43AL1B [MSYSTEM]

Digital Panel Meters 43 Series;
43AL1B
型号: 43AL1B
厂家: M-SYSTEM    M-SYSTEM
描述:

Digital Panel Meters 43 Series

文件: 总4页 (文件大小:131K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 43AL1-B  
Digital Panel Meters 43 Series  
[4] MOUNTING BRACKET  
0: Without  
1: With  
LOOP POWERED DIGITAL METER  
(explosion-proof; outdoor enclosure; process meter)  
Functions & Features  
[5] OPTIONS (multiple selections)  
Enclosure Materials  
• Loop powered -1999 to 9999 compact digital meter  
• No external power source needed  
Blank: Diecast aluminium enclosure  
/S: Stainless steel enclosure  
• Optional stainless steel enclosure  
(TIIS flameproof approval not selectable)  
Other Options  
blank: none  
/Q: Option other than the above (specify the specification)  
SELECTABLE WIRING CONDUITS SPECIFIC TO EACH APPROVAL  
‘N’ marked combinations are not selectable.  
APPROVAL  
0
3
8
WIRING CONDUIT  
0
Y
Y
Y
Y
N
Y
Y
N
N
N
1
2
3
N
N
MODEL:43AL1–B–[1][2][3][4][5]  
ORDERING INFORMATION  
• Code number: 43AL1–B-[1][2][3][4][5]  
Specify a code from below for each of [1] through [5].  
(e.g. 43AL1-B-0001/S/Q)  
SPECIFICATIONS OF OPTION: Q  
EX-FACTORY SETTING  
/SET: Preset according to the Ordering Information Sheet  
(No. ESU-9426)  
• Specify the specification for option code /Q  
(e.g. /SET)  
RELATED PRODUCTS  
• Cable gland (model: BX-E-EXP)  
• Stopping plug (model: BX-E-SBP)  
[1] SAFETY APPROVAL  
0: None  
3: FM explosion-proof  
8: TIIS flameproof (CE not available)  
Confirm selectable combinations of approval and wiring  
conduit types in the table.  
PACKAGE INCLUDES...  
Cable gland: Two provided for TIIS flameproof type  
Model No.: BX-E-EXP  
Cable entries: Elastomeric sealing rings  
Wiring conduit size: G 1/2  
[2] TERMINAL BLOCK  
0: None (Connection to the rear of digital meter module)  
(TIIS approval not selectable)  
Material: Chrome-plated brass (entry)  
CR (sealing ring)  
Applicable wire size: 8 - 12 dia.  
Stopping plug: One provided for TIIS flameproof type  
Model No.: BX-E-SBP  
T: Incorporated  
[3] WIRING CONDUIT  
Wiring conduit size: G 1/2  
0: G 1/2  
Material: Diecast aluminium (plug)  
NBR (O-ring)  
1: 1/2 NPT  
2: M20 × 1.5  
• Mounting screws  
3: PG 13.5  
Bolt (M8 x 15): 4 pcs.  
Confirm selectable combinations of approval and wiring  
conduit types in the table.  
Spring washer for M8: 4 pcs.  
Material: Stainless steel 304  
Mounting bracket assembly (option)  
43AL1-B SPECIFICATIONS  
ES-9426 Rev.4 Page 1/4  
https://www.m-system.co.jp/  
MODEL: 43AL1-B  
Mounting bracket: 1 pcs.  
M10 U-bolt: 2 pcs.  
INPUT SPECIFICATIONS  
DC Current  
Nut for M10: 4 pcs.  
Current range: 3.75 to 22 mA DC  
Spring washer for M10: 4 pcs.  
Material: Stainless steel 304  
Applicable pipe: 1 1/2” min.; 2” max.  
Engineering unit label (1)  
Voltage drop: Approx. 3.5 V with 4 mA; approx. 3.7 V with  
20 mA (Equivalent input impedance: Approx. 185 Ω)  
(Use of the unit causes voltage drop. For 2-wire transmitter,  
be sure that the voltage by which 2-wire transmitter can  
operate is ensured including the voltage drop by other  
devices and wiring resistance.)  
GENERAL SPECIFICATIONS  
Degree of protection: NEMA 4X, IP66/IP67  
Wiring conduit: See ‘Ordering information.’  
Connection:  
INSTALLATION  
Operating temperature  
Without terminal block : Screwless spring terminal in  
Digital meter  
No safety approval: -40 to +70°C (-40 to +158°F)  
FM approval:  
Applicable wire size: 1.0 to 1.3 mm2, stripped length 8 mm  
-40 to +70°C (T5)  
With Terminal block : Euro terminal  
-40 to +60°C (T6)  
Applicable wire size: 0.2 to 4 mm  
2, stripped length 8 mm  
TIIS approval: -20 to +60°C (T6)  
Weight:  
Materials  
Meter housing: Flame-resistant resin (gray)  
Enclosure: Diecast aluminium standard; stainless steel  
casting optional (equivalent to type 316); silver color, epoxy  
resin coated  
• Unit  
Approx. 1.5 kg (3.3 lb), aluminium  
Approx. 4.0 kg (8.8 lb), stainless steel  
Approx. 2.0 kg (4.4 lb), TIIS flameproof  
• Mounting bracket assembly (option)  
Approx. 0.78 kg (1.72 lb)  
Isolation: Input to FE (Functional Earth) to outdoor enclosure  
A/D conversion: Σ – Δ  
Sampling rate: 10 times/sec. (100 msec.)  
Averaging: None or moving average  
Setting: (Front button)  
PERFORMANCE  
Accuracy: ±0.1 % rdg ±1 digit× scaling-multiple  
(When the scaling-multiple is less than 1, rounded up to 1.)  
Temp. coefficient: ±0.3 digits× scaling-multiple/℃  
(When the scaling-multiple is less than 1, rounded up to 1.)  
Scaling-multiple = | (Display Scaling Value B - Display  
Scaling Value A) ÷ (default Display Scaling Value B - default  
Display Scaling Value A) |  
• Scaled range  
• Moving average  
DISPLAY  
Display: 4 digits of 10.2 mm (.4”) height, 7-segment, red  
LED  
Display range: -1999 to 9999  
Dielectric strength: 1500 V AC @ 1 minute (input to  
enclosure; when FE (Functional Earth) is not connected to  
the enclosure.)  
Scaling range for measurement range: -1999 to 9999  
counts  
Decimal point position: 10-1, 10-2, 10-3 or none  
Zero indication: Higher-digit zeros are suppressed.  
Over-range indication: '-1999' or '9999' blinking for display  
values out of the display range. 'S.ERR' blinks surpassing  
the permissible range.  
500 V DC @ 1 minute  
(input to FE (Functional Earth))  
STANDARDS & APPROVALS  
EU conformity:  
Engineering unit indication: Sticker label attached  
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,  
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,  
cm, mm, m, m/sec, mm/min, cm/min, m/min,  
EMC Directive  
EMI EN 61000-6-4  
EMS EN 61000-6-2  
RoHS Directive  
m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec,  
Safety approval:  
m3  
/min, m  
3
/h, Nm /h, N·m, N/m , g, kg, kg/h,  
3
2
FM: Explosion-proof and Dust-ignition proof  
Class I, Division 1, Groups B, C and D  
Class II, Division 1, Groups E, F and G  
Class III, Division 1  
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,  
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.  
T5 and T6  
43AL1-B SPECIFICATIONS  
ES-9426 Rev.4 Page 2/4  
https://www.m-system.co.jp/  
MODEL: 43AL1-B  
(Class 3615)  
TIIS: Flameproof  
Ex d IIC T6  
EXTERNAL DIMENSIONS unit: mm [inch]  
STOPPING PLUG (TIIS flameproof)  
*
MOUNTING BRACKET  
(optional)  
CABLE GLAND  
(TIIS flameproof)  
G 1/2  
*
92 (3.62)  
110 (4.33)  
4–M8, 12 deep  
SPACE REQUIRED TO REMOVE COVER  
approx. 7 (.28)  
114 (4.49)  
110 (4.33)  
max. 86.5 (3.41)  
2–G1/2, 1/2NPT,  
M20x1.5 or PG13.5  
*Two cable glands and one plug are provided with TIIS flameproof type.  
Use them according to the field wiring requirements.  
43AL1-B SPECIFICATIONS  
ES-9426 Rev.4 Page 3/4  
https://www.m-system.co.jp/  
MODEL: 43AL1-B  
CONNECTION DIAGRAM  
WITHOUT TERMINAL BLOCK  
TERMINAL BLOCK INCORPORATED  
(Connetion to the rear of meter module)  
Terminal Block  
1
+
1
3
2
INPUT  
HI(+)  
2
3
4
1
3
INPUT  
LO(–)  
Meter  
Body  
FE  
2
FE  
Specifications are subject to change without notice.  
43AL1-B SPECIFICATIONS  
ES-9426 Rev.4 Page 4/4  
https://www.m-system.co.jp/  

相关型号:

43B002A

Industrial Control IC
ETC

43B002G

Industrial Control IC
ETC

43B005A

Industrial Control IC
ETC

43B005G

Industrial Control IC
ETC

43B010A

Industrial Control IC
ETC

43B010G

Industrial Control IC
ETC

43B015A

Industrial Control IC
ETC

43B015G

Industrial Control IC
ETC

43B030A

Industrial Control IC
ETC

43B030G

Industrial Control IC
ETC

43B050A

Industrial Control IC
ETC

43B050G

Industrial Control IC
ETC