18RP-13M66-R [MSYSTEM]

Rack-mounted DCS Signal Conditioners 18-RACK;
18RP-13M66-R
型号: 18RP-13M66-R
厂家: M-SYSTEM    M-SYSTEM
描述:

Rack-mounted DCS Signal Conditioners 18-RACK

DCS 分布式控制系统
文件: 总3页 (文件大小:114K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 18RP  
Rack-mounted DCS Signal Conditioners 18-RACK  
OUTPUT 2  
Voltage  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
VAR TRANSDUCER  
Functions & Features  
• Providing two DC output signals in proportion to AC  
reactive power  
POWER INPUT  
DC Power  
• DC output containing little ripple is ideal for computer  
input  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
Typical Applications  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals on the front and connector on the rear; terminal  
cover provided  
• Centralized monitoring and control of power management  
system in a manufacturing facility or building  
Connection  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output 1: Connector  
Output 2: Connector  
Power input: Supplied from connector  
Screw terminal: Nickel-plated steel  
Isolation: Voltage input to current input to output 1 to  
output 2 to power  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
Span adjustment: 95 to 105 % (front)  
MODEL: 18RP–1[1][2]66–R  
ORDERING INFORMATION  
• Code number: 18RP-1[1][2]66-R  
Specify a code from below for each of [1] and [2].  
(e.g. 18RP-11P66-R)  
• Calibration range (e.g. lag 1000 – lead 1000 var)  
• VT ratio, CT ratio (e.g. VT 3300/110 V, CT 250/5 A)  
CONFIGURATION  
1: 3-phase / 3-wire  
[1] INPUT (unbalanced load)  
(Voltage must be balanced.)  
1: 110 V / 5 A AC  
2: 110 V / 1 A AC  
3: 220 V / 1 A AC  
4: 220 V / 5 A AC  
[2] OUTPUT SIGNAL POLARITY  
P: Negative in lag, positive in lead  
M: Negative in lead, positive in lag  
OUTPUT 1  
Voltage  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
18RP SPECIFICATIONS  
ES-1867 Rev.8 Page 1/3  
http://www.m-system.co.jp/  
MODEL: 18RP  
INPUT SPECIFICATIONS  
Frequency: 50 or 60 Hz  
INSTALLATION  
Current consumption: Approx. 80 mA  
Current Input  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 18BXx or 18KBXx  
Weight: 200 g (0.44 lb)  
Operational range: 0 – 120 % of rating  
Overload capacity: 1000 % of rating for 3 sec., 200 % for 10  
sec., 120 % continuous  
Voltage Input  
Operational range: 0 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
PERFORMANCE in percentage of span  
Accuracy: ±0.5 %  
Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)  
Response time: ≤ 1 sec. (0 – 90 %)  
Input Range  
How To Determine Var Range:  
Calibration Range [var] = Measuring Range ÷ ((VT Ratio) ×  
(CT Ratio))  
Ripple: 0.5 %p-p max. (50/60 Hz)  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(voltage input to current input to output 1 or output 2 or  
power)  
Check that the required calibration range is within the  
available range in the table. Specify this range when  
ordering.  
[example]  
500 V AC @ 1 minute (output 1 to output 2 to power)  
2000 V AC @ 1 minute (input or output or power to ground)  
3-phase / 3-wire, measuring range 75 kvar, VT 220 / 110 V,  
CT 250 / 5 A  
75 × 10 [var] ÷ ((220 ÷ 110) × (250 ÷ 5)) = 750 [var]  
3
3-phase / 3-wire  
INPUT  
BURDEN (VA)  
VOLT. CURR.  
AVAILABLE  
RANGE  
STD.RANGE  
0.1/phase  
0.2  
110V/1A  
110V/5A 1000 var  
220V/1A 400 var  
220V/5A 2000 var  
200 var  
100 – 240 var  
500 – 1200 var  
200 – 480 var  
1000 – 2400 var  
/phase  
0.5/phase  
0.1/phase  
0.5/phase  
0.4  
/phase  
OUTPUT SPECIFICATIONS  
OPERATION DIAGRAM (example)  
• Negative in lag, positive in lead  
OUT  
5V  
3
1
1000  
(Lag)  
0
1000Var  
(Lead)  
• Negative in lead, positive in lag  
OUT  
5V  
3
1
1000  
(Lag)  
0
1000Var  
(Lead)  
18RP SPECIFICATIONS  
ES-1867 Rev.8 Page 2/3  
http://www.m-system.co.jp/  
MODEL: 18RP  
CONNECTION DIAGRAM  
3-PHASE/3-WIRE  
SOURCE  
1
2
3
VT  
FUSE  
U
u
P1  
P2  
P3  
5
6
7
V
V
v
v
U
u
K
K
k
1S  
1L  
3S  
3L  
1
2
3
4
OUTPUT 1  
OUTPUT 2  
POWER  
k
CT  
l
l
L
L
LOAD  
EXTERNAL DIMENSIONS unit: mm (inch)  
2–M3  
SCREW  
8–M3.5  
7 (.28)  
SCREW  
7 (.28)  
24 (.94)  
32 (1.26)  
78 (3.07)  
TERMINAL ASSIGNMENTS  
7
8
5
6
1
2
3
4
Specifications are subject to change without notice.  
18RP SPECIFICATIONS  
ES-1867 Rev.8 Page 3/3  
http://www.m-system.co.jp/  

相关型号:

18RP-13P66-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RP-14M66-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RP-14P66-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-06-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-06-R/BL

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-16-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-16-R/BL

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-36-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-36-R/BL

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-46-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-46-R/BL

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM

18RS-56-R

Rack-mounted DCS Signal Conditioners 18-RACK
MSYSTEM