μsec.  
Saturation voltage: 0.6 V DC  
Sensing: Approx. 7.5 V DC @ 1 mA  
ON/OFF level: ≤ 20 kΩ for ON, ≥ 100 kΩ for OFF  
Voltage Pulse: Square or sine waveforms*  
Max. frequency: 100 kHz  
Relay Contact: 120 V AC @ 200 mA (cos ø = 1)  
240 V AC @ 100 mA (cos ø = 1)  
24 V DC @ 200 mA (resistive load)  
Maximum switching voltage: 240 V AC or 30 V DC  
Maximum switching power: 24 VA or 4.8 W  
Minimum load: 5 V DC @ 10 mA  
Pulse width time requirement: 5 μsec. min. (20 msec. min.  
for frequencies ≤ 10 Hz)  
Input amplitude: 25 mVp-p – 50 Vp-p  
Minimum amplitude requirement  
With duty ratio 50 ±10 %  
Frequency range: 0 – 2 Hz  
ON pulse width: Approx. 30 msec.  
Relay life: ≥ 5 × 10  
≥ 10 cycles (electrical)  
5 V Pulse  
7
cycles (mechanical)  
(frequency: amplitude)  
5
0 – 2 kHz: 25 mVp-p  
0 – 20 kHz: 50 mVp-p  
Frequency range: 0 – 20 kHz  
Low pulse width: Approx. 30 μsec.  
High level: 5 V ±10 %  
0 – 40 kHz: 1 Vp-p  
0 – 100 kHz: 5 Vp-p  
With duty ratio other than 50 ±10 %  
(pulse width: amplitude)  
Low level: ≤ 0.5 V  
Load resistance: 600 Ω minimum  
24 V Pulse  
5 μsec.: 5 Vp-p  
10 μsec.: 3.5 Vp-p  
Frequency range: 0 – 20 Hz  
High pulse width: Approx. 30 msec.  
High level: 24 V ±10 %  
50 μsec.: 2 Vp-p  
100 μsec.: 1 Vp-p  
500 μsec.: 0.5 Vp-p  
Low level: ≤ 0.5 V  
Input impedance: 100 kΩ minimum  
Load current: 30 mA max.  
Load resistance: 800 Ω minimum  
*Voltage pulse examples  
25mV – 50V  
INSTALLATION  
0V  
Current consumption: Approx. 80 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18BXx or 18KBXx  
Weight: 150 g (0.33 lb)  
25mV – 50V  
0V  
25mV p-p  
– 50V p-p  
0V  
PERFORMANCE  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 1500 V AC @ 1 minute  
(input to output or power)  
500 V AC @ 1 minute (outut to power)  
1500 V AC @ 1 minute (input or output or power to ground)  
18PR SPECIFICATIONS  
ES-1860 Rev.11 Page 2/4  
http://www.m-system.co.jp/  
MODEL: 18PR  
EXTERNAL VIEW  
7
8
5
1
6
2
Connector  
Sensitivity Adj.  
Scaling Factor Adj.  
Digital Switches  
3
4
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
18PR SPECIFICATIONS  
ES-1860 Rev.11 Page 3/4  
http://www.m-system.co.jp/  
MODEL: 18PR  
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM  
SENSITIVITY  
ADJ.  
SCALING  
FACTOR ADJ.  
Isolation  
*
Pulse Volt.  
Amplifier  
Output  
Driver  
+
1
2
3
4
7
8
5
6
+
Scaler  
One-Shot  
+7.5V  
INPUT  
OUTPUT  
OUTPUT  
POWER  
*Dry contact input only.  
Specifications are subject to change without notice.  
18PR SPECIFICATIONS  
ES-1860 Rev.11 Page 4/4  
http://www.m-system.co.jp/  

相关型号:

18PR-22-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-23-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PR-24-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A1S

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A2

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A2S

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A3

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-266-R/A3S

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-766-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-766-R/A1S

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18PV-766-R/A2

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM